background image

6

Consult Carrier Service for this type of test. Carrier mentions here 

only the principle of a test without removing the pressure switch:

 

-

Verify and and record the setpoints of pressure 

switches and relief devices (valves and possible 

rupture discs)

 

-

Be ready to switch-off the main disconnect switch of 

the power supply if the pressure switch does not 

trigger (avoid over-pressure or excess gas in case of 

valves on the high-pressure side with the recovery 

condensers)

 

-

Connect a calibrated pressure gauge (the values 

displayed on the user interface may be inaccurate in 

an instant reading because of the scanning delay 

applied in the control)

 

-

Neutralise the HP soft value

 

-

Cut the condenser water flow

 

-

Check the cut-off value

 

-

Reactivate HP soft value

 

-

Reactivate manually HP switch.

CAUTION: If the test leads to replacing the pressure switch, it 

is necessary to recover the refrigerant charge, these pressure 

switches are not installed on automatic valves (Schraeder type).

At least once a year thoroughly inspect the protection devices 

(valves). If the machine operates in a corrosive environment, 

inspect the protection devices more frequently. 

Regularly carry out leak tests and immediately repair any leaks.

Ensure regularly that the vibration levels remain acceptable 

and close to those at the initial unit start-up.

Before  opening  a  refrigerant  circuit,  purge  and  consult  the 

pressure gauges.

Change  the  refrigerant  when  there  are  equipment  failures, 

following a procedure such as the one described in NF E29-795 

or carry out a refrigerant analysis in a specialist laboratory.

If the refrigerant circuit remains open for longer than a day after 

an intervention (such as a component replacement), the openings 

must be plugged and the circuit must be charged with nitrogen 

(inertia principle). The objective is to prevent penetration of 

atmospheric humidity and the resulting corrosion on the internal 

walls and on non-protected steel surfaces.

CAUTION:

1.  Any handling of refrigerant contained in this product must 

comply with the F-Gas Directive N° 517/2014 and any other 

applicable local legislation.

2.  Ensure  that  the  refrigerant  is  never  released  to  the 

atmosphere during installation, maintenance or equipment 

disposal. 

3.  The deliberate gas release into the atmosphere is strictly 

not allowed.

4.  If a refrigerant leak is detected, ensure that it is stopped 

and repaired as quickly as possible.

5.  Only  a  qualified  and  certified  personnel  can  perform 

installation operations, maintenance, refrigerant circuit 

leak test as well as the equipment disposal and the refrigerant 

recovering.

6.  The gas recovery for recycling, regeneration or destruction 

is at customer charge.

7.  The customer has to carry out periodic leak tests

System WITHOUT 

leakage detection

No check

12 months 6 months

3 months

System WITH leakage 

detection

No check

24 months 12 months 6 months

Refrigerant charge/circuit 

(CO

2

 equivalent)

 < 5 tons

5 ≤ charge < 

50 tons

50 ≤ charge 

< 500 tons

Charge > 

500 tons*

Refrigerant 

charge/

Circuit (kg)

R134A 

(GWP 1430)

Charge < 

3.5 kg

3.5 ≤ charge 

< 34.9 kg

34.9 ≤ 

charge < 

349.7 kg

Charge > 

349.7 kg

R407C 

(GWP 1774)

Charge < 

2.8 kg

2.8 ≤ charge 

< 28.2 kg

28.2 ≤ 

charge < 

281.9 kg

Charge > 

281.9 kg

R410A 

(GWP 2088)

Charge < 

2.4 kg

2.4 ≤ charge 

< 23.9 kg

23.9 ≤ 

charge < 

239.5 kg

Charge > 

239.5 kg

HFO’s: 

R1234ze

No requirement

* From 01/01/2017, units must be equipped with a leakage detection system

8.  A logbook must be established for the systems that require 

a tightness check. It should contain the quantity and the 

type  of  fluid  present  within  the  installation  (added  and 

recovered),  the  quantity  of  recycled  fluid/regenerated/

destroyed, the date and output of the leak test, the designation 

of the operator and its belonging company, etc.

