45
ENG
Heos
+0300078EN - rel. 1.6 - 23.11.2017
Mask index Par.
Description
Default
UOM
Min
Max
Possible value descr.
R/W
Dab07
cIA
Compressor speed when starting
50.0
rps
cIc
cIb
R/W
cIb
Maximum compressor speed
Comp
rps
cIc
Type comp
R/W
cIc
Minimum compressor speed
Comp
rps
Type comp
cIb
R/W
Dab08
cId
Maximum speed increase (control)
1.0
rps/s
0.1
Type comp
R/W
cIE
Maximum speed decrease (control)
1.0
rps/s
0.1
Type comp
R/W
CIF
Maximum speed decrease (shutdown)
1.0
rps/s
0.1
Type comp
R/W
Dab09
cIH
Acceleration decrease (to return inside envelope)
0.5
rps/s
0.1
Type comp
R/W
cII
Minimum comp. speed to remain inside envelope
Comp
rps
Type comp
cIb
R/W
cIJ
Out of envelope alarm delay
180
s
0
600
R/W
Dab10
cIL
Low compression ratio alarm delay
180
s
1
600
R/W
cIn
Enable low compression ratio management by closing EEV 1
--
0
1
0: NO; 1: YES
R/W
cIo
Enable increase comp. speed with low compression ratio
1
--
0
1
0: NO; 1: YES
R/W
Dab11
cIP
Enable oil recovery management
1
--
0
1
0: NO; 1: YES
R/W
cIr
Oil recovery procedure activation time
30
min
1
480
R/W
cIS
Compressor override time during procedure
2
min
1
10
R/W
Dab12
cIu
Minimum comp. output to activate oil recovery procedure
Comp
%
10.0
99.9
R/W
cIV
Comp. speed during oil recovery procedure
100
%
0
100
R/W
Dab13
c6
ON delay between two compressors
10
s
0
999
R/W
c7
OFF delay between two compressors
10
s
0
999
R/W
Dad01
AI1
Set high compressor pressure
33.0 (484.7) barg/psig
-1.0 (-14.7)
200.0 (2938.0)
R/W
AI2
High compressor pressure diff erential
3.0 (44.1)
bar/psi
0.0 (0.0)
20.0 (293.8)
R/W
Dad02
AI3
Set low compressor pressure
0.5 (7.3)
barg/psig
-1.0 (-14.7)
200.0 (2938.0)
R/W
AI4
Low pressure compressor diff erential
2.0 (29.4)
bar/psi
0.0 (0.0)
20.0 (293.8)
R/W
Dad03
AI5
Low compressor pressure alarm delay at start-up
30
s
0
999
R/W
AI6
Low compressor pressure alarm delay in steady operation
5
s
0
999
R/W
AI7
Type of low compressor pressure alarm reset
0
--
0
1
0: 5 ATTEMPTS
1: 0 ATTEMPTS
R/W
Dad04
AI8
Type of envelope alarm reset
0
--
0
1
0: SEMIAUT.
1: MANUAL
R/W
AIA
Time range
60
min
0
999
R/W
AIb
No. of attempts performed
5
--
0
10
R/W
Dad05
AI9
Type of Power+ alarm reset
0
--
0
1
0: SEMIAUT.
1: MANUAL
R/W
AIC
Time range
60
min
0
999
R/W
AId
No. of attempts performed
5
--
0
10
R/W
Dad06
dtt
Low inverter temperature threshold
2.0 (3.6)
°C (°F)
-99.9 (-147,8) 99.9 (212.0)
R/W
dtE
Inverter temperature diff erential
3.0 (5.4)
°C (°F)
0.0 (0.0)
10.0 (18.0)
R/W
Dad07
Hdt
Threshold high alarm discharge temperature comp
90.0 (194.0) °C (°F)
0.0 (32)
200.0 (392.0)
R/W
Hdd
Diff erential discharge temperature
5.0 (9.0)
°C (°F)
0.0 (0.0)
20.0 (36.0)
R/W
dHd
Delay alarm discharge temperature
30
s
0
999
R/W
Dae08
Operating hours, compressor 1-5
0
h
0
99999
R
Dba01
P3
Superheat set point
10.0 (36.0)
°C (°F)
0.0 (0.0)
30.0 (54.0)
R/W
Dba02
P4
PID: EEV proportional gain
15.0
0.0
100.0
R/W
P5
PID: EEV integral time
150
s
0
999
R/W
P6
PID: EEV derivative time
5.0
s
0.0
100.0
R/W
Dbb01
EVP
EEV present
1
-
0
1
0: NO PRESENT
1: PRESENT
Dbb02
PH
Refrigerant type (depends on selected compressor)
Comp
--
0
13
0: R22
1: R134A
2: R404A
3: R407C
4: R410A
5: R507A
6: R290 (PROPANE)
7: R600 (BUTANE)
8: R600A (ISOBUTANE)
9: R717 (AMMONIA)
10: R744
11: R728 (NITROGEN)
12: R1270 (PROPILENE)
13: R417A
R
Dbb03
CP1
EEV opening at power on
50
%
0
100
R/W
Psb
Enable EEV opening in standby
0
--
0
1
0: NO; 1: YES
R/W
cP2
EEV pre-positioning delay
6
s
0
300.0
R/W
Dbc01
P7
Low superheat threshold
2.0 (3.6)
°C (°F)
0.0 (0.0)
30.0 (54.0)
R/W
P8
LowSH: EEV low superheat integral time
10
s
0.0
999
R/W
P9
LowSH: EEV low superheat alarm delay
120
s
0
300.0
R/W
Dbc02
PL1
LOP
-50.0 (-58.0) °C (°F)
-50.0 (-58.0)
MOP
R/W
PL2
LOP: Low evaporation temperature integral time
10
s
0.0
999
R/W
PL3
LOP: Low evaporation temperature alarm delay
120
s
0
300.0
R/W
Dbc03
PM1
MOP
15.0 (59.0)
°C (°F)
LOP
30.0 (86.0)
R/W
PM2
MOP: High evaporation temperature integral time
20.0
s
0.0
999
R/W
PM3
MOP: High evaporation temperature alarm delay
240
s
0
300.0
R/W
Dbc04
P11
Low suction temperature alarm threshold
-40.0 (-40.0) °C (°F)
-50.0 (-58.0)
30.0 (86.0)
R/W
P12
Low suction temperature alarm delay
120
s
0
300
R/W
Dbc05
Pa
High superheat threshold
35.0 (95.0)
°C (°F)
0.0 (32.0)
50.0 (122.0)
R/W
Pb
High superheat alarm delay
600
s
0
999
R/W
Dbc06
Pb1
Valve threshold position warning
99
%
0
100
R/W
Pb2
Alarm delay
10
min
0
999
R/W
Dbc07
Pb3
Superheat off set setpoint for low refrigerant charge
warning
3.0 (5.4)
°C (°F)
0 (0)
20.0 (36.0)
R/W
Pb4
Alarm delay
10
min
0
999
R/W
Dbc08
P15
Off set for LP calculation
3.0 (5.4)
°C (°F)
0 (0)
68.0 (122.4)
R/W
Dca01
d0
Type of defrost/end defrost
0
--
0
6
0: ELECTR./ TEMP-TIMEOUT
1: INV. CYCLE/ TEMP-TIMEOUT
2: ELECTR./ ONLY TIMEOUT
3: INV. CYCLE/ ONLY TIMEOUT
4: ELECTRICAL/
REGUL. TEMPERAT. TIME
5: BYPASS HOT-GAS /
TEMP-TIMEOUT
6: BYPASS HOT-GAS/
ONLY TIMEOUT
R/W