background image

(1.) Obtain average yearly heat value for local gas supply.

(2.) Obtain average yearly specific gravity for local gas

supply.

(3.) Verify the furnace model. Table 8 can only be used for

model 58EJB Furnaces.

(4.) Find natural gas heat value and specific gravity in

Table 8.

(5.) Follow heat value line and specific gravity line to

point of intersection to find orifice size and manifold
pressure settings for proper operation at given natural
gas condition.

(6.) Check and verify orifice size in furnace. NEVER

ASSUME THE ORIFICE SIZE. ALWAYS CHECK
AND VERIFY.

EXAMPLE: Heat value 1025 Btu/cu ft
Specific gravity of 0.62
Therefore, Orifice No. 41,
Manifold pressure 3.5-in. wc
The furnace is shipped with No. 42 orifices. In this example
all main burner orifices must be changed and manifold
pressure must be adjusted.

(7.) Proceed to item c to adjust manifold pressure.

b. Determine natural gas input rate by clocking gas meter and

adjusting manifold pressure per item c.

NOTE:

Be sure all pressure tubing, combustion-air and vent

pipes, and burner enclosure plates are in place when checking
input.

(1.) Obtain average yearly heat value for local gas supply.

NOTE:

Be sure heating value of gas used for calculations is

correct for your altitude. Consult local gas utility for altitude
adjustments of gas heating value.

(2.) Turn off all other gas appliances and pilots.

(3.) Start furnace and let it run for 3 minutes.

(4.) Measure time (in sec) for gas meter test dial to

complete 1 revolution.

(5.) Refer to Table 9 for cubic ft of gas per hr.

(6.) Multiply gas rate (cu ft/hr) by heating value (Btu/cu

ft). Obtain heating value from local gas utility.

EXAMPLE: Btu heating input = Btu/cu ft X cu ft/hr
Heating value of gas = 1070 Btu/cu ft
Time for 1 revolution of 2 cu ft dial = 72 sec
Gas rate = 100 cu ft/hr (from Table 9)
Btu heating input = 100 X 1070 = 107,000 Btuh

(7.) Measured gas input must not exceed gas input on unit

rating plate.

NOTE:

High altitude—Gas input on rating plate is for altitudes

up to 2000 ft. Ratings for altitudes over 2000 ft must be 4 percent
less for each 1000 ft above sea level. To obtain the adjusted
altitude rating, adjust the manifold pressure, item c, and replace the
main burner orifices as needed. Refer to NFGC Appendix F, Table
F-4 for proper orifice sizing at high altitudes.

(8.) Proceed to item c to adjust manifold pressure.

c. Adjust gas input.

NOTE:

The gas meter must always be clocked with the burner

enclosure front installed. The gas valve has been nominally set at
3.5-in. wc for natural gas.

(1.) Remove burner enclosure front and cap that conceals

adjustment screw for gas valve regulator. (See Fig.
14.)

(2.) Turn adjusting screw either counterclockwise (out) to

decrease input rate or clockwise (in) to increase rate.
When adjusting input rate, DO NOT set manifold
pressure less than 3.2 or more than 3.8-in. wc for
natural gas. Make any major adjustments by changing
main burner orifices.

DO NOT redrill orifices. Improper drilling (burrs, out-of-
round holes, etc.) can cause excessive burner noise and
misdirection of burner flames. This can result in flame
impingement of the burners and heat exchangers, causing
failures.

NOTE:

If orifice hole appears damaged or it is suspected to have

been redrilled, check the orifice hole with the correct size
numbered drill bit. Never redrill an orifice. A burr-free and
squarely aligned orifice hole is essential for proper flame charac-
teristics.

(3.) Replace burner enclosure plates and measure adjusted

gas input rate using method outlined in item b.

(4.) Replace cap that conceals gas valve regulator adjust-

ment screw.

Be sure burner enclosure front is in place after adjustments
have been made.

d. Look through sight glass in burner enclosure and check

burner flame. The main burner flame should be clear blue,
almost transparent. (See Fig. 15.)

