6
Installing the boiler
Logano plus GB312 - Technical specifications are subject to change without prior notice
30
6.9.2
Connecting the boiler to the heating system
Fig. 23 Water connections
RK
Boiler return
VK
Boiler supply
6.9.3
Installing B-Kit
The pressure relief valve, the temperture/pressure gauge
and the non-return check valve are connected to the
boiler supply VK using the supply manifold (included in B-
kit).
V
Fit the B-kit including non-return check valve with the
direction of flow away from the boiler (observe arrow
on non-return valve).
V
Align the B-kit so that the temperature/pressure gauge
faces horizontally outwards to the side of the boiler and
the pressure relief valve points upwards (
Æ
Fig. 24).
V
Insert seal in flange joint and tighten evenly.
V
Fit and seal the pressure relief valve in the connection
provided using the NPT double union supplied
(
Æ
Figs. 23 and 24).
V
Fit and seal the temperature/pressure gauge in the
connection provided (
Æ
Fig. 24).
Any additional safety devices required can be fitted and
sealed in the remaining connections. Follow the manu-
facturers' instructions.
Fig. 24 Installing B-Kit
1
Nut and washer x 4
2
Non-return check valve x 1
3
Supply pipe (external)
4
Bolt x 4
5
Washer x 4
6
NPT thread (on external supply pipe)
7
Seal x 2
8
Seal x 1
9
Threaded flange, 2½" x 2½", NPT
10
Pressure relief valve (safety valve)
11
Pressure/temperature gauge
VK
Boiler supply
Caution:
Risk of system damage due to
leaking connections.
V
Connect up the connecting pipes to the
boiler in such a way that they are not under
stress.
Boiler
Boiler supply (VK)
Boiler return (RK)
90-4 to 280-8
2½" NPT
Tab. 9
Water connection sizes
7 747 010 720-22.2RS
VK
RK
Caution:
Risk of system damage due to in-
correctly fitted B-kit or failure to fit non-return
valve.
V
Make sure that the non-return check valve
is fitted correctly (observe arrow). The ar-
row indicates the direction of flow. The
non-return check valve prevents water
flow in the opposite direction to the arrow.
Fitting an automatic air vent to the B-kit on
the flow pipe is recommended.
VK
8
9
3
6
11
7
10
1
2
5 4
NPT
7 747 010 720-03.1RS