S-Series Technical Manual
45
Cambridge Air Solutions
INSTALLATION INSTRUCTIONS
HORIZONTAL S-SERIES 4’ MOUNTING STAND
Only complete the following steps if installing a filter
section:
8. If attached, remove mounting bracket from filter
section. Any filters inside of the unit will need to be
removed before the next step to provide access to
internal mounting flange.
9. Lift the filter section into place at the inlet end of
heater. Secure by resting filter section onto unit’s
retaining bracket while using self tapping screws to
fasten the internal flange of the filter section the unit’s
front face.
10. Using the 2 additional filter section support legs,
brace, and provided fasteners to secure the filter
section to the mounting stand legs at the inlet side.
11. Seal all seams between accessories using appropriate
contractor grade caulk to mitigate potential water
ingestion and pressure loss.
bracket
stand
Heater
Heater
supports
bracket
stand
Heater
Heater
supports
bracket
stand
Heater
Heater
supports