background image

15

PRE--START--UP

FIRE, EXPLOSION, ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal injury,

death or property damage.

1. Follow recognized safety practices and wear protective

goggles when checking or servicing refrigerant system.

2. Relieve and recover all refrigerant from system before

touching or disturbing compressor plug if refrigerant
leak is suspected around compressor terminals.

3. Do not remove compressor plug until all electrical

sources are disconnected and tagged.

4. Never attempt to repair soldered connection while

refrigerant system is under pressure.

5. Do not use torch to remove any component. System

contains oil and refrigerant under pressure.

To remove a component, wear protective goggles and
proceed as follows:

a. Shut off electrical power to unit and install lockout

tag.

b. Relieve and reclaim all refrigerant from system

using both high-- and low--pressure ports.

c. Cut component connecting tubing with tubing

cutter and remove component from unit.

d. Carefully unsweat remaining tubing stubs when

necessary. Oil can ignite when exposed to torch

flame.

!

WARNING

Use the Start--Up Checklist supplied at the end of this book and
proceed as follows to inspect and prepare the unit for initial

start--up:

1. Remove all access panels.
2. Read and follow instructions on all DANGER, WARNING,

CAUTION, and INFORMATION labels attached to, or

shipped with, unit.

3. Make the following inspections:

a. Inspect for shipping and handling damages such as

broken lines, loose parts, disconnected wires, etc.

b. Inspect for oil at all refrigerant tubing connections and

on unit base. Detecting oil generally indicates a
refrigerant leak. Leak--test all refrigerant tubing

connections using electronic leak detector, or
liquid--soap solution. If a refrigerant leak is detected, see

following Check for Refrigerant Leaks section.

c. Inspect all field and factory--wiring connections. Be sure

that connections are completed and tight. Ensure wires

do not touch refrigerant tubing or sharp sheet metal
edges.

d. Inspect coil fins. If damaged during shipping and

handling, carefully straighten fins with a fin comb.

4. Verify the following conditions:

a. Make sure that outdoor--fan blade is correctly positioned

in fan orifice.

b. Make sure that air filter(s) is in place.

c. Make sure that condensate drain pan and trap are filled

with water to ensure proper drainage.

d. Make sure that all tools and miscellaneous loose parts

have been removed.

5. Each unit system has 2 Schrader--type ports, one low--side

Schrader fitting located on the suction line, and one

high--side Schrader fitting located on the compressor
discharge line. Be sure that caps on the ports are tight.

START--UP

Checking Cooling and Heating Control Operation

Start and check the unit for proper control operation as follows:

(1.) Place room thermostat SYSTEM switch or MODE

control in OFF position. Observe that blower
motor starts when FAN mode is placed in FAN ON

position and shuts down when FAN MODE switch
is placed in AUTO position.

(2.) Thermostat:

When the room temperature rises to a point that is
slightly above the cooling control setting of the

thermostat, the thermostat completes the circuit
between thermostat terminal R to terminals Y, O

and G.These completed circuits through the
thermostat connect contactor coil (C) (through unit
wire Y) and Indoor Fan board (through unit wire

G) across the 24--v. secondary of transformer
(TRAN).

(3.) Place system switch or MODE control in HEAT

position. Set control above room temperature.
Observe that compressor, outdoor fan, and indoor

blower motors start. Observe that heating cycle
shuts down when control setting is satisfied.

(4.) When using an automatic changeover room

thermostat place both SYSTEM or MODE control
and FAN mode switches in AUTO positions.

Observe that unit operates in Cooling mode when
temperature control is set to “call for Cooling”

(below room temperature), and unit operates in
Heating mode when temperature control is set to

“call for Heating” (above room temperature).

NOTE

: Once the compressor has started and then has stopped, it

should not be started again until 5 minutes have elapsed. The
defrost board has a built--in 5 minute delay between cycles. The 5
minute compressor delay also applies to heat pump heating mode.

Step 1 — Check for Refrigerant Leaks

Proceed as follows to locate and repair a refrigerant leak and to
charge the unit:

1. Locate leak and make sure that refrigerant system pressure

has been relieved and reclaimed from both high-- and

low--pressure ports.

2. Repair leak following Refrigerant Service procedures.

NOTE

: Install a bi--flow filter drier whenever the system has been

opened for repair.

3. Add a small charge of R--410A refrigerant vapor to system

and leak--test unit.

4. Recover refrigerant from refrigerant system and evacuate to

500 microns if no additional leaks are not found.

5. Charge unit with Puron (R--410A) refrigerant, using an

electronic scale. Refer to unit rating plate for required

charge.

Step 2 — Start--Up Adjustments

Complete the required procedures given in the Pre--Start--Up

section before starting the unit. Do not jumper any safety devices
when operating the unit. Do not operate the unit in Cooling mode

when the outdoor temperature is below 40

_

F (4

_

C) (unless

accessory low--ambient kit is installed).

IMPORTANT

: Three--phase, scroll compressors are direction

oriented. Unit must be checked to ensure proper compressor
3--phase power lead orientation. If not corrected within 5 minutes,
the internal protector will shut off the compressor. The 3--phase
power leads to the unit must be reversed to correct rotation. When
turning backwards, the difference between compressor suction and
discharge pressures may be near zero.

