Cambridge Air Solutions
6
S-Series Technical Manual
1. Verify that the number of items on the Bill of
Lading matches the number of items received.
2. Check for shipping damage. Take photographs of
any damage.
IMPORTANT
If damage is found, immediately file a claim with the
carrier before proceeding further.
3. Check the items received to make sure they agree
with the ordering information including verification
of data on the unit nameplate.
IMPORTANT
Do not discard any components or accessories.
MOUNTING LOCATION
Verify feasibility of the installation location selected
with respect to accessibility to the heater for service
and maintenance functions. Ensure the positioning
of the heater does not inhibit fork truck operation,
storage rack locations, or other operations within
the facility. Ensure the heater inlet and outlet are not
blocked or severely restricted in any way that would
affect the rated airflow through the heater or affect the
desired air distribution pattern of the heater.
It is the responsibility of the installer to communicate
any potential problems with the installation to
the person or persons responsible for providing
the installation instructions or drawings prior to
proceeding with the installation.
IMPORTANT
Where the mounting height of the heater is a
consideration, work platforms or service lifts should
be provided for accessibility to the equipment for
service and maintenance activities.
IMPORTANT
Field constructed intake accessories should be
designed to minimize the entry of snow and rain.
IMPORTANT
The minimum clearance from the face of the
electrical control enclosure to surrounding
grounded surfaces for service activities is 42”.
Adequate clearance of 42” for burner removal is
also required. Access for service functions is also
required on the side of the unit opposite the control
enclosure for a distance of 24”.
INSTALLATION INSTRUCTIONS
UNCRATING INSTRUCTIONS