2. Set temperature rise.

The furnace must not be operated outside the range of temperature
rise specified on the unit rating plate. Determine the air tempera-
ture rise as follows.

a. Place thermometers in return and supply ducts as near

furnace as possible. Be sure thermometers do not "see" heat
exchanger so that radiant heat does not affect readings. This
practice is particularly important with straight-run ducts.

b. When thermometer readings stabilize, subtract return-air

temperature from supply-air temperature to determine air
temperature rise.

Fig. 14—Redundant Automatic Gas Valve

A91219

REGULATOR
ADJUSTMENT

MANIFOLD

PRESSURE

TAP

INLET
PRESSURE
TAP

MANUAL

ON/OFF

13

Summary of Contents for 101 Series

Page 1: ...ther than wood The design of this furnace line is not A G A certified for installation in recreational vehicles manufactured housing mobile homes or outdoors Before installing this furnace refer to the current edition of the NFGC NFPA 54 1992 ANSI Z223 1 1992 which is available from the National Fire Protection Association Inc Batterymarch Park Quincy MA 02269 American Gas Association 1515 Wilson ...

Page 2: ...n UNIT SIZE 050 075 100 AND 125 Sides 0 Back 0 Top of Plenum 0 Vent Connector PVC Pipe 0 Front Casing 1 Front Service 30 Zero in with controls on front of furnace 1 in from back of elbow with combustion air inlet on back of furnace and 1 in from end of inducer motor with controls located on back of furnace Measured from end of inducer motor Table 2 Dimensions In UNIT SIZE LENGTH WIDTH WEIGHT LB 05...

Page 3: ...TION RELATIVE TO COOLING EQUIP MENT The cooling coil must be installed parallel with or on the downstream side of the furnace to avoid condensation in the heat exchanger When installed parallel with a furnace dampers or other means used to control the flow of air must prevent chilled air from entering the furnace If the dampers are manually operated they must be equipped with a means to prevent op...

Page 4: ... with appropriate straps hangers etc Use a minimum of 1 hanger every 6 ft Joint compounds pipe dope should be applied sparingly and only to the male threads of the joints This pipe dope must be resistant to the action of propane gas Install a sediment trap in the riser leading to the furnace The trap can be installed by connecting a tee to the riser leading to the furnace so that the straight thro...

Page 5: ...4 V WIRING Make field 24 v connections at the 24 v termi nal block Connect Y terminal as shown in Fig 4 for proper cooling operation The 24 v terminal board is marked for easy connection of field wiring See Fig 5 NOTE Use AWG No 18 color coded copper thermostat wire for lengths up to 100 ft For wire lengths over 100 ft use AWG No 16 wire ACCESSORIES Install accessories per manufacturer s instruc t...

Page 6: ...Standards COMBUSTION AIR AND VENT PIPING The combustion air and vent pipe fittings must conform to American National Standards Institute ANSI standards and American Society for Testing and Materials ASTM standards D1785 schedule 40 PVC D2665 PVC DWV D2241 SDR 21 and SDR 26 PVC D2661 ABS DWV or F628 schedule 40 ABS Pipe cement and primer must conform to ASTM standards D2564 PVC or D2235 ABS See Tab...

Page 7: ...ing such as when it passes through an unheated space or when a chimney is used as a raceway the pipe must be insulated with 1 2 in thick Armaflex type insulation When the combustion air pipe is installed above a suspended ceiling the pipe must be insulated with 1 2 in Armaflex type insulation The combustion air pipe should also be insulated when it passes through a warm humid space Solvent cements...

Page 8: ...lation level or grade whichever is greater b Minimum of 4 ft clearance must be provided from electric or gas meters regulators and relief equipment 4 Install 90 elbows as shown in Fig 6 or 7 or use a 180 U fitting 5 Install tee as shown in Fig 6 or 7 6 Check required dimensions as shown in Fig 6 or 7 7 Disassemble loose pipe fittings Clean and cement fittings using same procedures as outlined for ...

