Peak Period
Block Out
Start 1 End 1
Start 2 End 2
Peak Period Block Out
MON.
06:00 09:00 17:00 19:00
TUES.
06:00 09:00 17:00 19:00
WED.
06:00 09:00 17:00 19:00
THURS.
06:00 09:00 17:00 19:00
FRI.
06:00 09:00 17:00 19:00
SAT.
06:00 09:00 17:00 19:00
SUN.
06:00 09:00 17:00 19:00
Trip Point
Settings
Trip Flow Rate (GPM
ON
OFF
Trip
Delay
(SEC)
Trip Point Settings
Unit 1st
30 15 10
Unit 2nd
30 30 20
Unit 3rd
30 45 30
Unit 4th
30 60 40
Unit 5th
30 75 50
Trip Flow Rate (GPM
ON
OFF
Trip
Delay
(SEC)
Trip Point Settings
Multiple
10 75 50
PROGRAMMING
(CONTINUED)
TRIP DELAY TIME ON
This value controls the delay time in seconds that the flow rate must exceed the Trip Flow Rate before the next tank will come on line.
TRIP FLOW RATE ON
This value controls the flow rate that must be exceeded before the next tank will come on line.
TRIP FLOW RATE OFF
This value controls the flow rate limit that the actual flow must be less than before the tank will come off-line. The default delay time is 5 minutes
and is not adjustable.
TRIP DELAY TIME OFF MULTIPLE
This value controls the factor of time (Trip Delay Time Sec x Multiple) for the Trip Flow Rate Off delay. i.e. Trip Delay On Time = 30 sec, Multiple = 10,
therefore Trip Delay Off Time = 600 sec
Press the UP / DOWN button to highlight the desired menu icon. Press the SET button to enter the Trip Point Settings. These settings determine
what flow rate will cause additional tanks to come on line to increase flow capacity.
Press the UP / DOWN button to highlight the desired menu icon. Press the SET button to enter the Peak Period Block Out settings. These settings
allow the user to block out two periods per day where a regeneration will not be allowed. At the end of a Peak Period, and units scheduled for
regeneration will start.
NOTE: It is not recommended to use this function with softener mode.