Troubleshooting
Logano plus GB312 - Technical specifications are subject to change without prior notice
80
B
6A
577
No flame detected
within the safety
period.
Ionization current
< 1.1 μA during
safety period.
Gas supply/dynamic
pressure too low.
Gas pressure regu-
lator not set to
required gas flow
rate.
Cross-sectional area
of gas pipe insuffi-
cient (min. cross-
sectional area of gas
supply pipe).
Air in gas pipe.
Flue back-pressure
too high due to
unfavourable config-
uration (too many
bends, cross-sec-
tion too small, too
long, horizontal runs
too long).
Ignition/ionization
electrode dirty.
Check connecting
lead between SAFe
and ionization elec-
trode for poor con-
tact, breaks and
damage.
Check electrode
gaps and ignition/
ionization electrode
for damage.
Check connecting
lead between igni-
tion transformer and
ignition electrode for
poor contact (at
electrode and trans-
former), breaks and
damage.
(to be continued
on next page)
If pressure too low,
inform gas com-
pany.
Fit gas pressure
regulator adjusted
to required gas flow
rate; inform gas
company if neces-
sary.
Fit adequately
dimensioned gas
piping.
Purging the gas
pipe.
Fit properly dimen-
sioned and config-
ured flue system.
Clean/replace igni-
tion/ionization elec-
trode.
Establish good
electrical contact.
Replace lead if nec-
essary.
Align burner rod/
electrode. Replace
defective electrode.
Establish good
electrical contact.
Replace lead if nec-
essary.
Type
1)
Display
code
Fault code Cause
Description
Testing
sequence/Cause
Action
Tab. 17 Fault messages
1) V = locking; B = inhibiting; BC = operating code