32
ENG
"humiFog direct" +0300073EN rel. 1.4 - 29.03.2022
Type
Section
Address
Parameter
Variable
Size Min. Max. Def.
UoM
Dir.
Coils
Remote
control
1
Alarms reset
Alarms.AlrmResBySV
1
0
1
0
R/W
2
Unit on/off from supervisor
OnOff _Status.SVOn
1
0
1
0
R/W
Holding
registers
Remote
control
1
Unit request from supervisor zone 1
Regulation.SVReq_1
2
0
100
0
[%]
R/W
3
Unit request from supervisor zone 2
Regulation.SVReq_2
2
0
100
0
[%]
R/W
5
Setpoint zone 1 (humidity)
RegCfg_1.SetP_hum
2
0
100
50
[%rh]
R/W
7
Setpoint zone 1 (temperature)
RegCfg_1.SetP_temp
2
50
[°C]/[°F]
R/W
9
Setpoint limit zone 1 (humidity)
RegCfg_1.SetPLim_hum
2
0
100
50
[%rh]
R/W
11
Setpoint limit zone 1 (temperature)
RegCfg_1.SetPLim_temp
2
50
[°C]/[°F]
R/W
13
Setpoint zone 2 (humidity)
RegCfg_2.SetP_hum
2
0
100
50
[%]
R/W
15
Setpoint zone 2 (temperature)
RegCfg_2.SetP_temp
2
50
[°C]/[°F]
R/W
17
Setpoint limit zone 2 (humidity)
RegCfg_2.SetPLim_hum
2
0
100
50
[%]
R/W
19
Setpoint limit zone 2 (temperature)
RegCfg_2.SetPLim_temp
2
50
[°C]/[°F]
R/W
Tab. 10.b
10.4 List of BACnet parameters
Type
Section
BACNet
Parameter
Variable
Min. Max. Def.
UoM
Dir
Binary
values
Unit status 0
Unit on/off UnitOn
0
1
R
Alarms
1
Circuit breaker intervention
Al_CircBreaker.Active
0
1
R
2
High pressure switch intervention
Al_HiPSwitch.Active
0
1
R
3
High pressure
Al_HiP.Active
0
1
R
4
Low pressure
Al_LoP.Active
0
1
R
5
High pressure on bypass
Al_HiPByPassBlk.Active
0
1
R
6
High pressure on bypass
Al_HiPByPass.Active
0
1
R
7
High temperature on bypass
Al_HiTByPassBlk.Active
0
1
R
8
High temperature on bypass
Al_HiTByPass.Active
0
1
R
9
Low pressure on bypass
Al_LoPByPass.Active
0
1
R
10
Zone drain valves error
Al_Drain.Active
0
1
R
11
Expansion offl
ine
Al_ExpOffl
ine.Active
0
1
R
12
Warning high temperature on bypass
Wr_HiTByPass.Active
0
1
R
13
Retain memory error
Al_Retain.Active
0
1
R
14
Retain memory writes error
Al_RetainWrite.Active
0
1
R
15
Main probe 1 error
Al_MainPrb_1.Active
0
1
R
16
Limit probe 1 error
Al_LimPrb_1.Active
0
1
R
17
Main probe 2 error
Al_MainPrb_2.Active
0
1
R
18
Limit probe 2 error
Al_LimPrb_2.Active
0
1
R
19
Low pressure trasducer error
Al_PressByPass.Active
0
1
R
20
Bypass temperature probe error
Al_TempByPass.Active
0
1
R
21
High pressure transducer error
Al_Press.Active
0
1
R
22
Missing model
Al_MissModel.Active
0
1
R
23
Water treatment system alarm
Al_WTS.Active
0
1
R
24 ÷ 31
Wireless probe offl
ine 1 ÷ 8
Al_WPrb_1 ÷ 8.Active
0
1
R
32
Main probe 1 from wireless error
Al_WPrbMain_1.Active
0
1
R
33
Limit probe 1 from wireless error
Al_WPrbLim_1.Active
0
1
R
34
Main probe 2 from wireless error
Al_WPrbMain_2.Active
0
1
R
35
Limit probe 2 from wireless error
Al_WPrbLim_2.Active
0
1
R
36 ÷ 39
Unit 1 ÷ 4 alarm
Al_NetUnit_1 ÷ 4.Active
0
1
R
40
Change oil
Al_Maint_50.Active
0
1
R
41
Maintenance
Wr_Maint_1000.Active
0
1
R
42
Maintenance required
Al_Maint_3000.Active
0
1
R
Remote
control
43
Alarms reset
Alarms.AlrmResBySV
0
1
0
RW
44
Unit on/off from supervisor
OnOff _Status.SVOn
0
1
0
RW
P.I.V.
