7
Recommissioning the heating system
Logano plus GB312 - Technical specifications are subject to change without prior notice
50
7.14.1 Switching the status display on the BC 10 to
show the boiler temperature
V
Press the
button to change the display to the next
status.
Current operating pressure
is displayed.
V
Press the
button to change the display to the next
status.
Operating status
(display code) is displayed.
V
Press the
button to change the display to the next
status.
Boiler temperature is displayed.
7.14.2 Returning to operating mode from the flue
gas test
V
Press the
button to cancel the flue gas test.
V
Switch the RC35 back to operating mode.
V
Close the flap on the RC35.
V
If the boiler is intended to be used with the Logamatic
4000 control system, remove the RC35 again. Switch
on the Logamatic 4000 control system.
7.14.3 Flue pressure
The required flue pressure for the flue/air supply system
installed must not be greater than 0.4 inches W.C.
V
If the flue pressure at maximum output is higher than
0.4 inches W.C., contact the relevant flue system plan-
ner and check the calculations and and design of the
flue/air supply system.
7.14.4 Carbon monoxide content
CO levels in the absence of air must be below 400 ppm
or 0.04% by vol.
Levels above 100 ppm indicate incorrect burner adjust-
ment, incorrect appliance settings, dirt in the burner or
heat exchanger or burner faults.
V
Identify and eliminate the fault.
Danger:
Risk of fatal injury due to poisoning
by escaping flue gas.
V
Only operate the boiler in conjunction with
a chimney flue or flue system (
Æ
Table 1,
page 12).