9.  Contact  your  local  dealer  or  installer  if  you  have  any 

questions.

Protection device checks (EN 378):

The safety devices must be checked on site once a year for safety 

devices (see  chapter  11.3  -  Highpressure  safety switch),  and 

every five years for external overpressure devices (external relief 

valves).

The company or organisation that conducts a pressure switch test 

shall establish and implement a detailed procedure to fix:

 

-

Safety measures

 

-

Measuring equipment calibration

 

-

Validating operation of protective devices

 

-

Test protocols

 

-

Recommissioning of the equipment.

Summary of Contents for 30HXC Series

Page 1: ...INSTALLATION OPERATION AND MAINTENANCE INSTRUCTIONS Screw Compressor Water Cooled Liquid Chillers 30HXC 080 375 Original instructions Nominal cooling capacity 30HXC 286 1300 kW 50 Hz 60Hz...

Page 2: ...nsing temperature options 150 150A 19 5 4 Physical data 30HXC option 61 380V 3ph 60Hz 20 5 5 Electrical data 30HXC option 61 21 5 6 Electrical data 30HXC option 61 with high condensing temperature opt...

Page 3: ...0 11 MAIN OPTIONS AND ACCESSORIES 41 11 1 Compressor suction valves option 92 42 11 2 Electric protection level of the 30HXC control boxes to IP44C option 20 42 11 3 Tropicalised control box for 30HXC...

Page 4: ...unit more than 15 Safety is only guaranteed if these instructions are carefully followed If this is not the case there is a risk of material deterioration and injuries to personnel Never cover any pro...

Page 5: ...r pressure The units are intended to be stored and operate in an environment where the ambient temperature must not be less than the lowest allowable temperature indicated on the nameplate See section...

Page 6: ...omplywiththeF GasDirectiveN 517 2014andanyother applicable local legislation 2 Ensure that the refrigerant is never released to the atmosphereduringinstallation maintenanceorequipment disposal 3 The d...

Page 7: ...for the system and the refrigerant type used must be within easy reach Do not siphon refrigerant Avoid contact with liquid refrigerant on the skin or splashing it into the eyes Use safety goggles Was...

Page 8: ...ATTENTION No part of the unit must be used as a walk way rack or support Periodically check and repair or if necessary replace any component or piping that shows signs of damage The refrigerant lines...

Page 9: ...rams During the installation test national regulations must be followed If no national regulation exists standard EN 378 can be used as a guide External visual installation checks Ensure that the mach...

Page 10: ...r to the certified dimensional drawings supplied with the unit when designing an installation 30HXC 080 30HXC 090 30HXC 100 30HXC 110 A D B 600 500 4 700 4 3 C E 3 3 F 1 2 Legend All dimensions are in...

Page 11: ...imensional drawings supplied with the unit when designing an installation 4 2 E 500 B 3 A C D 700 3 4 500 3 F 1 Legend All dimensions are in mm Evaporator Condenser Clearances required for operation a...

Page 12: ...nces for air flow as follows Top do not restrict in any way In case of multiple chillers up to four units the respective clearance between them should be increased from 1830 to 2000 mm for the side sp...

Page 13: ...nimum step capacity 19 19 21 19 21 19 17 19 21 21 14 14 14 14 10 10 10 Evaporator Shell and tube with internally finned copper tubes Net water volume l 50 50 58 69 65 65 75 75 88 88 126 155 170 170 19...

Page 14: ...io circuit A 3 02 3 13 2 79 2 99 2 96 2 79 2 99 Max starting current max current draw ratio circuit B 4 70 4 58 4 58 4 97 2 96 2 79 2 99 Max starting current reduced current start Un A std std std std...

