12
ENG
Heos
+0300078EN - rel. 1.6 - 23.11.2017
2.7 General connection diagram
PAY ATTENTION
TO THE POWER SUPPLY!
Discharge temp. probe (CAREL NTC-HT)
LP Probe
HP Probe
Evap Fan
Lights
Defrost
L N
BUS pLAN for
Alarm
Rail Heaters
pGDe Terminal
pLD PRO
Expansion
Valve
Analog Input
Power supply
Analog Output (0-10V)
Digital Input (free voltage)
RS485 serial card
to connect
supervisory system
pLD Terminal
L
N
Fuse or
High press
switch
MCB
U
V
W
L
PE
K
N
-
DC
+DC
1 2
3 4 5 6 7
PTC
Klixon
Master/Slave
Suction temp. probe (CAREL NTC)
Air ON (return) probe (CAREL NTC)
Defrost probe (CAREL NTC)
Air OFF (supply) probe (CAREL NTC)
Digital Output
(POWERED)
Digital Output
(NOT POWERED)
Inverter 10A
Inverter 12/16A
White
Black
Green
White
Black
Green
Liquid
Injection
(optional)
(*)
(*)
(**)
J1
J9
J11
J12
J14
J16
J17
J18
J19
J20
J21
J22
J23
J24
J10
J13
J2
J3
J4
J5
J6
J8
J7
HEOS configuration
ON
1
2
OFF
DIP1=ON
DIP2=OFF
G
G0
Out2
C2
Out3
C2
Out4
C2
Out5
C2
C2
V-IN
N06
C6
N07
C7
N08
C8
U8
U9
U10
+Vdc
+5VR
GND
RX-/TX-
RX+/TX+
GND
RX-/TX-
RX+/TX+
GND
Vout
RX-/TX-
RX+/TX+
GND
N01
NC1
C1
U4
U5
+Vdc
+5VR
GND
U6
U7
+Vdc
+5VR
GND
DI1
DI2
DI3
DI4
GND
U1
U2
U3
GND
GND
(A01) Y1
(A02) Y2
(A03) Y3
- for UP2A*: 230 Vac 50/60 Hz, +10%/-15%;
- for UP2B*: 24 Vac +10%/-15% 50/60 Hz,
28 to 36 Vdc +10%/-15%;
L2/N L3
U
V
W
L1/L
1 2
3 4 5
8
6 7
9 10
PTC
Klixon
to HEOS controller
M
3
M
3
Fuse or
High press
switch
MCB
L
K
N
PE
to HEOS controller
to power+
GND
+
-
GND
+
-
Fig. 2.m
(*) The 4-20 mA pressure probes are connected as follows: white to Ux and black to +Vdc, green not used
(**) 230 Vac SSR output, maximum switchable power 15VA
Important:
Class A software: the safety devices providing overload and high pressure protection must control the compressor directly, and consequently need
to be wired in series with compressor contactor control signal. For the type of cable to use, refer to power+ manual (cod. +0300048IT).
I/O selection table
Par.
Description
(
A
nalogue inputs)
/FA
Air outlet temperature (default U1)
/Fb
Defrost temperature (default U2)
/Fc
Air intake temperature (default U3)
/P3
Condensing pressure (default U7)
/P4
Suction pressure (default U5)
/P1
Discharge temperature (default U6)
/P2
Suction temperature (default U4)
/Fq
Liquid temperature
/FI
Room temperature
/FL
Room humidity
/FM
Glass temperature
/FW
Condenser water inlet temperature
/FY
Condenser water outlet temperature
/FG
Auxiliary probe 1
/FH
Auxiliary probe 2
Par.
Description
(
D
igital inputs)
/b1
Remote alarm
/b2
Delayed remote alarm
/b3
Enable defrost
/b4
Start network defrost
/b5
Door switch
/b6
Remote ON/OFF
/b7
Curtain/light switch - day/night
/b8
Continuous cycle
/b9
Cold room maintenance
/bA
Showcase cleaning
/bb
Inverter alarm
/bC
Lights
/A9
Virtual input
/bl
Dual temperature
Par.
Description
(
A
nalogue outputs)
/LA
EC evaporator fans
/Lb
Anti-sweat heaters
/Lc
Water control valves
/Ld
Condenser pump
/LE
Auxiliary output
/LF
Water-cooled condenser output
/LG
Air-cooled condenser output
Par.
Description
(
D
igital outputs)
/EA
Fans 1 (default DO6)
/EC
Lights (default DO7)
/Ed
Defrost heaters (default DO8)
/EE
Alarms
/EF
Auxiliary output
/EG
Anti-mist heaters
/EM
Liquid injection solenoid
/EN
Curtain contact
/Eo
ON/OFF compressor
/Er
Inverter valve output
/ES
Fan/condenser output
/EY
Dual temperature output
Summary of Contents for Heos