15
4.3 - Compressor electrical data 30HXC
Reference
Size
I nom.
MHA
LRA
LRA (Y)
LRA (S) 1 cp
LRA (S) 2 cp
06NW2146S7N
39
50
79
344
109
NA
NA
06NW2174S7N
46
60
97
423
134
NA
NA
06NW2209S7N
56
71
117
506
160
260
350
06NW2250S7N
66
86
142
605
191
330
400
06NW2300S5N
80
105
172
715
226
370
420
06NW2300S5E
80+
114
189
856
270
385
480
Legend
06NW
- Compressor for water-cooled units
N
- Non-economized compressor
E
- Economized compressor
I nom.
- Average current draw of the compressor at Eurovent conditions (A)
MHA
- Must hold amperes (maximum operating current) at 360 V (A)
LRA
- Locked rotor current with across-the-line start (A)
LRA (Y)
- Locked rotor current at reduced current (star/delta start-up mode) (A)
LRA (S) 1 cp. - Start-up with reduced current (A) with electronic starter (start-up duration 3 seconds max.) for one compressor per circuit
LRA (S) 2 cp. - Start-up with reduced current (A) with electronic starter (start-up duration 3 seconds max.) for two compressors per circuit
4.4 - Electrical data for 30HXC units with high condensing temperatures (option 150/150A)
30HXC
080 090
100 110 120 130 140 155 175
190
200 230 260
285
310 345 375
Power circuit
Nominal power supply (Un)*
V-ph-Hz 400-3-50
Voltage range
V
360-440
Control circuit supply
The control circuit is supplied via the factory-installed transformer
Max. power input*
kW
108
122
136
149
163
180
196
213
229
287
278
310
343
431
426
458
574
Circuit A
kW
-
-
-
-
-
-
-
-
-
-
180
196
229
287
213
229 287
Circuit B
kW
-
-
-
-
-
-
-
-
-
-
98
114
114
144
213
229 287
Max. current drawn (Un - 10%)**
A
198
223
247
271 295
325 355
385
415
516
502
562
622
774
770
830 1032
Circuit A
A
-
-
-
-
-
-
-
-
-
-
325
355
415
516
385
415 516
Circuit B
A
-
-
-
-
-
-
-
-
-
-
177
207
207
258
385
415 516
Maximum current drawn (Un)**
A
180 203
225
246
268
295
323
350
377
469
456
512
566
704
700
754 938
Circuit A
A
-
-
-
-
-
-
-
-
-
-
295
323
377
469
350
377 469
Circuit B
A
-
-
-
-
-
-
-
-
-
-
161
189
189
235
350
377 469
Maximum starting current,
standard unit (Un)***
A
281
316
338
382
404
437
521
548
576
635
1255
1549
1603
1734 1737 1792 1969
Circuit A***
A
-
-
-
-
-
-
-
-
-
-
1094
1360 1415 1500
1387
1415 1500
Circuit B***
A
-
-
-
-
-
-
-
-
-
-
960
1226 1226 1265
1387
1415 1500
Max. starting current/max. current
draw ratio, unit
1.56 1.56 1.51 1.55 1.51 1.48 1.62 1.57 1.53 1.35 2.75 3.03 2.83 2.46 2.48 2.38 2.10
Max. starting current/max. current
draw ratio, circuit A
-
-
-
-
-
-
-
-
-
-
3.71 4.22 3.75 3.19 3.97 3.75 3.19
Max. starting current/max. current
draw ratio, circuit B
-
-
-
-
-
-
-
-
-
5.96 6.50 6.50 5.39 3.97 3.75 3.19
Max. starting current - reduced
current start (Un)***
A
std.
std.
std.
std.
std.
std.
std.
std.
std.
std.
870
933
987
1129
1121
1176
1364
Circuit A
A
std.
std.
std.
std.
std.
std.
std.
std.
std.
std.
709
744
799
895
771
799 895
Circuit B
A
std.
std.
std.
std.
std.
std.
std.
std.
std.
std.
435
490
490
510
771
799
895
Max.starting current - red. current
start/max. current draw ratio, unit
std.
std.
std.
std.
std.
std.
std.
std.
std.
std.
1.91 1.82 1.75 1.60 1.60 1.56 1.45
Circuit A
std.
std.
std.
std.
std.
std.
std.
std.
std.
std.
2.40 2.31 2.12 1.91 2.21 2.12 1.91
Circuit B
std.
std.
std.
std.
std.
std.
std.
std.
std.
std.
2.70 2.60 2.60 2.17 2.21 2.12 1.91
Three-phase short circuit holding
current
kA
25
25
25
25
25
25
25
25
25
25
N/A N/A N/A N/A N/A N/A N/A
Circuit A
kA
-
-
-
-
-
-
-
-
-.
-
25
25
25
25
25
25
25
Circuit B
kA
-
-
-
-
-
-
-
-
-
-
15
15
15
15
25
25
25
Customer standby capacity, unit
or circuit B, for evaporator
water pump connections†
kW
8
8
8
11
11
11
15
15
15
15
15
18
18
30
30
30
30
* Power input, compressor, at unit operating limits (evaporator water entering/leaving temperature = 15°C/10°C, condensing temperature = 68°C) and a nominal voltage
of 400 V (data given on the unit name plate).
** Maximum unit operating current at maximum unit power input.
*** Maximum instantaneous starting current (maximum operating current of the smallest compressor(s) + locked rotor current or reduced starting current of the largest
compressor)
† Current and power inputs not included in the values above
N/A Not applicable