76
humiSteam -
cod. +030221910 rel. 5.2 - 07.11.2005
12. TECHNICAL SPECIFICATIONS
Model
UE001* UE003* UE003** UE005* UE005** UE008** UE009* UE010** UE015** UE025** UE035** UE045** UE065**
steam
connection (diam. mm) 208-230 V
22/30
30
2x40
400-460-575 V
22/30
30
1x40
2x40
outlet pressure limits (Pa)
0 - 2000
0 - 1600
0 - 1700
0 - 2300
supply water
connection
3
/
4
“G
temperature limits (°C)
1 to 40
pressure limits (MPa)
0.1 to 0.8 (1 to 8 bar)
hardness limits (°fH)
≤
40
instant flow-rate (l/min)
0,6
1,2
4
7
conductivity range (µS/cm)
125 - 1250
drain water
connection (diam. mm)
40
typical temperature (°C)
≤
100
instant flow-rate (l/min)
5
22,5
environmental conditions
ambient operating temperature (°C)
1 to 40
ambient operating humidity (% rH)
10 to 60
storage temperature (°C)
-10 to 70
storage humidity (% rH)
5 to 95
index of protection
IP20
electronic controller
type
UES-UEP-UEH-UEA
auxiliary voltage / frequency (V - Hz)
24 / 50-60
maximum auxiliary power (VA)
30
40
probes inputs for versions C and P
input impedance: 15k
Ω
, range 0-10 Vdc
(general characteristics)
probe inputs for versions H and T
selectable by signal: 0 to 1 Vdc, 0 to 10 Vdc, 2 to 10 Vdc, 0 to 20 mA, 4 to 20 mA
(general characteristics)
input impedance: 60 k
Ω
with signals: 0 to 1 Vdc, 0 to 10 Vdc, 2 to 10 Vdc
50
Ω
with signals: 0- to 20 mA, 4 to 20 mA
power to active probes for versions H or T
28 V (24Vac rectified), Imax= 250 mA
(general characteristics)
12 Vdc 5%, Imax= 50 mA
alarm relay outputs for versions H or T
250 V 5A (2A) - microinterruption action type 1C
(general characteristics)
alarm relay and dehum. outputs for vers. H or T
250 V 8A (2A) - microinterruption action type 1C
(general characteristics)
remote enabling input (general characteristics)
free contact; max. resistance 50
Ω
; Vmax= 24 Vdc; Imax= 5 mA
serial communication for versions H or T
RS-485 two-wire
power
rated power supply voltage: 208V - 1~N code U
instant steam production
(1)
(kg/h) 1.5
3.0
5.0
8,7
power input at rated voltage (kW)
1.12
2.25
3.75
6,52
rated power supply voltage: 230V - 1~N code D
instant steam production
(1)
(kg/h) 1.5
3.0
5.0
9
power input at rated voltage (kW)
1.12
2.25
3.75
6,75
rated power supply voltage: 208V - 3~ code W
instant steam production
(1)
(kg/h) 3.0
5.0
8.0
10.0
15.0
25
35
45
power input at rated voltage (kW)
2.25
3.75
6.00
7.50
11.25
18.75
26.25
33.75
rated power supply voltage: 230V - 3~ code K
instant steam production
(1)
(kg/h) 3.0
5.0
8.0
10.0
15.0
25
35
45
power input at rated voltage (kW)
2.25
3.75
6.00
7.50
11.25
18.75
26.25
33.75
rated power supply voltage: 400V - 3~ code L
instant steam production
(1)
(kg/h) 3.0
5.0
8.0
10.0
15.0
25
35
45
65
power input at rated voltage (kW)
2.25
3.75
6.00
7.50
11.25
18.75
26.25
33.75
48.75
rated power supply voltage: 460V - 3~ code M
instant steam production
(1)
(kg/h) 3.0
5.0
8.0
10.0
15.0
25
35
45
65
power input at rated voltage (kW)
2.25
3.75
6.00
7.50
11.25
18.75
26.25
33.75
48.75
rated power supply voltage: 208V - 1~N code U
instant steam production
(1)
(kg/h) 3.0
5.0
8.0
10.0
15.0
25
35
45
65
power input at rated voltage (kW)
2.25
3.75
6.00
7.50
11.25
18.75
26.25
33.75
48.75
Tab. 12.1
* single-phase, ** three-phase.
(1)
the average steam production is affected by factors such as: the ambient temperature, the quality of the water and the steam distribution system