607C

Summary of Contents for 607C024

Page 1: ...Piston 21 Pressure Switches 22 Loss of Charge Switch 22 High Pressure Switch 22 Copeland Scroll compressor Puron Refrigerant 22 C99062 Fig 1 Unit 607C Refrigerant System 22 Refrigerant 22 Compressor...

Page 2: ...The slab should extend approximately 2 in 51 mm beyond the casing on all 4 sides of the unit Do not secure the unit to the slab except when required by local codes Ground Mount The unit may be install...

Page 3: ...he brackets to the unit PROPERTY DAMAGE HAZARD Failure to follow this warning could result in personal injury death or property damage Rigging bracket MUST be under the rain lip to provide adequate li...

Page 4: ...4 A08084 Fig 2 607C024 030 Unit Dimensions 607C...

Page 5: ...5 A08085 Fig 3 607C036 060 Unit Dimensions 607C...

Page 6: ...c heaters require 90 degree elbow in supply duct WARNING When designing and installing ductwork consider the following 1 All units should have field supplied filters or accessory filter rack installed...

Page 7: ...BTyp Supply opening B x C Long Support D 445 16 Return opening B X C Insulated deck pan Short Support CTyp bracket 1126 mm C00076 UNIT SIZE CATALOG NUMBER A IN MM B IN MM C IN MM D IN MM 607C024 030...

Page 8: ...ield supplied 3 4 in PVC or field supplied 3 4 in copper pipe at outlet end of the 2 in 51 mm trap See Fig 11 Do not undersize the tube Pitch the drain trough downward at a slope of at least 1 in 25 m...

Page 9: ...rmostat through the control wiring inlet hole grommet Fig 2 and 3 and into the low voltage splice box Provide a drip loop before running wires through panel Secure and strain relief all wires so that...

Page 10: ...0 11x10 279x254 3 4 1400 11x10 279x254 3 4 1600 11x10 279x254 1 0 1750 11x10 279x254 1 0 HIGH PRESSURE SWITCH psig Cutout Reset Auto 650 15 420 25 LOSS OF CHARGE LOW PRESSURE SWITCH Liquid Line psig C...

Page 11: ...11 Duct Covers C00092 Fig 10 607C with Duct Covers On Shown with optional louvers 1 25 mm MIN 2 51 mm MIN TRAP OUTLET A08001 Fig 11 Condensate Trap 607C...

Page 12: ...12 A08024 Fig 12 Wiring Schematics 208 230 1 60 607C...

Page 13: ...13 A08025 Fig 13 Wiring Schematics 208 230 3 60 607C...

Page 14: ...14 A08026 Fig 14 Wiring Diagram 460 3 60 607C...

Page 15: ...the unit for proper control operation as follows 1 Place room thermostat SYSTEM switch or MODE control in OFF position Observe that blower motor starts when FAN mode is placed in FAN ON position and s...

Page 16: ...efrigerant leak refer to Check for Refrigerant Leaks section Indoor Airflow and Airflow Adjustments All 607C blower motors are factory wired for nominal cooling airflow operation at minimum external s...

Page 17: ...control which includes a field selectable time period DIP switch 1 and 2 on the board between defrost cycles of 30 60 90 or 120 minutes factory set at 60 minutes To initiate a forced defrost two optio...

Page 18: ...eplace the filter with the same dimensional size and type as originally installed See Table 1 for recommended filter sizes Inspect air filter s at least once each month and replace throwaway type or c...

Page 19: ...2292 2238 2158 2049 1935 1840 1732 1635 1513 Air delivery values are without air filter and are for dry coil See 607C Wet Coil Pressure Drop Table 1 Factory shipped cooling heat pump heating speed NOT...

Page 20: ...ith a mild detergent and water solution Rinse coils with clear water using a garden hose Be careful not to splash water on motors insulation wiring or air filter s For best results spray condenser coi...

Page 21: ...ontrols and wiring replace all the panels Start the unit and observe at least one complete cooling cycle to ensure proper operation If discrepancies are observed in operating cycle or if a suspected m...

Page 22: ...amic suction or discharge valves and it is more tolerant of stresses caused by debris liquid slugging and flooded starts The compressor is equipped with an internal pressure relief port The pressure r...

Page 23: ...evice wired into control circuit low voltage It shuts off the compressor if abnormally low pressures are present in the refrigeration circuit NOTE Because these switches are attached to refrigeration...

Page 24: ...driers with rated working pressures less than 600 psig S Do not leave Puron suction line filter driers in line longer than 72 hours S Do not install a suction line filter drier in liquid line S POE o...

Page 25: ...Defective run start capacitor overload or start relay Determine cause and replace Defective thermostat Replace thermostat Faulty condenser fan motor or capacitor Replace Restriction in refrigerant sys...

Page 26: ...OLTAGE __________________________________ COMPRESSOR AMPS_________________________________ INDOOR EVAPORATOR FAN AMPS___________ TEMPERATURES OUTDOOR CONDENSER AIR TEMPERATURE ___________DB RETURN AIR...

Reviews: