44
d
Default = US 2001--3000
S
Static Pressure selection:
0 to 10,000 feet. This value is used to correct the
static pressure readings the system performs.
6.3.3.7.
Furnace Dehumidifier Drain
This option selects the time the continuous fan turns off at the end of cooling in
order to drain the indoor coil of water. The fan will only be turned off if a
dehumidify demand existed at the start of or during the cooling cycle.
S
Dehumidify Drain Time:
Adjustable from 5 to 60 minutes
d
Default = 15 minutes
6.3.3.8.
Furnace G Terminal
This setup option selects desired operation when the R--G circuit changes state on
the furnace control board depending on setup.
Under the function option,
FAN
turns on fan to selected fan speed when G terminal
is energized.
SHUTDOWN
shuts off fan and equipment when initiated.
After the selections are made, touch
SAVE
.
S
Function
: Disabled, Fan or Shutdown
d
Default = Disabled
S
Fan Speed
: Low, Med, or High
d
Default = Low
S
Shutdown:
d
Normally Open
d
Normally Closed\
d
The shutdown function may not be immediate. Blower off delays, etc., will
still be used. The shutdown is not intended for commercial applications. If
immediate shutdown is required, provision must be made to remove power
to indoor unit.
Summary of Contents for Evolution Connex SYSTXBBECC01-
Page 34: ...25 A12186 ...
Page 103: ...94 A160170 NIM Chart ...
Page 104: ...95 A160171 Wiring Diagram Single Stage Non Communicating Heat Pump NIM ...
Page 105: ...96 A160172 Wiring Diagram Two Stage Non Communicating Heat Pump NIM ...
Page 106: ...97 R G FE Fan Coil or Variable Speed Furnace A07114 G Input Wiring for Blower Operation ...
Page 107: ...98 R G FE Fan Coil or Variable Speed Furnace A07115 G Input Wiring for System Shutdown ...
Page 110: ...101 NOTES ...
Page 111: ......