average will be calculated between the main probes, depending on the 
defi ned weight, and the limit probes will also have their own average, 
again depending on the defi ned weight. For “humidity (two probes)“ or 
“temperature (two probes)” control, only a group of main probes can be 
defi ned. Wired probes can be connected to the main probe input (M2.1) 
and the limit probe input (M2.5), which will be used as a second probe, 
with the average calculated. If using wireless probes (maximum of four), 
only a group of main probes can be defi ned, with the average calculated, 
depending on the defi ned weight. For the connections of the signals 
and/or probes, see chap. 4. 

8.2.4 

Weighted average of the probes (installer menu)

If using two temperature probes or two humidity probes, the humidifi er 
controller will calculate the weighted average of the probe readings. 
In this way, two probes can be used, for example humidity probes, at 
opposite ends of the room, calculating the average. 

Index

Description

Parameter

Da03
Da06

Weight of the 
probes

Set the weight of the probes
Default: 100
Possible settings: 0 to 100
Step: 1

 
The weight of each probe should be expressed with a value from 0 to 
100. 

The weighted average is calculated as follows:
Weighted average =   ((S1×p1)+(S2×p2))

                                    ----------------------------
                                               (p1+p2)

where “Si” is the probe reading, and “pi” the relative weight.

To calculate the arithmetic average, equal weights should be set (for 
example: p1 = p2 = 100).

8.3 Functions

8.3.1 Filling

For correct functioning of the system there must be no air in the lines, so 
as to avoid vibrations, unstable pressure and poor quality atomisation. To 
eliminate all air, the fi lling time must be set correctly. When starting the 
system the fi rst time, measure the time required for the water to reach 
the end of the circuit, and wait only until water visibly comes out of the 
circuit. The longer the water circuit, the higher the fi lling time needs to 
be. 

With reference to the high pressure hose supplied (Øint=6.3 mm), it is 
recommended to set the times indicated in the table.

Pumping station

40/50 l/h

80/90 l/h

Time

1 min per 15 m of 

tubing

1 min per 30 m of 

tubing

Ref.

Display

Description

Range Def UoM

Db01 En. fi lling When the pumping station needs 

to start and the water supply line is 
detected as being empty, i.e. when 
fi rst starting, enabling the pump, 
starting again for the new season 
etc., by setting the parameter to Yes, 
the pump delivers the fl ow-rate for 
the time defi ned by the following 
parameter, so as to fi ll the line before 
atomisation commences

Yes/No Yes

Duration

Line fi lling time before starting ato-
misation, only if the water supply line 
is detected as beeing empty

1/60

2

min

Tab. 8.c 

8.3.2 Washing

The washing function involves fl ushing all of the water pipes for a set 
time. The purpose is to completely wash the system and avoid stagnation.

Ref.

Display

Description

Range

Def

UoM

Db02 Washing: 

periodical 
daily
Disable 
washing

washing carried out after 
a set number of hours of 
inactivity.
Washing performed daily at a 
predefi ned time
Washing disabled

periodical
daily
disabled

peri-
odical

type

Interval
Time

Number of hours of inactiv-
ity after which a periodical 
washing cycle is performed
Time of day when the daily 
washing cycle is performed

0/99
0/24

12
0

h
h

Duration
Duration

Periodical washing cycle time 
in minutes
Daily washing cycle time in 
minutes

0/60
0/60

4

min

Tab. 8.d 

NOTICE: (*) it is advisable to set a washing time twice as long as the fi lling 
time.

8.3.3 

Blower fan management

The blower fans that atomise the water can be started before atomisation 
commences, so as to reach an air fl ow that can support atomisation 
when this starts.
A delay can be set for stopping the fans when atomisation ends, so as to 
guarantee air fl ow immediately after the end of atomisation.

Ref.

Display

Description

Range

Def

UoM

Db04 On ad-

vance

Start fans in advance before 
starting atomisation

0-10

3

s

Off  delay

Delay in stopping fans after 
atomisation ends

3-120

10

s

Tab. 8.e 

8.4 Confi gurations

8.4.1 

Main humidity probe setting

The main probe can be confi gured on screen index Dc01 for the single-
zone and Dc07 for two-zone cabinets.

Index Description Parameter

Dc01
Dc07

Main probe Main probe confi guration

Default: Enable: Enabled (depending on the type of 
control)
Type: 0-10 V
Minimum: 0% rH - Maximum: 100% rH
Off set: 0
En. Al (enable alarms): Yes
Del: 60 seconds
Possible settings: 
Type 0-10 V/0-1 V/NTC/4-20 mA/0-20 mA/2-10 V
Minimum: 0-100% rH - Maximum: 0-100% rH
Off set: 0
En. Al (enable alarms): Yes
Del: 0-600 seconds

Tab. 8.f 

For each probe, after having specifi ed the type, the minimum and 
maximum values readable can be defi ned, as well as an “off set”  to 
compensate for any imprecisions in the value read (example: off set  = 
3% rH corresponds to a 3 percent increase in the humidity value read by 
the probe). The "En. Al." parameter enables the alarms corresponding to 
probe faults. If a fault is detected for longer than the value of the "Delay" 
parameter (seconds), the "main probe broken or disconnected" alarm will 
be activated.

