11
ENG
Heos
+0300078EN - rel. 1.6 - 23.11.2017
2.4 E
2
V unipolar valves
30,20
C
D
Ø
F out
Ø
F in
Ø E in
Ø E out
G
G
A
Ø 35
47,75
B
34,80
Valve
type
E2V**FSF** copper 12-
12mm ODF
A
133.5mm (5.26inch)
B
85.4 mm (3.36 inch)
C
55.1 mm (2.17 inch)
D
57.5 mm (2.26 inch)
E
In 12 / Out 14 mm (In 0.47/
Out 0.55 inch)
F
In 12 / Out 14 mm (In 0.47/
Out 0.55 inch)
G
10 mm (0.39 inch)
CAREL E
2
V-U operating specifi cations (+
050001440
)
CAREL E2V-U stator (+
050001440
)
Compatibility
Group 1: R1234yf, R290, R600, R600a
Group 2: R22, R134a, R404A, R407C, R410A, R417A,
R507A, R744, R1234ze, R448A, R449A, R450A, R513A
Power supply voltage
12 V
Drive frequency
50 Hz
Phase resistance (25 °C)
40 Ohm ± 10%
Maximum operating pressure (MOP) CE approval: 60 bars (870psi).
UL approval: 45 bars (652 psi)
Ingress protection
IP67
Step angle
15°
Maximum operating PD (MOPD)
35 bars (508 psi); for
E2V35 unipolar:
26 bars (377psi)
Linear movement/step
0.03 mm (0,0012 inch)
P.E.D.
Gr 1 & 2, art. 4, par. 3.
Connections
6 pin (AWG 18-22) with 1; 2; 0.3 m cable
included
Refrigerant temperature
-40T70 °C (-40T158 °F)
Ambiente temperature
-30T70 °C (-22T158 °F)
Complete closing /control steps
500 / 480
Tab. 2.j
2.5 Pressure probe (SPKT00**P0)
Ch 14
7/16”-20UNF
Ø 21
48.2
10.5
9.2
Reference technical document
+050000598
Power supply
4,5...5,5 Vdc
Output
0,5...4,5 Vdc
Connector thread
7/16” 20 UNF
Operating conditions
-40T135 °C
Protection degree
IP65 with mechanical protection; IP67 with electrical connector plugged in
Environmental pollution level
Normal
Material in contact with the fl uid
Brass or plated steel
Separation with plastic
Compatible
with fl uids R12, R22, R134A, R404A, R407C, R410A, R502, R507, R744, HFO 1234ze
Not compatible
with R717 (ammonia), not to be used with water and glycol.
Clamping force
12...16 Nm
Tab. 2.k
2.6 Temperature
probe
Models
NTC***HP00
NTC***HT41
NTC***HF01
Reference technical document
+030220655
+030220655
+030220655
Operating range
-50T105 °C in air - -50T50 °C in fl uid
0T150 °C in air
-50T105 °C
Connections
Stripped ends, dimensions: 5±1 mm
Stripped ends, dimensions: 6±1mm
Stripped ends, dimensions: 6±1mm
Sensor
NTC 10 kΩ ±1% a 25 °C Beta 3435
NTC 50 kΩ ±1% a 25 °C Beta 3977
R(25 °C)= 10 kOhm 1%; Beta 3435
Dissipation factor (in air)
ca. 3 mW/°C
ca. / approx. 3 mW
3 mW
Thermal constant over time (in air)
ca. / approx. 25 s
ca. / approx. 30 s
ca. 50 s
Sensitive element index of protection
IP67
IP55
IP67
Sensitive element housing
Polyolefi n
High temperature polyester dim. 20x5 mm Thermoplastic with fastening clamp
Classifi cation according to protection
against electric shock
Basic insulation for 250 Vac
Basic insulation for 250 Vac
Basic insulation for 250 Vac
Category of resistance to heat and fi re
Flame retardant
In accordance with CEI 20-35
UL/HB cable
for inside showcase temperature
for outlet temperature
for evaporation temperature
Tab. 2.l
Summary of Contents for Heos
Page 2: ......
Page 4: ...4 ENG Heos 0300078EN rel 1 6 23 11 2017 ...
Page 6: ......
Page 57: ...57 ENG Heos 0300078EN rel 1 6 23 11 2017 Notes ...
Page 58: ...58 ENG Heos 0300078EN rel 1 6 23 11 2017 Notes ...
Page 59: ......