Unit status 0
Unit status
0: OFF BY KEYB
5: STAND BY
10: MANUAL MODE
1: OFF BY DIN
6: PRODUCTION
11: READY BACKUP
2: OFF BY SV
7: ALARM
12: SWITCH OFF
3: OFF BY SCHED
8: FILL
4: STARTUP
9: WASH
UnitStatus
1
0
12
R
Analog
values
Unit status 0
Request zone 1
ReqMsk_1
0
100
[%]
R
1
Request zone 2
ReqMsk_2
0
100
[%]
R
2
Production zone 1
Prod_1
0
100
[%]
R
3
Production zone 2
Prod_2
0
100
[%]
R
4
Water consumption 1
WProd_1
[Kg/h]/[lb/h]
R
5
Water consumption 2
WProd_2
[Kg/h]/[lb/h]
R
Inputs
6
Main probe 1
MainPrb_1
[%rh]/[°C/°F]
R
7
Main probe 2
MainPrb_2
[%rh]/[°C/°F]
R
8
Limit probe 1
LimPrb_1
[%rh]/[°C/°F]
R
9
Limit probe 2
LimPrb_2
[%rh]/[°C/°F]
R
10
Pressure on bypass
PressByPass
[bar]/[psi]
R
11
Pressure on mail line
Press
[bar]/[psi]
R
12
Bypass temperature
TempByPass
[°C]/[°F]
R
13-15-17-19-
21-23-25-27
Humidity from wireless probe 1 ÷ 8
Inputs_WPrbs.WirelessPrbVal_1
÷ 8.Hum
[%rh]
R
14-16-18-20-
22-24-26-28
Temperature from wireless probe 1 ÷ 8
Inputs_WPrbs.WirelessPrbVal_1
÷ 8.Temp
[°C]/[°F]
R
Remote
control
29
Unit request from supervisor zone 1
Regulation.SVReq_1
0
100
0
[%]
RW
30
Unit request from supervisor zone 2
Regulation.SVReq_2
0
100
0
[%]
RW
31
Setpoint zone 1 (humidity)
RegCfg_1.SetP_hum
0
100
50
[%rh]
RW
32
Setpoint zone 1 (temperature)
RegCfg_1.SetP_temp
50
[°C]/[°F]
RW
33
Setpoint limit zone 1 (humidity)
RegCfg_1.SetPLim_hum
0
100
50
[%rh]
RW
34
Setpoint limit zone 1 (temperature)
RegCfg_1.SetPLim_temp
50
[°C]/[°F]
RW
35
Setpoint zone 2 (humidity)
RegCfg_2.SetP_hum
0
100
50
[%]
RW
36
Setpoint zone 2 (temperature)
RegCfg_2.SetP_temp
50
[°C]/[°F]
RW
37
Setpoint limit zone 2 (humidity)
RegCfg_2.SetPLim_hum
0
100
50
[%]
RW
38
Setpoint limit zone 2 (temperature)
RegCfg_2.SetPLim_temp
50
[°C]/[°F]
RW
Tab. 10.c