Page 15: ...B A 161 189 189 235 350 377 469 Maximum starting current standard unit Un A 281 316 338 382 404 437 521 548 576 635 1255 1549 1603 1734 1737 1792 1969 Circuit A A 1094 1360 1415 1500 1387 1415 1500 Ci...

Page 16: ...cal to those of the standard 30HXC units The only difference is in the diameter of the incoming field wiring connection described in the chapter Recommended selection Refer to the dimensional drawings...

Page 17: ...19 21 19 17 19 21 21 14 14 14 14 10 10 10 Evaporator Shell and tube with internally finned copper tubes Net water volume l 50 50 58 69 65 65 75 75 88 88 126 155 170 170 191 208 208 Water connections V...

Page 18: ...87 1 91 Max starting current max current draw ratio circuit A 2 88 3 04 2 73 2 83 2 88 2 73 2 83 Max starting current max current draw ratio circuit B 4 45 4 46 4 46 4 66 2 88 2 73 2 83 Max starting c...

Page 19: ...2 24 Max starting current max current draw ratio circuit A 3 56 3 52 3 11 3 48 3 32 3 11 3 48 Max starting current max current draw ratio circuit B 5 66 5 23 5 23 5 96 3 32 3 11 3 48 Max starting curr...

Page 20: ...10 10 Evaporator Shell and tube with internally finned copper tubes Net water volume l 50 50 58 69 65 65 75 75 88 88 126 155 170 170 191 208 208 Water connections Victaulic connections Inlet outlet i...

Page 21: ...77 1 81 Max starting current max current draw ratio circuit A 2 67 2 81 2 54 2 63 2 67 2 54 2 63 Max starting current max current draw ratio circuit B 4 06 4 08 4 08 4 25 2 67 2 54 2 63 Max starting...

Page 22: ...std std std std std std std 1 62 1 64 1 57 1 68 1 47 1 42 1 51 Circuit A 1 96 2 01 1 85 2 01 1 93 1 85 2 01 Circuit B 2 29 2 04 2 04 2 52 1 93 1 85 2 01 Three phase short circuit holding current kA 2...

Page 23: ...n range allows the production of glycol water solution down to 10 C with ethylene glycol at 35 by weight or down to 7 C with propylene glycol at 30 by weight The precision of these amounts is critical...

Page 24: ...eration permitted but performances is not optimized Condenser entering water temperature C Condenser entering water temperature C Evaporator leaving water temperature C 50 48 44 20 15 13 D C 7 0 4 13...

Page 25: ...evaporator is equipped with heat insulation of 38 mm thick polyurethane foam Cooler pressure drop 30HXC low brine version Pure water flow rate l s Pressure drop kPa 0 01 0 1 1 10 100 1000 1 10 100 HXC...

Page 26: ...ing temperature 50 C at full load 4 For low evaporator leaving temperatures 4 C and 6 C order option 5 Legend A Standard unit operating at full load B Standard unit operating at reduced load C Units o...

Page 27: ...ary for stable operation and accurate temperature control It is often necessary to add a buffer water tank to the circuit in order to achieve the required volume The tank must itself be internally baf...

Page 28: ...ser pressure drop curve Pressure drop kPa Water flow rate l s Note The dotted part of the curves corresponds to the flow values only permitted for closed circuits Legend 1 30HXC 080 090 100 110 2 30HX...

Page 29: ...ble section see table Recommended wire sections 30HXC A B C D E F G H Standard Circuit A 310 375 400A 56 25 4 1492 6 314 1824 314 10 5 Circuit B 310 345 400A 56 25 4 1492 6 314 1824 314 10 5 375 630A...

Page 30: ...s disconnect switches and branch sections designed to supply the evaporator and condenser pump power input IMPORTANT Generally the recommendations of IEC 60364 are accepted as compliance with the requ...

Page 31: ...IMPORTANT Before connection of the main power cables L1 L2 L3 on the terminal block it is imperative to check the correct order of the 3 phases before proceeding to the connection on then terminal blo...

