Low Cool Run Time:
Selectable from 0 to 120 minutes
d
Default = 5 minutes
S
High Cool Run Time:
Selectable from 0 to 120 minutes
d
Default = 5 minutes
6.4.5.
Heat Pump Heating
The heat pump heating mode can be exercised with this menu option. With a 2--stage
heat pump, a Low Heat and a High Heat Run Time are independently selectable to
exercise.
For variable speed heat pumps, you can select the speed at which the heat pump will
exercise.
For 18VS heat pumps, you can select the stage at which the heat pump will exercise.
During the checkout, the stage and time can be changed by pressing the Change button
on the checkout status screen.
After the selections are made, touch
START
.
NOTE
: Airflows during Checkout modes are fixed to the
EFFICIENCY
setting
and are independent of other airflow settings. To view airflows for normal air
conditioning cooling mode, exit the
CHECKOUT
screen and apply a heating
demand to the system.
S
Low Heat Run Time:
Selectable from 0 to 120 minutes
d
Default = 5 minutes
S
High Heat Run Time:
Selectable from 0 to 120 minutes
d
Default = 5 minutes
S
Speed (variable speed heat pump only):
Selectable from lowest available to 100%
d
Default = lowest available as specified by variable speed heat pump
S
Defrost:
Yes or No (For Geothermal Heat Pumps, this option is not available.)
d
Default = No
Summary of Contents for Evolution Connex SYSTXBBECC01-
Page 34: ...25 A12186 ...
Page 103: ...94 A160170 NIM Chart ...
Page 104: ...95 A160171 Wiring Diagram Single Stage Non Communicating Heat Pump NIM ...
Page 105: ...96 A160172 Wiring Diagram Two Stage Non Communicating Heat Pump NIM ...
Page 106: ...97 R G FE Fan Coil or Variable Speed Furnace A07114 G Input Wiring for Blower Operation ...
Page 107: ...98 R G FE Fan Coil or Variable Speed Furnace A07115 G Input Wiring for System Shutdown ...
Page 110: ...101 NOTES ...
Page 111: ......