10
Troubleshooting
Logano plus GB312 - Technical specifications are subject to change without prior notice
87
V
EE
626
Electrode voltage
incorrect.
Voltage to ioniza-
tion electrode too
low.
Check connecting
lead between SAFe
and electrode for
breaks or damage.
Check electrode
gaps and electrode
for damage.
Check power supply
voltage at MC10
input (at least
102 V).
Check if voltage
dips are occurring
(e.g. when large
electrical consum-
ers are switched on)
Replace defective
lead or rectify
breaks.
Align burner rod/
electrode Replace
defective electrode.
Ensure power sup-
ply voltage is cor-
rect.
Eliminate voltage
dips.
If all checks OK,
replace SAFe.
Type
1)
Display
code
Fault code Cause
Description
Testing
sequence/Cause
Action
Tab. 17 Fault messages
1) V = locking; B = inhibiting; BC = operating code