Chapter 5: Installation
Mount the ODU, LPU and surge suppressor
Page
17
Caution
Do not attach grounding cables to the ODU mounting bracket bolts, as this arrangement
will not provide full protection.
Basic requirements
The following basic protection requirements must be implemented:
•
ODU must be in ‘Zone B’ (see
•
ODU must be grounded to the supporting structure.
•
A surge suppression unit must be installed on the outside of the building.
•
The distance between the ODU and Gigabit Surge Suppressor should be kept to a minimum.
•
The drop cable must not be laid alongside a lightning air terminal.
•
All grounding cables must be a minimum size of 10 mm
2
csa (8AWG), preferably 16 mm
2
csa
(6AWG), or 25 mm
2
csa (4AWG).