12
13
Chemical
Pump
Chemical Pump
Volume
100
GAL
Time On
10
SEC
CON BY AUX RELAY 1
Product Water Polish
Min Flow Rate
5
GPM
Time On
20
Sec
CON BY AUX RELAY 2
Product
Water Polish
Auxillary Outputs
Remote Start Switch 1 OFF
Remote Start Switch 1 OFF
AUX Relay 1 Chemical Pump
AUX Relay 2 Water Polish
PROGRAMMING
(CONTINUED)
Press the UP / DOWN button to highlight the desired menu icon. Press the SET button to enter the Chemical Pump menu. This setting will control
the Time On (Seconds) per Volume (Gallon) of water passed through the system.
Press the UP / DOWN button to highlight the desired menu icon. Press the SET button to enter the Product Water Polish menu. The Min Flow Rate
setting will control at what flow rate the Product Water Recycle Pump will turn on to recycle the water and avoid hardness
channelling through the bed.
The Time On function controls how long the Product Water Recycle Pump will turn on each time the tank comes into service. This will polish the
water and avoid any hardness to leak into the service line.
NOTE: For the Chemical Pump function or Product Water Polish function, the options must be selected the Auxiliary Out Put Menu.
Please refer to the Advance Programming section.