40
ENG
Heos
+0300078EN - rel. 1.6 - 23.11.2017
Mask index Par.
Description
Default
UOM
Min
Max
Possible value descr.
R/W
Bac10
/bA
Select showcase cleaning input position
0
--
0
5
0: --
1: DI1, ..., 4: DI4
5: MST
R/W
Showcase cleaning input status
0
--
0
1
0: CLOSED
1: OPEN
R
Select showcase cleaning input logic
0
--
0
1
0: N.C.; 1: N.A.
R/W
Showcase cleaning input function
0
--
0
1
0: NOT ACTIVE
1: ACTIVE
R
Bac11
/bb
Select inverter alarm input position
0
--
0
5
0: --
1: DI1, ..., 4: DI4
5: MST
R/W
Inverter alarm input status
0
--
0
1
0: CLOSED
1: OPEN
R
Select inverter alarm input logic
0
--
0
1
0: N.C.; 1: N.A.
R/W
Inverter alarm input function
0
--
0
1
0: NOT ACTIVE
1: ACTIVE
R
Bac12
/bC
Select showcase light input position
0
--
0
MaxPosDin
0: --
1: DI1, ..., 4: DI4
5: MST
R/W
Showcase light input status
0
--
0
1
0: CLOSED
1: OPEN
R
Select showcase light input logic
0
--
0
1
0: N.C.; 1: N.A.
R/W
Showcase light input function
0
--
0
1
0: NOT ACTIVE
1: ACTIVE
R
Bac14
A9
Select virtual digital input
0
--
0
4
R/W
Display type of virtual digital input
0
--
0
13
0: --
1: REMOTE ALARM
2: DELAYED REMOTE ALARM
3: ENABLE DEFROST
4: START NETWORK DEF.
5: DOOR CONTACT
6: REMOTE ON/OFF
7: DAY/NIGHT
9: COLD ROOM MAINT.
10: SHOWCASE CLEANING
11: INVERTER ALARM
12: SHOWCASE LIGHTS
13: CURTAIN CONTACT
R
Bac15
/bE
Select position of alarm input on compressor 1
0
--
0
5
0: --
1: ID1, ..., 4: ID4
5: U01, ..., 14: U10
R/W
Status of alarm input on compressor 1
0
--
0
1
0: CLOSED
1: OPEN
R
Select alarm input logic on compressor 1
0
--
0
1
0: N.C.; 1: N.O.
R/W
Alarm input function on compressor 1
0
--
0
1
0: NOT ACTIVE
1: ACTIVE
R
Bac16
/bF
Select position of alarm input on compressor 2
0
--
0
5
0: --
1: ID1, ..., 4: ID4
5: U01, ..., 14: U10
R/W
Status of alarm input on compressor 2
0
--
0
1
0: CLOSED
1: OPEN
R
Select alarm input logic on compressor 2
0
--
0
1
0: N.C.; 1: N.O.
R/W
Alarm input function on compressor 2
0
--
0
1
0: NOT ACTIVE
1: ACTIVE
R
Bac17
/bG
Select position of alarm input on compressor 3
0
--
0
5
0: --
1: ID1, ..., 4: ID4
5: U01, ..., 14: U10
R/W
Status of alarm input on compressor 3
0
--
0
1
0: CLOSED
1: OPEN
R
Select alarm input logic on compressor 3
0
--
0
1
0: N.C.; 1: N.O.
R/W
Alarm input function on compressor 3
0
--
0
1
0: NOT ACTIVE
1: ACTIVE
R
Bac18
/bH
Select position of alarm input on compressor 4
0
--
0
5
0: --
1: ID1, ..., 4: ID4
5: U01, ..., 14: U10
R/W
Status of alarm input on compressor 4
0
--
0
1
0: CLOSED
1: OPEN
R
Select alarm input logic on compressor 4
0
--
0
1
0: N.C.; 1: N.O.
R/W
Alarm input function on compressor 4
0
--
0
1
0: NOT ACTIVE
1: ACTIVE
R
Bac19
/bI
Select position of alarm input on compressor 5
0
--
0
5
0: --
1: ID1, ..., 4: ID4
5: U01, ..., 14: U10
R/W
Status of alarm input on compressor 5
0
--
0
1
0: CLOSED
1: OPEN
R
Select alarm input logic on compressor 5
0
--
0
1
0: N.C.; 1: N.O.
R/W
Alarm input function on compressor 5
0
--
0
1
0: NOT ACTIVE
1: ACTIVE
R
Bac20
/bI
Select dual temperature valve output position
0
--
0
5
0: --
1: ID1, ..., 4: ID4
5: U01, ..., 14: U10
R/W
Dual temperature valve output status
0
--
0
1
0: CLOSED
1: OPEN
R
Select dual temperature valve output logic
0
--
0
1
0: N.C.; 1: N.O.
R/W
Dual temperature valve output function
0
--
0
1
0: NOT ACTIVE
1: ACTIVE
R
Bad01
/EA
Select fan output 1 position
6
--
0
8
0: --
1: DO1, ..., 8: DO8
9: Y1
10: Y2
11: Y3
R/W
Fan output 1 status
0
--
0
1
0: OPEN
1: CLOSED
R
Select fan output 1 logic
0
--
0
1
0: N.A; 1: N.C.
R/W
Fan output 1 function
0
--
0
1
0: NOT ACTIVE
1: ACTIVE
R
Summary of Contents for Heos
Page 2: ......
Page 4: ...4 ENG Heos 0300078EN rel 1 6 23 11 2017 ...
Page 6: ......
Page 57: ...57 ENG Heos 0300078EN rel 1 6 23 11 2017 Notes ...
Page 58: ...58 ENG Heos 0300078EN rel 1 6 23 11 2017 Notes ...
Page 59: ......