20
5.4.1.
Hydronic Heat Application
The Evolution Connex Control supports two types of Hydronic Heat applications:
1. Hot water coil in combination with an FE fan coil and heat pump, or hot
water coil as sole heat source with an FE fan coil.
2. Non--zoned FE fan coil combined with radiant hot water heat.
In either application, a Hydronic Heat kit should be installed in place of an electric
heater. See FE fan coil Product Data for accessory part number. The system will
self--identify that hydronic heat has been installed during electric heater selection.
The system will treat the hot water coil as either auxiliary heat in a heat pump
application, or the sole heat source. Setup options for Hydronic Heat applications
are described in the setup section of this instruction.
NOTE
: The daily airflow verification test will take place even when the radiant
hydronic heat option is selected.
A13117
5.5.
Searching for SAM Module (If Applicable)
“Searching for SAM Module” will appear on the screen to determine if a System
Access Module, used for home automation only, is connected to the system.
The SYSTXBBSAM01 is not compatible with this control. The compatible modules
are SYSTXBBRCT01 and SYSTXBBRWF01. The SAM is used for home
Summary of Contents for Evolution Connex SYSTXBBECC01-
Page 34: ...25 A12186 ...
Page 103: ...94 A160170 NIM Chart ...
Page 104: ...95 A160171 Wiring Diagram Single Stage Non Communicating Heat Pump NIM ...
Page 105: ...96 A160172 Wiring Diagram Two Stage Non Communicating Heat Pump NIM ...
Page 106: ...97 R G FE Fan Coil or Variable Speed Furnace A07114 G Input Wiring for Blower Operation ...
Page 107: ...98 R G FE Fan Coil or Variable Speed Furnace A07115 G Input Wiring for System Shutdown ...
Page 110: ...101 NOTES ...
Page 111: ......