22
5.6 - Electrical data - 30HXC + option 61 with high condensing temperature (options 150/150A)
30HXC
080 090
100 110 120 130 140 155 175
190
200 230 260
285
310 345 375
Power circuit
Nominal power supply (Un)*
V-ph-Hz 380-3-60
Voltage range
V
342-418
Control circuit supply
The control circuit is supplied via the factory-installed transformer
Max. operationg power input*
kW
107
119
131
146
162
180
196
214
231
277
279
312
347
415
429
462 553
Circuit A
kW
-
-
-
-
-
-
-
-
-
-
180
196
231
277
214
231
277
Circuit B
kW
-
-
-
-
-
-
-
-
-
-
99
116
116
138
214 231
277
Max. operating current drawn
(Un - 10%)**
A
203
225
246
275
304
337
367
400
431
517
522
582
646
776
800
862 1034
Circuit A
A
-
-
-
-
-
-
-
-
-
-
337
367
431
517
400 431
517
Circuit B
A
-
-
-
-
-
-
-
-
-
-
185
215 215
259
400
431
517
Maximum operating current drawn
(Un)**
A
184
204
224
250
276
306
334 364
392
470
474
530
588
705
728 784 940
Circuit A
A
-
-
-
-
-
-
-
-
-
-
306
334
392
470
364
392 470
Circuit B
A
-
-
-
-
-
-
-
-
-
-
168
196
196
235 364
392 470
Maximum starting current,
standard unit (Un)
†
A
301 301
320
356
347
430 465
496
534 648
1225
1374
1443
1775
1580 1656 2013
Circuit A
†
A
-
-
-
-
-
-
-
-
-
-
1050 1161 1230
1537 1192
1230
1537
Circuit B
†
A
-
-
-
-
-
-
-
-
-
-
906
1017 1017 1299 1192
1230
1537
Max. starting current/max.
current draw ratio, unit
1,54 1,40
1,37
1,36 1,33 1,35 1,30 1,28 1,25 1,36 2,48 2,41 2,26
2,49
2,04
1,94
2,11
Max. starting current/max.
current draw ratio, circuit A
-
-
-
-
-
-
-
-
-
-
3,29
3,25
2,89
3,23
3,07 2,89
3,23
Max. starting current/max.
current draw ratio, circuit B
-
-
-
-
-
-
-
-
-
5,18
4,77 4,77
5,46
3,07 2,89
3,23
Max. starting current - reduced
current start (Un)
†
A
std
std
std
std
std
std
std
std
std
std
799
932
1001
1196
1138 1214 1434
Circuit A
A
-
-
-
-
-
-
-
-
-
-
624
719
788
958
750
788 958
Circuit B
A
-
-
-
-
-
-
-
-
-
-
400
435
435
600
750
788 958
Max.starting current - red. current
start/max. current draw ratio, unit
std
std
std
std
std
std
std
std
std
std
1,62 1,64
1,57
1,68
1,47
1,42 1,51
Circuit A
-
-
-
-
-
-
-
-
-
-
1,96
2,01 1,85 2,01
1,93
1,85 2,01
Circuit B
-
-
-
-
-
-
-
-
-
-
2,29
2,04 2,04 2,52
1,93
1,85 2,01
Three-phase short circuit holding
current
kA
25
25
25
25
25
25
25
25
25
25
N/A N/A N/A N/A N/A N/A N/A
Circuit A
kA
-
-
-
-
-
-
-
-
-
-
25
25
25
25
25
25
25
Circuit B
kA
-
-
-
-
-
-
-
-
-
-
15
15
15
15
25
25
25
Customer standby capacity, unit
or circuit B, for evaporator water
pump connections
‡
kW
8
8
8
11
11
11
15
15
15
15
15
18
18
30
30
30
30
* Power input, compressor, at unit operating limits (evaporator water entering/leaving temperature = 15°C/10°C, condensing temperature = 68°C) and a nominal voltage
of 460 V (data given on the unit name plate).
** Maximum unit operating current at maximum unit power input.
†
Maximum instantaneous starting current (maximum operating current of the smallest compressor(s) + locked rotor current or reduced starting current of the largest
compressor)
‡
Current and power inputs not included in the values above
N/A Not applicable
5.7 - Compressor electrical data - 30HXC + option 60/61
Reference
Size
I nom.
MHA
LRA
LRA (Y)
LRA (S) 1 cp.
LRA (S) 2 cp.
06NW2123S6N
39
43
67
330
104
NA
NA
06NW2146S7N
46
49
80
330
104
NA
NA
06NW2174S7N
56
61
100
405
128
175
210
06NW2209S7N
66
73
120
485
153
205
250
06NW2250S7N
80
88
143
580
183
245
300
06NW2250S7E
80+
97
162
685
216
285
345
Legend
06NA
- Compressor for air-cooled units
N
- Non-economized compressor
E
- Economized compressor
I nom.
- Average current draw of the compressor at ARI conditions
MHA
- Must hold amperes (maximum operating current) at 342 V (A)
LRA
- Locked rotor current with across-the-line start
LRA (Y)
- Locked rotor current at reduced current (star/delta start-up mode)
LRA (S) 1 cp. - Start-up with reduced current with electronic starter (start-up duration 3 seconds max.) for one compressor per circuit
LRA (S) 2 cp. - Start-up with reduced current with electronic starter (start-up duration 3 seconds max.) for two compressors per circuit