43
ENG
Heos
+0300078EN - rel. 1.6 - 23.11.2017
Mask index Par.
Description
Default
UOM
Min
Max
Possible value descr.
R/W
Bb03
J7
Display analogue output confi guration AO1-AO3
0
--
0
7
0: NOT CONFIGURED
8: FAN (DO)
10: LIGHT (DO)
11: DEFROST (DO)
12: ALARM (DO)
13: AUXILIARY (DO)
14: SOFT GAS SOLENOID
15: LIQUID SOLENOID
16: EQUALIZATION SOLENOID
17: SUCCTION SOLENOID
18: RAIL HEATERS
19: HOT GAS SOLENOID
20: LIQUID INJECTION
21: CIRTAIN SWITCH (DO)
22: COMP. ON/OFF (DO)
23: HEAT RECLAIM
24: CONDENSER BYPASS
25: INVERTER WATER SOLEN.
26: AIR CONDENSER
27...31: COMPR. 1...5 (DO)
R
Bb03
% analogue outputs in manual mode
0.0
--
0.0
100.0
R/W
Bb04
J8
Enable compressor in manual mode
0
--
0
1
0: NO; 1: YES
R/W
J9
Compressor capacity percentage in manual mode
0.0
--
0.0
100.0
R/W
Bb05
PMP
Enable manual expansion valve positioning (A)
0
--
0
1
0: AUTO; 1: MAN.
R/W
PMu
Manual expansion valve position (A)
0
steps
0
480
R/W
Bb06
PME
Enable man. expansion valve positioning (B)
0
--
0
1
0: AUTO; 1: MAN.
R/W
PMV
Manual expansion valve position (B)
0
steps
0
480
R/W
Ca01
tPS
Type of set point in multi-evaporator confi guration
0
0
1
0: TEMPERATURE
1: PRESSURE
R/W
tPU
Pressure set point set as:
0
0
1
0: TEMPERATURE
1: PRESSURE
R/W
Ca02
St
User temperature set point
2.0 (35.6)
°C (°F)
r1
r2
R/W
Current temperature set point (read-only)
°C (°F)
R
/4
Virtual probe composition (weighted average Sr, Sm)
0
%
0
100
R/W
Ca03
Kp
Temperature control diff erential
10
%/°C
1
200
R/W
tI
Compressor control integral time
500
s
0
999
R/W
Ca04
StP
Pressure control set point
5.8 (84.1)
barg (psig)
1.2 (17.3)
8.3 (121.9)
R/W
KpP
Pressure control proportional coeff .
10
%/bar
1
200
R/W
tiP
Compressor control integral time
500
s
0
999
R/W
Ca05
r0
Control off set with probe error (intake, outlet)
5.0 (9.0)
°C (°F)
0.0 (0.0)
20.0 (36.0)
R/W
Ca06
Enc
Enable cut-off
0
--
0
1
0: NO
1: YES
R/W
cof
Cut-off off set
2,0 (3.6)
°C (°F)
0
99,9 (179.8)
R/W
Cba01
r4
Set point off set in night mode
3.0 (5.4)
°C (°F)
-50.0 (-90.0)
50.0 (90.0)
R/W
Pressure set point off set in night mode
0
bar (psi)
-99.9 (-1.449) 99.9 (1.449)
r6
Enable night-time control on intake probe (Sr)
0
--
0
1
0: NO; 1: YES
R/W
HL
Enable lights off at night
1
--
0
1
0: NO; 1: YES
R/W
Cbb01
S1
Night time band 1
0
--
0
11
0: NONE
1: MON
2: TUE
3: WED
4: THU
5: FRI
6: SAT
7: SUN
8: MON-FRI
9: MON-SAT
10: WEEKEND
11: ALWAYS
R/W
hS1
Night start hours
0
h
0
23
R/W
mS1
Night start minutes
0
min
0
59
R/W
hE1
Night end hours
0
h
0
23
R/W
mE1
Night end minutes
0
min
0
59
R/W
Cbb02
S2
Night time band 2
0
--
0
11
0: NONE
1: MON
2: TUE
3: WED
4: THU
5: FRI
6: SAT
7: SUN
8: MON-FRI
9: MON-SAT
10: WEEKEND
11: ALWAYS
R/W
hS2
Night start hours
0
h
0
23
R/W
mS2
Night start minutes
0
min
0
59
R/W
hE2
Night end hours
0
h
0
23
R/W
mE2
Night end minutes
0
min
0
59
R/W
Cbb03
S3
Night time band 3
0
--
0
11
0: NONE
1: MON
2: TUE
3: WED
4: THU
5: FRI
6: SAT
7: SUN
8: MON-FRI
9: MON-SAT
10: WEEKEND
11: ALWAYS
R/W
hS3
Night start hours
0
h
0
23
R/W
mS3
Night start minutes
0
min
0
59
R/W
hE3
Night end hours
0
h
0
23
R/W
mE3
Night end minutes
0
min
0
59
R/W
Cc01
r1
Minimum control set point limit
-50.0 (-58.0) °C (°F) -50.0
(-58.0)
max
R/W
r2
Maximum control set point limit
50.0 (122.0) °C (°F)
min
50.0 (122.0)
R/W
Cc02
Pr1
Minimum pressure control set point limit
1.2 (17.3)
barg (psig)
1.2 (17.3)
8.3 (121.9)
R/W
Pr2
Maximum pressure control set point limit
8.3 (121.9)
barg (psig)
1.2 (17.3)
8.3 (121.9)
R/W