3-7
Electrical Installation and Cabling
Chassis Connections
Power Connections
There are three power supplies available with the Axxius 800; 24 VDC and 48 VDC
and 48 VDC NI, all use this connector. The Axxius 800 supports a redundant power
system, therefore there is INPUT (power) P1 and P2.
Input Power
A separate
fuse should be used for each DC input
NOTE:
If two power supplies are installed into the system they MUST be
of the same type (24 VDC, 48 VDC or 48 VDC NI).
Wire each connector to a power source:
1. Ensure that no power is present on the two wires to be connected.
DANGER!
P
OSSIBLE
SHOCK
HAZARD
EXISTS
,
PLEASE
FOLLOW
INSTRUCTIONS
CAREFULLY
.
2. Strip the two wires from the power source so that approximately 5/16 inch of
bare wire is exposed. 16
or
18
AWG
insulated
copper
wire
is recommended
for power
connections.
3. Insert the Battery Return and DC wires into the appropriate square holes, one
at a time.
4. Tighten screws to clamp wires.
Power Supply
Rated Amperage
Recommended External
Input Fuse
24 VDC
5 Amp
7 Amp
48 VDC/48 VDC NI
2.5 Amp
3.5 Amp
Summary of Contents for Network Device Axxius 800
Page 1: ...Axxius 800 USER MANUAL Part Number 770 0104 AG Product Release 2 2 May 2004 ...
Page 32: ...xxxii Axxius 800 Release 2 2 Table of Contents ...
Page 50: ...1 18 Axxius 800 Release 2 2 Base Platform ACO ...
Page 101: ...CHAPTER CLI Commands In this Chapter n Command Line Interface Help n CLI Commands ...
Page 392: ...8 8 Axxius 800 Release 2 2 FXO Voice Card Channel Associated Signaling CAS Conversions ...
Page 430: ...12 8 Axxius 800 Release 2 2 Power Supply Installing Replacing a Power Supply ...
Page 472: ...15 20 Axxius 800 Release 2 2 Terminal Server Router Card LEDs ...
Page 500: ...18 12 Axxius 800 Release 2 2 Maintenance Hot Swap Service Card ...
Page 532: ...C 22 Axxius 800 Release 2 2 Loopback Tests V 35 V 54 Loop ...
Page 552: ...Glossary 20 Axxius 800 Release 2 2 Glossary ...