56
airflow;
HIGH
means 250% of maximum assessed airflow; and
NO LIMIT
means
the equipment does not stage down due to airflow, but the system may stage down
due to high static pressure.
CFM associated for each limit is shown on the screen. Compare this value with the
equipment’s low stage CFM value to ensure that equipment will run for each zone.
Assessed airflow is determined as described in
DUCT ASSESSMENT
.
After the selections are made, touch
SAVE
.
S
Touch the zone name that you wish to change
S
Select the zone to adjust airflow:
Low, Med--Low, Medium, Med--High, High,
or No Limit
d
Default = High
6.3.8.4.
Duct Assessment Time
NOTE
: The daily duct assessment will occur even if static pressure monitoring is
disabled. This is done to ensure that the system will continue to provide proper
airflow for all installed equipment, since duct system changes may occur at any
time, such as opened or closed registers.
This option allows the installer to select the time in which the duct assessment will
be performed. After the selection is made, touch
SAVE
.
S
Duct Assessment Time:
Selectable between 12 AM and 11PM
d
Default = 1 PM
6.3.9.
Accessories
First touch
SETUP
, then touch
ACCESSORIES
to set up the parameters for the
accessories installed with the system.
Summary of Contents for Evolution Connex SYSTXBBECC01-
Page 34: ...25 A12186 ...
Page 103: ...94 A160170 NIM Chart ...
Page 104: ...95 A160171 Wiring Diagram Single Stage Non Communicating Heat Pump NIM ...
Page 105: ...96 A160172 Wiring Diagram Two Stage Non Communicating Heat Pump NIM ...
Page 106: ...97 R G FE Fan Coil or Variable Speed Furnace A07114 G Input Wiring for Blower Operation ...
Page 107: ...98 R G FE Fan Coil or Variable Speed Furnace A07115 G Input Wiring for System Shutdown ...
Page 110: ...101 NOTES ...
Page 111: ......