Troubleshooting
Logano plus GB312 - Technical specifications are subject to change without prior notice
86
V
LL
571
Too many restarts
despite resetting.
15 directlly consec-
utive restarts have
taken place. In
other words, the
same problem was
still present after
resetting.
Important: this fault
can only be reset
by the button on
the SAFe.
Faults have continu-
ally been simply
reset and not recti-
fied.
Identify and elimi-
nate the cause of
the problem caus-
ing the resets.
V
EE
601
Flow temperature sen-
sor reading.
Successive flow
temperature read-
ings are too widely
divergent.
Check lead to boiler
sensor.
Check connector.
Check sensor read-
ings against table.
Check temperature
sensor voltage levels
against table.
Replace if dam-
aged.
If dirty, clean or
replace as neces-
sary.
If connector is
loose, reconnect
properly.
Replace tempera-
ture sensor if there
are discrepancies.
Replace SAFe if
there are discrep-
ancies.
V
EE
612
Return sensor read-
ing.
Successive return
temperature read-
ings are too widely
divergent.
Check lead to boiler
sensor.
Check connector.
Check sensor read-
ings against table.
Check temperature
sensor voltage levels
against table.
Replace if dam-
aged.
If dirty, clean or
replace as neces-
sary.
If connector is
loose, reconnect
properly.
Replace tempera-
ture sensor if there
are discrepancies.
Replace SAFe if
there are discrep-
ancies.
Type
1)
Display
code
Fault code Cause
Description
Testing
sequence/Cause
Action
Tab. 17 Fault messages
1) V = locking; B = inhibiting; BC = operating code