10.3 Table of alarms and signals
code displayed
controller
remote causes
solution
action
reset
alarm
reset
term.*
display (H)
relay
relay (H)
P
H
P
H
2 fast
E102
over-current at the electrodes;
1. check the operation of the drain
total
total
not
active
not
flashes
probable electrode malfunction
electrovalve
shut-
shut-
available
available
red
or water conductivity
2. check the seal of the fill electrovalve
down
down
LED
temporarily too high (especially
when not energised
when starting after a short
3. drain part of the water and re-start
stop)
3 fast
E103
power not available; with the
1. with the machine off and disconnected
total
total
not
active
not
flashes
machine on no steam is
from the mains, check the internal
shut-
shut-
available
available
red produced
electrical
connections
down
down
LED
not
E105
high supply water conductivity
1. check limit set for b6;
-
total
not
active
not
featured
2. turn the machine off and clean the water
shut-
available
available
conductivity measuring electrodes;
down
3. if the problem persists, change the
source of supply water or install a
suitable treatment system
(demineralisation, even partial).
N.B.: the problem will not be resolved
by softening the supply water.
4 slow
E113
excessive reduction in
1. cylinder completely depleted or water
total
machine
manual
active
manual
flashes
production
with excessive foam. Perform
shut-
disabled
red
maintenance on the cylinder
down
LED
3 slow
E114
no water
1. check that the fill pipe from the mains
total
machine
automatic
active
automatic
flashes
to the humidifier and the internal pipe
shut-
disabled
when water
when
red
are not blocked or bent and that there
down
returns (see
water
LED
is sufficient pressure (0.1-0.8 MPa,
par. 11.4.10)
returns
1-8 bar);
2. check the operation of the fill
electrovalve;
3. check that the steam outlet is not
working against excessive back-pressure,
preventing the flow of water into the
cylinder by gravity;
4. check that the steam outlet pipe is not
is choked and that there are no pockets
of condensate.
not
E115
excessive foam in the cylinder
the formation of foam is generally due to
-
signal
manual
active
manual
featured
during boiling
the presence of surfactants in the water
only
(lubricants, solvents, detergents, water
treatment agents, softeners) or an
excessive concentration of dissolved salts:
1. drain the water supply lines
2. clean the cylinder
3. check for the presence of softeners
(in this case, use another type of water
or reduce the softening)
5 slow
E116
drain malfunction
check the drain circuits and the correct
total
machine
manual
active
manual
flashes
operation of the drain electrovalve
shut-
disabled
red
down
LED
7 slow
E131
high water conductivity
check the conductivity of the supply water
-
signal
auto
not
-
flashes
pre-alarm
if necessary, install a suitable treatment
only
active
system N.B.: the problem will not be
resolved by softening the supply water.
not
E121
high humidity in the room
check the operation of the probe and the
-
signal
manual
active
auto
featured
(high temp. for T control)
limit set for parameter P2
only
not
E122
low humidity in the room
check the operation of the probe and the
-
signal
manual
active
auto
featured
(low temp. for T control)
limit set for parameter P3
only
not
E124
high outlet humidity
check the operation of the outlet
-
signal
manual
active
auto
featured
probe
only
continues