55
A12191
6.3.8.1.
Disable Zoning
This option allows the installer to enable or disable zoning. After the selection is
made, touch
SAVE
.
S
Disable Zoning:
Yes or No
d
Default = No
6.3.8.2.
Zone Offsets
This option allows actual temperature offset for each zone, allowing calibration (or
deliberate miscalibration) of each sensor. Use the Left (<) or Right (>) buttons to
change the zone. After the selection is made, touch
SAVE
.
S
Temperature Offset:
Adjustable between --5 to 5
_
F (--3 to 3
_
C)
d
Default = 0
_
F
6.3.8.3.
Airflow Limits
Since a bypass damper is prohibited in this system, this setting is used to select the
maximum allowable noise/airflow relationship into each zone based on air noise
and comfort requirements.
LOW
means 100% of maximum assessed airflow;
MED--LOW
means 138% of maximum assessed airflow;
MEDIUM
means 176%
of maximum assessed airflow;
MED--HIGH
means 214% of maximum assessed