5. STARTUP
5.1 Guided commissioning procedure
The Heos controllers can be setup the fi rst time from the pGDe user
terminal connected to J15. After programming, the terminal can be
removed or remain connected.
If the controller has not yet been confi gured, the user terminal shows the
language selection and than the fi rst screen in a guided confi guration
procedure, called the “wizard”. Otherwise, the same menu can be
accessed from branch.
E.Confi guration>>f.default
.
The main parameters needed for general confi guration are shown one at
a time. The wizard screens are all numbered in the top right corner; the
following explanations refer to this number. To go from one screen to the
next press
, while to return to previous screen press
.
Important:
at the end of the procedure, exit by powering the unit OFF,
after having exited screen WZ19 by pressing
.
Screen WZ01:
this shows the code of the application loaded on the
controller (FLSTDmWL0M) and the revision. Pressing
starts the
guided procedure.
x.x xxx
Screen WZ02:
select multi-evaporator/individual compressor
confi guration. A group of controllers is called “multi-evaporator” when
multiple controllers (up to 6) are connected in a Master/Slave network,
and share the same compressor, controlled by the Master. If setting “Y” for
the parameter on this screen, the unit will be part of a multi-evaporator
group. Setting “NO”, the unit is confi gured as stand-alone or part of a
Master/Slave group with an individual compressor on each unit.
Screen WZ03
: unit address. The unit can be confi gured as the Master or
as one of the Slaves, setting the parameter to MASTER or SLAVE1, SLAVE2,
… SLAVE 5. Setting this parameter also sets the controller pLAN address
as a consequence: 1 for the Master, 2 for Slave 1, 3 for Slave 2, and so on
up to 6 for Slave 5.
Screen WZ04:
this is only shown if the controller is set as the Master and
the multi-evaporator confi guration has been selected. This specifi es the
number of evaporators connected to the Master. The default value is the
number of Slaves connected.
Screen WZ05:
this is only shown if the controller is set as the Master and
the multi-evaporator confi guration has not been selected. specifi es the
number of Slaves connected to the Master.
Screen WZ06:
evaporator capacity. If the unit is confi gured as part of a
multi-evaporator group, this screen is used to set the rated evaporator
cooling capacity. This data is used to adjust the compressor speed based
on demand from the various units served.
Screen WZ07:
select type of unit. The type of unit can be selected as
SHOWCASE or COLD ROOM. If COLD ROOM is selected, other parameters
are proposed: the position of the door switch and enable/disable the
three temperature probes: outlet, defrost and intake.
Screen WZ08:
select type of unit of measure (SI or Imperial) for
temperature and pressure.
Screen WZ09:
set point and virtual probe composition. This screen
is used to set the control set point and the weight of the outlet and
intake temperature probes in the average for calculating the control
temperature. When the parameter is set to 0%, the virtual probe coincides
with the outlet probe, if set to 100% the virtual probe coincides with the
intake probe.
Screen WZ10:
select type of compressor: BLDC, ON/OFF (single) or ON/
OFF (multiple).
Screen WZ11:
select the digital input for multi compressors.
Screen WZ12:
select compressor and inverter programming. For the
Compressor parameter, any one of the compressors managed by
Heos can be selected. Under the type of compressor, if the inverter is
connected and on, the model of Power+ can be read. If the inverter is
off or not connected, the last row of the screen displays the message
Power+ not connected. After having confi rmed the type of compressor, if
communication with the inverter is active, Write parameters is displayed;
choosing Y starts writing some of the parameters to the inverter, so as
to ensure correct operation with the selected compressor. During the
write procedure, the display shows Installing parameters…, replaced
by a confi rmation message when the write procedure has ended. If the
control is fi tted on a Slave on a multi-evaporator unit, this screen is not
displayed.
Screen WZ13:
select type and limits of the suction and condensing
pressure probes.
Screen WZ14:
with on-board compressor, if confi guring a Slave in on a
multi-evaporator unit, only the suction probe is proposed.
Screen WZ15:
select the type of outlet, defrost, intake, compressor
suction and compressor discharge temperature probes. If is a Slave unit
being confi gured, the compressor discharge temperature probe is not
displayed.
Screen WZ16:
select the type defrost and main defrost parameters.
Screen WZ17:
select the operating mode for the evaporator fans.
Screen WZ18:
set the parameters for connecting the supervisor.
Screen WZ19:
end the wizard procedure. Pressing ENTER ends the
procedure, and starts confi guring the system with the chosen options.
At the end of the confi guration, the controller needs to reset the unit to
confi rm the data (
WZ20
). Power down the controller for a few seconds
and power on again.
WZ19