36
ENG
Heos
+0300078EN - rel. 1.6 - 23.11.2017
7. PARAMETER
TABLE
Mask index”
: iindicates the unique address of each screen and consequently the path needed to reach the parameters available on this screen; for example,
to reach the parameters corresponding to the suction pressure probe with mask index Bab01, proceed as follows:
Main menu
B.In./Out.
Î
a.Status
Î
b.Analog.in.
Below is the table of the parameters that can be displayed on the terminal. The values indicated with ‘---‘ are not signifi cant or are not set, while the values indicated
with ‘…’ may vary according to the confi guration, with the possible options visible on the user terminal. A row of ‘…’ means that there are a series of parameters similar
to the previous ones.
Note
: not all the screens and parameters shown in the table are always visible or can be set, the screens and parameters that are visible or can be set depend
on the confi guration and the access level
.
R/W = Read / Write
Mask index Par.
Description
Default
UOM
Min
Max
Possible value descr.
R/W
Aa01
Select unit status
0
--
0
13
0: ON
1: UNIT OFF FROM ALARM
2: UNIT OFF FROM SUPERVIS
.
3: UNIT OFF FROM TIME-BAND
4: UNIT OFF FROM DIG. INPUT
5: UNIT OFF FROM KEYPAD
6: DEFROST - 7: DRIPPING
8: POST DRIPPING
9: DOOR OPEN
10: CONTINUOS CYCLE
11: UNIT OFF FROM START-UP
12: MAINTENANCE
13: UNIT OFF FROM MASTER
14: OIL RECOVERY
R
O/F
Select unit status
0
--
0
1
0: UNIT OFF
1: UNIT ON
2: UNIT FORCED OFF
R/W
Aa02
H2
Enable On/Off from supervisor
0
--
0
1
0: NO; 1: YES
R/W
H3
Enable On/Off from keypad
1
--
0
1
0: NO; 1: YES
R/W
Ab01
J1
Run local defrost from keypad
0
--
0
1
0: NO; 1: YES
R/W
J2
Run network defrost from keypad
0
--
0
1
0: NO; 1: YES
R/W
Defrost temperature
°C (°F)
R
Ab03
J4
Management of light digital input
0
--
0
1
0: SWITCH LIGHTS ON
1: SWITCH LIGHTS OFF
R/W
Ab04
J5
Enable force water valve
0
--
0
1
0: NO
1: YES
R/W
J6
Maximum valve forcing time
480
min
0
999
R/W
Baa01
/FA
Select outlet temperature probe position (Sm)
1
--
0
10
0: --
1: U01…10: U10
11: SPV
12: MST
13: SL1
R/W
Select type of outlet temperature probe (Sm)
0
--
0
2
0: NTC
1: NTC-HT
2: PT1000
R/W
Outlet temperature reading (Sm)
°C (°F)
R
Outlet temperature probe off set (Sm)
0.0 (0.0)
°C (°F)
-50.0 (-90.0)
50.0 (90.0)
R/W
Baa02
/Fb
Select defrost temperature probe position (Sd)
2
--
0
10
0: --
1: U01…10: U10
11: SPV
12: MST
13: SL1
R/W
Select type of defrost temperature probe (Sd)
0
--
0
2
0: NTC
1: NTC-HT
2: PT1000
R/W
Defrost temperature reading (Sd)
°C (°F)
R
Defrost temperature probe off set (Sd)
0.0 (0.0)
°C (°F)
-50.0 (-90.0)
50.0 (90.0)
R/W
Baa03
/Fc
Select intake temperature probe position (Sr)
3
--
0
10
0: --
1: U01…10: U10
11: SPV
12: MST
13: SL1
R/W
Select type of intake temperature probe (Sr)
0
--
0
2
0: NTC
1: NTC-HT
2: PT1000
R/W
Intake temperature reading (Sr)
°C (°F)
R
Intake temperature probe off set (Sr)
0.0 (0.0)
°C (°F)
-50.0 (-90.0)
50.0 (90.0)
R/W
Baa04
/P3
Select condensing pressure probe position
7
--
0
10
0: --
1: U01…10: U10
11: SPV
12: MST
13: SL1
R/W
Select type of condensing pressure probe
0
--
0
3
0: RAT.0-5V
1: 4-20MA
2: 4-20MA REM
3: 4-20MA EXT
R/W
Condensing pressure probe reading
0.0 (0.0)
barg/psig
R
Maximum condensing pressure probe value
45.0 (650.0) barg/psig
min
200.0 (2938.0)
R/W
Minimum condensing pressure probe value
0.0 (0.0)
barg/psig
-1.0 (-14.7)
max
R/W
Condensing pressure probe off set
0.0 (0.0)
bar/psi
-10.0 (-146.9) 10.0 (146.9)
R/W
Summary of Contents for Heos