17
ENG
"humiFog direct" +0300073EN rel. 1.4 - 29.03.2022
6.4 Analogue signal from an ext. controller
As an alternative to the main probe, a signal from an external controller
can be used. The latter processes the request to send to humiFog Direct
via an analogue signal, which varies from 0 to 100%. humiFog will adjust
the capacity delivered proportionally to the signal received, and the
display will show the request sent as a percentage.
The following types of proportional signals are allowed:
•
4-20 mA, 0-20 mA current signals
•
0-10 V, 0-1 V, 2-10 V voltage signals
The external signal for the fi rst zone is connected to the c.pHC controller
via inputs 1 [IN a] and 2 [GND] on terminal M2.
The external signal for the second zone is connected to the c.pCOe
controller via inputs U1 [IN a] and [GND] on the terminal J2.
M2
M9
1 2
1
1 2 3
1 2 3
4 5
2
1 2
1
1
2
2
1 2 3 4 5 6
J17C
GA1
2 1
J17L
J23
J24
J19
J20
J3
J16
M3
J18
2 1
J21
M8
M1
M5
M6
M12
1
1
2
3
4
5
6
7
8
2
1
1
3 2
3
1
2
2
1
2
1
2
Ethernet
EXTERNAL SIGNAL ZONE 1
[IN
a
] [GND]
[IN
a
] [GND]
EXTERNAL SIGNAL
ZONE 2
Fig. 6.e
Fig. 6.f
The limit probes can also be associated with the external proportional
signal, and will be connected as shown in the previous paragraphs. For
the fi rst zone to c.pHC control: inputs 5, 6 and 3 to M2 connector. For the
second zone to the c.pCOe expansion card: U2 and GND of connector J2
and voltage supply to Vdc terminal of connector J9.
6.5 Digital signal from humidistat or
external controller
The signal from the external controller can be replaced by the signal from
a humidistat, thermostat, or any external device with digital contact. In
this case, humiFog Direct will work in ON/OFF mode, either delivering
100% of fl ow-rate or remaining in standby. The capacity delivered can
be reduced by setting parameter P0 (the reduction is managed by PWM,
see paragraph "Settings"). The electrical connection is the same as in
the previous case (see fi gure in para. "Analogue signal from external
controller"). WARNING: confi gure the setting of humiFog Direct (via
display screens), so that it can be controlled by an ON/OFF signal from an
external controller or device.
6.6 Serial or Ethernet communication
humiFog Direct can be controlled by a supervisor that reads the humiFog
Direct parameters and sends commands. To connect a supervisor, the
RS485 serial port (terminal M12, inputs 1 [Tx/Rx-] 2 [Tx/Rx+] 3 [GND]) or
Ethernet port is used. The choice of which port to use depends on the
supervisor. Modbus and BACnet communication protocols are available
as standard: no auxiliary cards need to be fi tted on the c.pHC controller
M2
M9
1 2
1
1 2 3
1 2 3
4 5
2
1 2
1
1
2
2
1 2 3 4 5 6
J17C
GA1
2 1
J17L
J23
J24
J19
J20
J3
J16
M3
J18
2 1
J21
M8
M1
M5
M6
M12
1
1
2
3
4
5
6
7
8
2
1
1
3 2
3
1
2
2
1
2
1
2
ETHERNET
SERIAL RS4
8
5
1 [Tx/Rx-]
2 [Tx/Rx+]
GND
Fig. 6.g
The Ethernet port can also be used for the Webserver function (see cap.
"Connectivity"), so as to monitor and control humiFog Direct via a local
network, without needing a supervisor.
6.7 Alarm relay output
The digital output for communication of an alarm status is connected to
contacts 1-2-3 on terminal M6 on the c.pHC. N.C. logic is set by connecting
the two wires to contacts 1-2, while N.O. logic is set connecting the two
wires to contacts 1-3.
M2
M9
1 2
1
1 2 3
1 2 3
4 5
2
1 2
1
1
2
2
1 2 3 4 5 6
J17C
GA1
2 1
J17L
J23
J24
J19
J20
J3
J16
M3
J18
2 1
J21
M8
M1
M5
M6
M12
1
1
2
3
4
5
6
7
8
2
1
1
3 2
3
1
2
2
1
2
1
2
ALAR
M
RELAY
N.C.
N.O.
Fig. 6.h
6.8 Unit status digital output
The c.pHC controller provides a digital output corresponding to unit status.
This is a voltage-free contact that provides the following information:
•
contact closed: unit on or in standby
•
contact open: unit off (OFF from keypad or from remote contact, or
no power)
The unit status digital output is available at contacts 1-2 on terminal M5
on the c.pHC.
6.9 Production percentage analogue
outputs
The c.pHC controller provides an analogue output (0-10 V) corresponding
to the percentage of production that humiFog Direct is delivering.
The output replicates the request signal relating to the corresponding
humiFog Direct zone.
The production percentage analogue outputs are connected to the
following terminals:
•
zone 1: outputs 1 and 2 on terminal M8 on the c.pHC.
•
zone 2: outputs U3 and GND on terminal J2 on the c.pCOe.
M2
M9
1 2
1
1 2 3
1 2 3
4 5
2
1 2
1
1
2
2
1 2 3 4 5 6
J17C
GA1
2 1
J17L
J23
J24
J19
J20
J3
J16
M3
J18
2 1
J21
M8
M1
M5
M6
M12
1
1
2
3
4
5
6
7
8
2
1
1
3 2
3
1
2
2
1
2
1
2
% PRODUC
.
ZONE 1
% PRODUCTION
ZONE 2
SYSTE
M
STATUS
Fig. 6.i
Important
: when several GND contacts are wired to the same terminal
these are equivalent to each other, and can be used indiff erently.
Summary of Contents for DLAQ2DF100
Page 1: ...NO POWER SIGNAL CABLES TOGETHER READ CAREFULLY IN THE TEXT humiFog direct User manual...
Page 2: ......
Page 4: ...4 ENG humiFog direct 0300073EN rel 1 4 29 03 2022...
Page 42: ...42 ENG humiFog direct 0300073EN rel 1 4 29 03 2022 14 2 Two zone wiring diagram GA1 Fig 14 b...
Page 46: ......
Page 47: ......