Summary of Contents for DLAQ2DF100

Page 1: ...NO POWER SIGNAL CABLES TOGETHER READ CAREFULLY IN THE TEXT humiFog direct User manual...

Page 2: ......

Page 3: ...om an ext controller 17 6 5 Digital signal from humidistat or external controller 17 6 6 Serial or Ethernet communication 17 6 7 Alarm relay output 17 6 8 Unit status digital output 17 6 9 Production...

Page 4: ...4 ENG humiFog direct 0300073EN rel 1 4 29 03 2022...

Page 5: ...al use of the product Do not attempt to open the humidifier in any way other than described in the manual This installation operation and maintenance manual must be kept in paper format in a safe and...

Page 6: ...be operated with a DC power supply Regularly check that all safety and monitoring devices are working properly Do not remove or disable the safety devices NOTICE Possibility of water leaks due to faul...

Page 7: ...perature or humidity or external controller When the operation consent is enabled remote ON OFF and at the same time there is a request for humidification or cooling the system opens the delivery sole...

Page 8: ...lower units differ based on the number of nozzles the type of nozzles the nozzles are already pre assembled in the factory power supply voltage frequency and the direction of spray front or two direct...

Page 9: ...High pressure sensor 9 Temperature controlled safety valve 10 High pressure sensor 11 Temperature sensor 12 Overflow valve 13 Drain solenoid valve 14 Bypass solenoid valve 15 NC fill solenoid valve 16...

Page 10: ...already assembled in cardboard boxes The user is responsible for removing the blower from the packaging removing the side plastic covers so as to make the water and electrical connections and then re...

Page 11: ...ical connections the appliance must be disconnected from the mains power supply and must be prevented from being powered on Electrical disconnection must be verified by measurement NOTE observe the lo...

Page 12: ...by at least 20 30 cm NOTICE the drain water must be able to flow freely 4 2 4 Blower water supply line With reference to the high pressure hoses provided by CAREL inside diameter 6 3 mm in order to e...

Page 13: ...r a correct installation see the example or contact Carel for different temperature and humidity conditions 4 3 1 Fuses The following table lists the technical specifications of the fuses supplied for...

Page 14: ...g drilled the holes in the wall fix the metal support using anchor screws not supplied Then attach the blower to the protrusions on the wall mounting support bracket Fix the blower unit to the bracket...

Page 15: ...he cables through the cable glands and in accordance with local safety standards Also check that the cable is the right size for the distance and voltages used Carel recommends an AWG14 or AWG12 cable...

Page 16: ...uts 1 IN a 2 GND 3 12 Vdc on terminal M2 The limit probe optional is used for the auxiliary function to reduce humiFog Direct humidification or cooling capacity when approaching a set humidity or temp...

Page 17: ...humiFog Direct parameters and sends commands To connect a supervisor the RS485 serial port terminal M12 inputs 1 Tx Rx 2 Tx Rx 3 GND or Ethernet port is used The choice of which port to use depends o...

Page 18: ...unit Step 1 10 Enter the humidifier model Step 2 10 Enter the humidification load in kg h for zone 1 and if present zone 2 The humidification load can be easily calculated by multiplying the number of...

Page 19: ...s the HOME icon Fig 7 e 7 3 2 Set point quick menu Press the icon to access the menu The menu is used to modify the set point and proportional control band Press the white number to change the value E...

Page 20: ...to the previous display press To return to the home menu press the HOME icon Fig 7 l 7 3 7 Notification centre Press the icon to access the notification centre To view the details of an individual not...

Page 21: ...ss the icon to access the function The same screen is displayed which is also accessible from the input output quick menu 7 3 14 Graphs Press the icon to access the function The graphs function is use...

Page 22: ...n to change the unit of measure Press the icon to update the display application from a USB pendrive Press the icon to access the configuration wizard or factory data reset Press the icon to access th...

Page 23: ...Dc08 Set the type of signal for the main temperature probe in zone 2 minimum maximum probe reading probe offset enable disconnected probe alarm and set the alarm delay Dc09 Set the type of external s...

Page 24: ...nalY selectable from the following options 0 to 1 Vdc 0 to 10 Vdc 2 to 10 Vdc 0 to 20 mA 4 to 20 mA The maximum production Pmax corresponds to the maximum value of the external signal Y and will be th...