Page 9: ...ield reversal be sure to have a correct wiring diagram available and be prepared to mark all wires as they are disconnected The inducer assembly burner controls gas valve and electrical controls are designed to be field reversed as necessary for certain field installations and applications per the following procedure 1 Remove manifold cover plate and air inlet plate burner re moval cover 2 Disconn...

Page 10: ...all vent return pipe so pipe outlet is facing rear of unit Reinstall 4 washers and nuts securing pipe to heat exchanger bottom plate Remove and discard cardboard previously placed between fins and pipe Remove patch plate and cut insulation on rear center panel and position vent return pipe through panel Secure pipe to panel with 4 screws 30 Remove blower motor wiring harness strain relief from fro...

Page 11: ...umper wire on pressure switches 11 Turn on gas valve 12 Turn on electrical supply to unit Unit should begin ignition cycle Step 11 Start up Adjustment and Safety Check GENERAL The furnace must have a 115 v power supply properly connected and grounded Proper polarity must be main tained for correct operation Thermostat wire connections at R W Y G and C must be made at the 24 v terminal block on the...

Page 12: ... 34 35 36 3 2 3 3 3 7 890 38 39 3 4 3 7 37 38 39 3 2 3 5 3 8 37 38 3 3 3 6 37 38 3 4 3 8 36 37 3 2 3 5 36 37 3 3 3 6 36 37 3 4 3 7 36 3 5 35 36 3 2 3 6 905 38 39 40 3 3 3 6 3 8 38 39 3 4 3 7 37 38 39 3 2 3 5 3 8 37 38 3 3 3 6 37 38 3 4 3 8 36 37 3 2 3 5 36 37 3 3 3 6 36 37 3 4 3 7 36 37 3 5 3 8 920 38 39 40 3 2 3 4 3 7 38 39 40 3 3 3 6 3 8 38 39 3 4 3 7 37 38 39 3 2 3 5 3 8 37 38 3 3 3 6 37 38 3 4...

Page 13: ... pressure item c and replace the main burner orifices as needed Refer to NFGC Appendix F Table F 4 for proper orifice sizing at high altitudes 8 Proceed to item c to adjust manifold pressure c Adjust gas input NOTE The gas meter must always be clocked with the burner enclosure front installed The gas valve has been nominally set at 3 5 in wc for natural gas 1 Remove burner enclosure front and cap ...

Page 14: ...selector located at the blower motor See Table 10 Table 10 Blower Speed Selection SPEED TAP NO Common 1 High 2 Medium 3 Low 4 Recheck the temperature rise It must be within limits specified on the unit rating plate Recommended operation is at midpoint of rise or above 3 Set thermostat heat anticipator The thermostat heat anticipator must be set to match the amp draw of the components in the R to W...

Page 15: ...drain safety switch This control ensures the condensate drain is open to allow condensate flow and that combustion air is flowing through the unit prior to starting the ignition cycle The blocked drain safety switch has only 1 tube connected to it Check switch operation as follows a Place unit into operation with burners on b Pinch off tube leading to pressure switch P2 The burners should shut off...

Page 16: ...D DISCONNECT ON HOT LEG 1 2 3 4 60 SEC 90 SEC 120 SEC DELAY OFF SCREW SETTINGS 150 SEC MED HI GND N2 HEAT COOL N3 D1 N4 C BI S1 S2 M2 K1 K2 K2 K3 X R Y C W G CN23 2 CN23 1 CN23 6 LIMIT CONTROL TRANSFORMER CONDENSING UNIT PRESSURE SW N O N C PS1 PS2 V1 CN23 3 CN23 5 COM ST912081005 ELECTRONIC FAN TIMER ROS MV PV MV PV MV MV PV PV 24V GNO GNO BURNER SPARK GAS VALVE HONEYWELL VR8204 PILOT 24V IGNITIO...

Reviews: