A160188B
6.3.7.1. Freeze Limits
This setting controls the temperature level to which the loop liquid can drop before
the Geo HP unit will stop operating. See the Geo HP Installation Instructions for
more details. Typically, 26
_
F is chosen for open--loop systems using untreated
water; and 15
_
F is chosen for closed--loop systems using glycol or other anti--freeze
solutions. After the selection is made, touch
SAVE
.
S
Freeze Limits:
26
_
F or 15
_
F
d
Default = 26
_
F