Page 25: ...pump delivers the flow rate for the time defined by the following parameter so as to fill the line before atomisation commences Yes No Yes Duration Line filling time before starting ato misation only...

Page 26: ...responding to probe faults If a fault is detected for longer than the value of the Delay parameter seconds the main probe broken or disconnected alarm will be activated 8 4 5 Temperature limit probe s...

Page 27: ...itch Carel markets a switch P N KITSE08000 that can connect a maximum of eight units 8 Ethernet ports If necessary use several KITSE08000 switches with a cascaded arrangement Main technical specificat...

Page 28: ...et the maximum capacity go to menu Dd03 The Capacity parameter identifies the maximum production request for the Main Secondary system and can therefore be set by the user The Maximum capacity paramet...

Page 29: ...N buttons to display the details of all the units 9 4 5 Software backup function in the Main Secondary system Main Secondary mode can also be used to manage the software backup function if one or more...

Page 30: ...etwork parameters subnet mask and gateway The disadvantage is that if adding other devices to the same network with humiFog Direct off and not connected the IP address originally assigned to the unit...

Page 31: ...iTByPass Active 1 0 1 R 9 Low pressure on bypass Al_LoPByPass Active 1 0 1 R 10 Zone drain valves error Al_Drain Active 1 0 1 R 11 Expansion offline Al_ExpOffline Active 1 0 1 R 12 Warning high temper...

Page 32: ...High pressure transducer error Al_Press Active 0 1 R 22 Missing model Al_MissModel Active 0 1 R 23 Water treatment system alarm Al_WTS Active 0 1 R 24 31 Wireless probe offline 1 8 Al_WPrb_1 8 Active...

Page 33: ...for industrial use Battery WS01G01M00 SA probe Room tempera ture humidity Battery WS01AB2M20 Access Point Gateway radio ZigBee RS485 Modbus 12 24 Vac dc 10 100 mA 50 60 Hz Use a Class II safety trans...

Page 34: ...DR2 zone discharge and BYP bypass discharge solenoid valves NO valves 24Vac to close that filling is enabled with a duration that is appropriate to the length of the water line If necessary replace th...

Page 35: ...shown in the wiring diagram that c pCOe is powered 24Vac between G G0 on terminal J1 Automatic Active Humidification interrupted Oil change requested ALA13 Pump oil change requested Change pump oil a...

Page 36: ...tion of probes with access point access point power supply Automatic Active Signal Unit 1 in alarm ALN01 Network unit no 1 in alarm Only if network function is active Perform checks according to the a...

Page 37: ...nciple the requirements for air humidification according to VDI 6022 1 must be observed All tests and measurements shall be documented in a logbook available for inspection The user is responsible for...

Page 38: ...irst 50 hours of operation the oil in the pump needs to be changed P N 5024646AXX Failure to change the oil after the first 50 hours may cause damage to the pump and reduce its working life The first...

Page 39: ...same occurs after 2000 hours of operation After 3000 hours of operation instead humiFog direct generates a non blocking request for oil change and parts replacement alarm In this case the machine mus...

Page 40: ...oil 5024646AXX 7 High pressure gauge scale 0 100 bars radial fitting 1 4 GAS UAKMWHP001 8 Pump high pressure switch calibration 90 bars UAKPSHP000 9 Temperature controlled safety valve 1309549AXX 10 R...

Page 41: ...41 ENG humiFog direct 0300073EN rel 1 4 29 03 2022 14 APPENDIX 14 1 Single zone wiring diagram GA1 Fig 14 a...

Page 42: ...42 ENG humiFog direct 0300073EN rel 1 4 29 03 2022 14 2 Two zone wiring diagram GA1 Fig 14 b...

Page 43: ...Rating 5 kA 5 kA Minimum cable size required for blower power supply AWG 14 AWG 14 Tab 14 b WATER CIRCUIT SPECIFICATIONS UA040DD 01 UA080DD 01 Required feedwater quality Feed water temperature deminer...

Page 44: ...0 20 mA NTC probe Multi probe available available Webserver available available Serial communication via Ethernet and or via RS485 Modbus BACnet Modbus BACnet Tab 14 h 14 3 3 CE version blower datashe...

Page 45: ...050 AWG 14 with UA050 AWG 12 with UA090 AWG 12 with UA090 Maximum number of blower units connected to one cabinet 12 6 Tab 14 k Double blower units for mounting in centre of corridor UL version DLA04U...

Page 46: ......

Page 47: ......

Page 48: ...INDUSTRIES Headquarters Via dell Industria 11 35020 Brugine Padova Italy Tel 39 049 9716611 Fax 39 049 9716600 e mail carel carel com www carel com Agenzia Agency humiFog direct 0300073EN rel 1 4 29 0...

Reviews: