18
19
English
Spanish French
CUBIC METERS
Display Unit
Of Measure
Language
Language
System
Type
The following actions will change the system
parameters, enter the confirmation needed
for set up.
Please Enter Code: 1234
System Type
System Setting
BNT 950
BNT 950-X
YES
NO
System Type
Valve Type:
BNT 950
Softener (Demand Flow)
Filter (Time Clock)
Filter (Meter Delay)
Filter (Meter Immediate)
Filter (Pressure Drop)
Slave Valve NO.:
01
06
Format Slave Valve NO.:
01 Enter
Restore History Data
From Slave Valve:
01 Enter
Restore Setting
From Slave Valve:
01 Enter
1st
Last
Current Mode: Softener
Change to: Filter
(Time Clock)
Change SYS Type
Valve Type
RestoreSetting
has been completed!
Restore
Restore History Data
has been completed!
Restore
Format Slave Valve
has been completed!
Total 4 Units.
Format
ADVANCED PROGRAMMING
(CONTINUED)
FORMATTING SLAVE & MASTER PCB’S
For standard MTS system single valve the default Valve Type is BNT 950. For the 2 piston valve the type is BNT 950-X
When changing from different System Types, a page will displayed that will confirm you want to change the System Type. Select Yes to change the
type and No to keep the current settings. A System Setting page will be displayed. Press the MENU button to exit the System
Setting page and return to the Main Menu.
If you wish to erase the current valve history (Diagnostic Information), it will be necessary to format the slave PCB’s. If you are changing a valve PCB
and want to restore the history and settings, you need to use the “Restore History Data” and “Restore Setting” options, respectively.
The Format Slave Valve function wipes out all the stored settings in the slave PCB. The Restore History Data function will upload the stored settings
from the slave PCB to the main PCB. The Restore Settings function will transfer the saved settings from main PCB back to the slave PCB.
RE-FORMAT (ERASE) SLAVE PCB SETTINGS & HISTORY DATA
If you wish to reset the history (System Diagnostics) back to zero and start tracking new data the Slave PCB’s can be re-formatted. You may choose
the individual Slave Valve No. or ALL. When you press enter, the history data will be erased and set to zero values.
RESTORE MAIN PCB SETTINGS
If you replace the main PCB, you can restore the current settings and history from the Slave PCB’s to the Main PCB. Select Restore History Data to
restore history data from Slave PCB’s to new Master PCB. Select Restore Setting to restore valve settings (People, Hardness, Backwash Time, etc,)
from Slave Valve PCBs to Main PCB.