14
4.2 - Electrical data 30HXC
30HXC
080 090
100 110 120 130 140 155 175
190
200 230 260
285
310 345 375
Power circuit
Nominal power supply (Un)*
V-ph-Hz 400-3-50
Voltage range
V
360-440
Control circuit supply
The control circuit is supplied via the factory-installed transformer
Nominal power input*
kW
53
62
67
76
80
89
102 112 121
129
140 164
192 195
221 250 263
Nominal current drawn*
A
101 115
127
143
149
168
190 207
226 234 255
294 337
354
399
448
477
Max. power input**
kW
87
97
108
119
131 144 161
175 192
212 223
257
288 318 350 384 424
Circuit A
kW
-
-
-
-
-
-
-
-
-
-
144 161
192
212
175 192
212
Circuit B
kW
-
-
-
-
-
-
-
-
-
-
79
96
96
106
175 192
212
Cosine phi, unit at full load
0.88 0.88 0.88 0.88 0.89 0.88 0.88 0.89 0.89 0.89 0.88 0.89 0.89 0.89 0.89 0.89 0.89
Total harmonic distortion***
%
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
Max. current drawn (Un - 10%)***
A
158
176 195
215 235
259 289
314 344
379
401 461
517
568 628 688
758
Circuit A
A
-
-
-
-
-
-
-
-
-
-
259 289
344
379
314 344
379
Circuit B
A
-
-
-
-
-
-
-
-
-
-
142
172 172 189
314 344
379
Max. current drawn (Un)***
A
143 160
177 195
213 236 263 285 312 344 365
419
468 516
570
624 688
Circuit A***
A
-
-
-
-
-
-
-
-
-
-
236 263 312 344 285 312 344
Circuit B***
A
-
-
-
-
-
-
-
-
-
-
129
156 156
172
285 312 344
Max. starting current, std. unit (Un)****
A
181 206 223
249 267 298
333 355 382 442 841
978 1027
1200
1129
1184
1373
Circuit A****
A
-
-
-
-
-
-
-
-
-
-
712
822
871
1028 844
871
1028
Circuit B****
A
-
-
-
-
-
-
-
-
-
-
605
715 715
856 844
871
1028
Max. starting current/max. current
draw ratio, unit
1.26 1.28 1.26 1.27 1.25 1.26 1.27 1.24 1.22 1.28 2.31 2.33 2.19 2.32 1.98 1.89 1.99
Max. starting current/max. current
draw ratio, circuit A
-
-
-
-
-
-
-
-
-
-
3.02 3.13 2.79 2.99 2.96 2.79 2.99
Max. starting current/max. current
draw ratio, circuit B
-
-
-
-
-
-
-
-
-
4.70 4.58 4.58 4.97 2.96 2.79 2.99
Max. starting current - reduced current
start (Un)****
A
std.
std.
std.
std.
std.
std.
std.
std.
std.
std.
636
683
732
824 834
889 997
Circuit A
A
std.
std.
std.
std.
std.
std.
std.
std.
std.
std.
507 527 576
652
549 576
652
Circuit B
A
std.
std.
std.
std.
std.
std.
std.
std.
std.
std.
330
370 370
385
549 576
652
Max. starting current - red. current
start/max. current draw ratio, unit
std.
std.
std.
std.
std.
std.
std.
std.
std.
std.
1.74 1.63 1.56 1.60 1.46 1.42 1.45
Circuit A
std.
std.
std.
std.
std.
std.
std.
std.
std.
std.
2.15 2.00 1.84 1.89 1.93 1.84 1.98
Circuit B
std.
std.
std.
std.
std.
std.
std.
std.
std.
std.
2.56 2.37 2.37 2.24 1.93 1.84 1.89
Three-phase short circuit holding
current
kA
25
25
25
25
25
25
25
25
25
25
N/A N/A N/A N/A N/A N/A N/A
Circuit A
kA
-
-
-
-
-
-
-
-
-
-
25
25
25
25
25
25
25
Circuit B
kA
-
-
-
-
-
-
-
-
-
-
15
15
15
15
25
25
25
Customer standby capacity, unit or
circuit B, for evaporator water pump
connections†
kW
8
8
8
11
11
11
15
15
15
15
15
18
18
30
30
30
30
* Standard Eurovent conditions: Evaporator entering/leaving water temperature 12°C and 7°C. Condenser entering/leaving water temperature 30°C/35°C.
** Power input, compressor, at unit operating limits (evaporator water entering/leaving temperature = 15°C/10°C, condenser entering/leaving water temperature =
45°C/50°C) and a nominal voltage of 400 V (data given on the unit name plate).
*** Maximum unit operating current at maximum unit power input.
**** Maximum instantaneous starting current (maximum operating current of the smallest compressor(s) + locked rotor current or reduced starting current of the largest
compressor)
† Current and power inputs not included in the values above.
N/A Not applicable.
Summary of Contents for 30HXC Series
Page 49: ......