10
Troubleshooting
Logano plus GB312 - Technical specifications are subject to change without prior notice
82
B
8L
579
No gas pressure.
There is no gas
pressure.
(
Æ
Section 10.3,
page 88 ff.)
Check that the gas
cock is turned on.
Check that gas
pressure is present.
Check setting of low
pressure switch
(available sepa-
rately).
Check continuity on
SAFe pressure
switch, air supply
pressure switch, flue
gas pressure switch
and high gas pres-
sure switch (avail-
able separately)
If continuity OK on
SAFe, air supply
pressure, flue gas
pressure and high
gas pressure switch
Turn on gas cock if
necessary.
Measure gas pres-
sure.
Correct low pres-
sure switch (avail-
able separately)
settings.
If there is no conti-
nuity on SAFe pres-
sure switch:
– Check whether
manual gas cock
before Venturi is
open.
– Check connec-
tor on gas valve
is properly
seated.
– Replace pres-
sure switch.
If no continuity on
pressure/air supply
pressure/flue gas
pressure/high gas
pressure switch:
Replace pressure
switch concerned.
Replace low gas
pressure switch
and wiring.
Type
1)
Display
code
Fault code Cause
Description
Testing
sequence/Cause
Action
Tab. 17 Fault messages
1) V = locking; B = inhibiting; BC = operating code