36
ENG
"humiFog direct" +0300073EN rel. 1.4 - 29.03.2022
Alarm
Code Cause
Solution
Reset
Alarm relay
Action
Wireless probe 5 offl
ine
ALP12 No communication
with probe 5
Verify:
• the probe/access point association
• battery
status
• the signal level of the probe
Automatic
Active
Signal
Wireless probe 6 offl
ine
ALP13 No communication
with probe 6
Verify:
• the probe/access point association
• battery
status
• the signal level of the probe
Automatic
Active
Signal
Wireless probe 7 offl
ine
ALP14 No communication
with probe 7
Verify:
• the probe/access point association
• battery
status
• the signal level of the probe
Automatic
Active
Signal
Wireless probe 8 offl
ine
ALP15 No communication
with probe 8
Verify:
• the probe/access point association
• battery
status
• the signal level of the probe
Automatic
Active
Signal
Main probe 1 offl
ine
ALP16 No communication
with all wireless probes
- main control zone 1
Verify:
• probe
connection
• association of probes with access point
• access point power supply
Automatic
Active
Signal
Limit probe 1 offl
ine
ALP17 No communication
with all wireless probes
- limit control zone 1
Verify:
• probe
connection
• association of probes with access point
• access point power supply
Automatic
Active
Main probe 2 offl
ine
ALP18 No communication
with all wireless probes
- main control zone 2
Verify:
• probe
connection
• association of probes with access point
• access point power supply
Automatic
Active
Signal
Limit probe 2 offl
ine
ALP19 No communication
with all wireless probes
- limit control zone 2
Verify:
• probe
connection
• association of probes with access point
• access point power supply
Automatic
Active
Signal
Unit 1 in alarm
ALN01 Network unit no. 1 in
alarm
Only if network function is active
Perform checks according to the alarm displayed on the
machine concerned
Automatic
Active
Signal
Unit 2 in alarm
ALN02 Network unit no. 2 in
alarm
Only if network function is active
Perform checks according to the alarm displayed on the
machine concerned
Automatic
Active
Signal
Unit 3 in alarm
ALN03 Network unit no. 3 in
alarm
Only if network function is active
Perform checks according to the alarm displayed on the
machine concerned
Automatic
Active
Signal
Unit 4 in alarm
ALN04 Network unit no. 4 in
alarm
Only if network function is active
Perform checks according to the alarm displayed on the
machine concerned
Automatic
Active
Signal
High bypass temperature
WRA12 Bypass water
temperature > 50°C
Prolonged recirculation of water through the bypass is
possible. Verify:
• that the humidifi cation capacity set on the Dc18
screen is equal to no. of nozzles x capacity of the
single nozzle;
• that the zone is capable of delivering a water fl ow rate
≥ the minimum fl ow rate supplied by the pump;
• that the NTC probe is connected to terminals J5.2-J5.3
-
Not Active
Notice
Visual hydraulic check
WRA14 Pump check required
• Every 1000 operating hours check the wear condition
of the oil and the pump
Manual
Not Active
Signal
Low pressure
-
Pressure measured by
RHP probe < 60 bar
with active pump
Possible small leak in water delivery, check the tightening
of the pipe fi ttings and the absence of leakage from the
DR1 and DR2 discharge solenoid valves.
Verify that the pump is capable of delivering the required
fl ow rate to meet the nozzle load.
-
Not Active
Notice
Tab. 12.a