S-Series Technical Manual
43
Cambridge Air Solutions
B
D
C
A
Footprint Detail
Heater footprint
Leg base
12” sonotube center
12”sonotube
2 1/2”
2 1/2”
INSTALLATION INSTRUCTIONS
HORIZONTAL S-SERIES 4’ MOUNTING STAND
The horizontal S-Series mounting stand is suitable for outdoor pad mounted configurations. The 48” height is ideal
for easy maintenance access while still remaining high enough to avoid potential snow ingestion from the ground
during winter months. It is designed to be installed perpendicular to the building and includes room for both the unit
and upturn to be situ-ated on the frame. Additional support legs are provided if a filter section is ordered.
Parts List
Item
Description
Qty.
1
4’ mounting stand (assembled)
1
2
Leveling shims
20
Stand Size
Weight (lbs.)
(w/F.S. supports)
Stand Footprint
Anchor/Sonotube
Locations
A
B
C
D
S400/S800
330
25 3/8”
85 3/8”
20 1/4”
80 1/8”
S950/S1200/S1600
370
42”
100 1/8”
36 7/8”
95”
S1850/S2200/S3200
400
47”
117 1/2”
41 7/8”
112 3/8”
Note:
• The anchors’ mounting locations are centered on
the 12” sonotubes
Note:
• 2 additional support legs, brace, and fasteners are
also included when ordering a Filter Section with
a horizontal mounting stand
Horizontal Mounted
support
brackets (Qty 4)