Page 32: ...itches are indicated by a 1 8 4 3 Selection table of minimum and maximum wire sections 400V 3ph 50Hz option 150 30HXC Minimum wire section mm2 Wire type L m Maximum wire section mm2 Wire type L m 080...

Page 33: ...E Al 265 2 x 95 XLPE Cu 270 375 Circuit A 1 x 150 XLPE Cu 190 2 x 185 XLPE Al 270 2 x 120 XLPE Cu 280 200 Circuit B 1 x 50 XLPE Cu 160 1 x 120 XLPE Al 205 1 x 70 XLPE Cu 205 230 Circuit B 1 x 70 XLPE...

Page 34: ...u 190 2 x 240 XLPE Cu 295 Power supply wire section see diagram in chapter Electrical connection 8 4 6 Selection table of minimum and maximum wire sections 380V 3ph 60Hz option 61 30HXC Minimum wire s...

Page 35: ...PE Cu 190 2 x 185 XLPE Al 270 1 x 240 XLPE Cu 235 260 Circuit A 1 x 240 XLPE Cu 190 2 x 240 XLPE Al 280 2 x 150 XLPE Cu 290 285 Circuit A 1 x 240 XLPE Cu 190 2 x 240 XLPE Cu 295 310 Circuit A 1 x 185...

Page 36: ...any start up verify that the heat exchange fluid is compatible with the materials and the water circuit coating In case additives or other fluids than those recommended by Carrier are used ensure tha...

Page 37: ...second B Initialisation validation Release the button for between 1 and 5 seconds C Threshold control Press for the number of seconds that corresponds to the required setpoint pressing for 10 seconds...

Page 38: ...ator flow stopped to allow safe pressure equilibrium Special attention has to be given to the hydraulic design when option 152 is selected in order to maintain the condenser flow even when the 0 10V s...

Page 39: ...se a flooded evaporator The water circulates in the tubes and the refrigerant is on the outside in the shell One vessel is used to serve both refrigerant circuits There is a center tube sheet which se...

Page 40: ...oint on until the initialization the processor counts the total number of open and closed steps it has sent to each valve 10 4 Economizer Economizers are installed on 30HXC 190 285 and 375 The economi...

Page 41: ...um water side service pressure to 21 bar standard 10 bar Covers applications with a high water column condenser side typically high buildings 080 375 Reversed evaporator water connections 107 Evaporat...

Page 42: ...get the best performance from your HVAC unit improved cooling performance reduced power consumption prevention of accidental component failure prevention of major time consuming and costly interventio...

Page 43: ...rsunder normal operation The 30HXC metering device is designed to work properly under these conditions 1 Make sure that the circuit is running at a full load condition TocheckwhethercircuitAisfullyloa...

Page 44: ...sor 2 Manually force the operation of the oil solenoid valve in order to press the internal valve shutter onto its seat 3 Close the oil filter service valve Bleed pressure from the filter cavity throu...

Page 45: ...the bottom of its stroke If it is believed that the valve is not working properly contact your Carrier service department for further checks on output signals on EXV module wire connections continuity...

Page 46: ...Additional air handling units and accessories Preliminary equipment check Is there any shipping damage If so where Will this damage prevent unit start up Unit is level in its installation Power supply...

Page 47: ...power company for assistance All incoming power voltage is within rated voltage range Check cooler water loop Water loop volume litres Calculated volume litres 3 25 litres nominal kW capacity for air...

Page 48: ...t Condenser water sensors Water valve type If installed To start the chiller WARNING Be sure that all service valves are open and all pumps are on before attempting to start this machine Once all chec...

Page 49: ......

Page 50: ...es order No 13050 03 2011 Manufacturer Carrier SCS Montluel France Manufacturer reserves the right to change any product specifications without notice Printed in the European Union www eurovent certif...

Reviews: