13
4 - PHYSICAL AND ELECTRICAL DATA - STANDARD 50HZ APPLICATION
4.1 - Physical data 30HXC
30HXC
080 090
100 110 120 130 140 155 175
190
200 230 260
285
310 345 375
Sound levels - standard unit
Sound power level
(1)
dB(A)
94
94
94
94
94
97
98
100 101
101
99
101
102
102
103
104 104
Sound pressure level at 1 m
(2)
dB(A)
77
77
77
77
76
79
80
82
83
83
80
82
83
83
84
85
85
Operating weight
kg
2274 2279
2302 2343 2615
2617 2702 2712
3083
3179 3873
4602 4656
4776
5477
5553
5721
Compressor size
Semi-hermetic, twin-screw
The compressor size is identified by its nominal cooling capacity in tons of refrigeration
(1 ton = 3.517 kW)
Circuit A
39
46
46
56
56
66
80
80
80
80+ 66/56 80/56 80/80 80+/80+ 80/66 80/80 80+/80+
Circuit B
39
39
46
46
56
56
56
66
80
80+ 66
80
80
80+
80/66 80/80 80+/80+
Refrigerant - standard unit
(3)
R-134a
Circuit A
kg
33
33
32
31
49
51
48
51
54
56
92
115
117
117
109
104
119
teqCO
2
47
47
46
44
70
73
69
73
77
80
132
164
167
167
156
149 170
Circuit B
kg
34
34
30
35
52
47
48
50
50
59
54
63
75
75
106
102
137
teqCO
2
49
49
43
50
74
67
69
72
72
84
77
90
107
107
152
146
196
Oil - standard unit
(4)
Polyolester oil CARRIER SPEC. PP 47-32
Circuit A/B
l
17/17 17/17 17/17 17/17 17/17 17/17 17/17 17/17 17/17 17/17 30/17 30/17 30/17 30/17
34/34 34/34 34/34
Capacity control
PRO-DIALOG Plus control
No. of control steps
6
6
6
6
6
6
6
6
6
6
8
8
8
8
10
10
10
Minimum step capacity
%
19
19
21
19
21
19
17
19
21
21
14
14
14
14
10
10
10
Evaporator
Shell and tube with internally finned copper tubes
Net water volume
l
50
50
58
69
65
65
75
75
88
88
126
155
170
170
191
208 208
Water connections
Victaulic connections
Inlet/outlet
in
4
4
4
5
5
5
5
5
5
5
6
6
6
6
8
8
8
Drain and vent (NPT)
in
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
Max. water-side operating pressure
kPa
1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000
1000 1000 1000
Condenser
Shell and tube with internally finned copper tubes
Net water volume
l
48
48
48
48
78
78
90
90
108
108 141
190
190
190
255
255 255
Water connections
Victaulic connections
Inlet/outlet
in
5
5
5
5
5
5
5
5
6
6
6
8
8
8
8
8
8
Drain and vent (NPT)
in
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
Max. water-side operating pressure
kPa
1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000
1000 1000 1000
(1)
In dB ref=10-12 W, (A) weighting. Declared dualnumber noise emission values in accordance with ISO 4871 (with an associated uncertainty of +/-3dB(A)). Measured in
accordance with ISO 9614-1 and certified by Eurovent.
(2)
In dB ref 20µPa, (A) weighting. Declared dualnumber noise emission values in accordance with ISO 4871 (with an associated uncertainty of +/-3dB(A)). For
information, calculated from the sound power level Lw(A).
(3)
Values shown are guidelines only. Please refer to the unit nameplate.
(4)
For options 150 and 150A the units are supplied with an additional charge of 3 litres per compressor.