10
Troubleshooting
Logano plus GB312 - Technical specifications are subject to change without prior notice
84
V
CY
566
Return temperature
< 23 °F (< -5 °C) (cir-
cuit break)
Control unit is
receiving implausi-
ble signals from
return sensor.
Check connecting
lead between SAFe
and return sensor.
Check electrical
connection of con-
necting lead to
SAFe.
Check resistance
levels of tempera-
ture sensor against
table.
Check voltage at
temperature sensor
terminals on SAFe
against table.
Replace connect-
ing lead if neces-
sary.
Rectify any contact
problems.
Replace tempera-
ture sensor if nec-
essary.
If temperature sen-
sor resistances are
correct but volt-
ages incorrect,
replace SAFe.
V
CY
567
Return temperature
> 266 °F (> 130 °C)
(short circuit)
Control unit is
receiving implausi-
ble signals from
return sensor.
Check connecting
lead between SAFe
and return sensor.
Check electrical
connection of con-
necting lead to
SAFe.
Check resistance
levels of tempera-
ture sensor against
table.
Check voltage at
temperature sensor
terminals on SAFe
against table.
Replace connect-
ing lead if neces-
sary.
Rectify any contact
problems.
Replace tempera-
ture sensor if nec-
essary.
If temperature sen-
sor resistances are
correct but volt-
ages incorrect,
replace SAFe.
V
CO
568
Water pressure sen-
sor fault (break in
cable).
Water pressure
sensor circuit break
(voltage > 3.5 V)
Check connection
between SAFe and
water pressure sen-
sor for poor con-
tact, breaks and
damage.
Check water pres-
sure sensor.
Establish good
electrical contact.
Replace lead if nec-
essary.
Replace water
pressure sensor.
V
CO
569
Water pressure sen-
sor fault (short circuit).
Water pressure
sensor short circuit
(voltage < 0.5 V).
Check connecting
lead to water pres-
sure sensor.
Check water pres-
sure sensor.
Rectify any short
circuits.
Replace water
pressure sensor.
Type
1)
Display
code
Fault code Cause
Description
Testing
sequence/Cause
Action
Tab. 17 Fault messages
1) V = locking; B = inhibiting; BC = operating code