48
6.3.4.2.
Cooling Lockout
Outside temperature below which cooling will not be provided. After the selection
is made, touch
SAVE
.
S
Cooling Lockout Temp:
None, 45, 50 or 55 (
_
F)
d
Default = None
NOTE
: When simultaneous heating and cooling demand feature is on, the cooling
lockout shall be ignored.
6.3.4.3.
Defrost Interval
Time interval at which defrost cycles can occur on a heat pump.
AUTO
means the
defrost interval is optimized by the outdoor control. After the selection is made,
touch SAVE.
S
Set Defrost Interval:
30, 60, 90, 120 minutes or AUTO
d
Default = AUTO
NOTE
: See Heat Pump Installation Instructions for Defrost Timing Interval when
using AUTO Defrost.
6.3.4.4.
Low Ambient Cooling
Selecting
YES
will enable the low ambient cooling operation in the outdoor unit.
This setting is only available with communicating outdoor units and with Cooling
Lockout set to
NONE
. Low ambient kits are not needed with communicating
outdoor units. After the selection is made, touch
SAVE
.
S
Low Ambient Cooling:
Yes or No
d
Default = No
6.3.4.5.
Quiet Shift
This option turns on Quiet Shift function in 1--stage or 2--stage communicating heat
pumps. After the selection is made, touch
SAVE
.
Summary of Contents for Evolution Connex SYSTXBBECC01-
Page 34: ...25 A12186 ...
Page 103: ...94 A160170 NIM Chart ...
Page 104: ...95 A160171 Wiring Diagram Single Stage Non Communicating Heat Pump NIM ...
Page 105: ...96 A160172 Wiring Diagram Two Stage Non Communicating Heat Pump NIM ...
Page 106: ...97 R G FE Fan Coil or Variable Speed Furnace A07114 G Input Wiring for Blower Operation ...
Page 107: ...98 R G FE Fan Coil or Variable Speed Furnace A07115 G Input Wiring for System Shutdown ...
Page 110: ...101 NOTES ...
Page 111: ......