background image

17

A07794

Fig. 16 -- Interface Fan Board (IFB)

COMPRESSOR

ACCUMULATOR

OUTDOOR COIL

INDOOR COIL

LCS

LEGEND

HPS – High Pressure Switch

LCS – Loss of Charge Switch

Accurater

 ®

 Metering De vice

Arrow indicates direction of flo

  w

   Position

HP S

TXV in Bypass

Metering 
Position

C03012

Fig. 17 -- Typical Heat Pump Operation, Heating Mode

Step 3 — Defrost Control

Quiet Shift

Quiet Shift is a field--selectable defrost mode, which will eliminate

occasional noise that could be heard at the start of defrost cycle and
restarting of heating cycle. It is selected by placing DIP switch 3

(on defrost board) in ON position.
When Quiet Shift switch is placed in ON position, and a defrost is

initiated, the following sequence of operation will occur. Reversing
valve will energize, outdoor fan will turn off, compressor will turn

off for 30 sec and then turn back on to complete defrost. At the

start of heating after conclusion of defrost reversing valve will
de--energize, compressor will turn off for another 30 sec, and the

outdoor fan will stay off for 40 sec, before starting in the Heating
mode.

Defrost

The defrost control is a time/temperature control which includes a

field--selectable time period (DIP switch 1 and 2 on the board)
between defrost cycles of 30, 60, 90, or 120 minutes (factory set at

60 minutes). To initiate a forced defrost, two options are available
depending on the status of the defrost thermostat.
If defrost thermostat is closed, speed--up pins (J1) must be shorted
by placing a flat head screw driver in between for 5 sec and

releasing, to observe a complete defrost cycle. When the Quiet

Shift switch is selected, compressor will be turned off for two 30
sec intervals during this complete defrost cycle, as explained

previously. When Quiet Shift switch is in factory default OFF
position, a normal and complete defrost cycle will be observed.
If defrost thermostat is in open position, and speedup pins are

shorted (with a flat head screw driver) for 5 sec and released, a
short defrost cycle will be observed (actual length is dependent

upon the selected Quiet Shift position). When Quiet Shift switch is
in ON position, the length of defrost is 1 minute (30 sec

compressor off period followed by 30 sec of defrost with

compressor operation). On return to heating operation, compressor
will again turn off for an additional 30 sec and the outdoor fan for

40 sec. When the Quiet Shift is in OFF position, only a brief 30
sec. cycle will be observed.

607C

Summary of Contents for 607C024

Page 1: ...Piston 21 Pressure Switches 22 Loss of Charge Switch 22 High Pressure Switch 22 Copeland Scroll compressor Puron Refrigerant 22 C99062 Fig 1 Unit 607C Refrigerant System 22 Refrigerant 22 Compressor...

Page 2: ...The slab should extend approximately 2 in 51 mm beyond the casing on all 4 sides of the unit Do not secure the unit to the slab except when required by local codes Ground Mount The unit may be install...

Page 3: ...he brackets to the unit PROPERTY DAMAGE HAZARD Failure to follow this warning could result in personal injury death or property damage Rigging bracket MUST be under the rain lip to provide adequate li...

Page 4: ...4 A08084 Fig 2 607C024 030 Unit Dimensions 607C...

Page 5: ...5 A08085 Fig 3 607C036 060 Unit Dimensions 607C...

Page 6: ...c heaters require 90 degree elbow in supply duct WARNING When designing and installing ductwork consider the following 1 All units should have field supplied filters or accessory filter rack installed...

Page 7: ...BTyp Supply opening B x C Long Support D 445 16 Return opening B X C Insulated deck pan Short Support CTyp bracket 1126 mm C00076 UNIT SIZE CATALOG NUMBER A IN MM B IN MM C IN MM D IN MM 607C024 030...

Page 8: ...ield supplied 3 4 in PVC or field supplied 3 4 in copper pipe at outlet end of the 2 in 51 mm trap See Fig 11 Do not undersize the tube Pitch the drain trough downward at a slope of at least 1 in 25 m...

Page 9: ...rmostat through the control wiring inlet hole grommet Fig 2 and 3 and into the low voltage splice box Provide a drip loop before running wires through panel Secure and strain relief all wires so that...

Page 10: ...0 11x10 279x254 3 4 1400 11x10 279x254 3 4 1600 11x10 279x254 1 0 1750 11x10 279x254 1 0 HIGH PRESSURE SWITCH psig Cutout Reset Auto 650 15 420 25 LOSS OF CHARGE LOW PRESSURE SWITCH Liquid Line psig C...

Page 11: ...11 Duct Covers C00092 Fig 10 607C with Duct Covers On Shown with optional louvers 1 25 mm MIN 2 51 mm MIN TRAP OUTLET A08001 Fig 11 Condensate Trap 607C...

Page 12: ...12 A08024 Fig 12 Wiring Schematics 208 230 1 60 607C...

Page 13: ...13 A08025 Fig 13 Wiring Schematics 208 230 3 60 607C...

Page 14: ...14 A08026 Fig 14 Wiring Diagram 460 3 60 607C...

Page 15: ...the unit for proper control operation as follows 1 Place room thermostat SYSTEM switch or MODE control in OFF position Observe that blower motor starts when FAN mode is placed in FAN ON position and s...

Page 16: ...efrigerant leak refer to Check for Refrigerant Leaks section Indoor Airflow and Airflow Adjustments All 607C blower motors are factory wired for nominal cooling airflow operation at minimum external s...

Page 17: ...control which includes a field selectable time period DIP switch 1 and 2 on the board between defrost cycles of 30 60 90 or 120 minutes factory set at 60 minutes To initiate a forced defrost two optio...

Page 18: ...eplace the filter with the same dimensional size and type as originally installed See Table 1 for recommended filter sizes Inspect air filter s at least once each month and replace throwaway type or c...

Page 19: ...2292 2238 2158 2049 1935 1840 1732 1635 1513 Air delivery values are without air filter and are for dry coil See 607C Wet Coil Pressure Drop Table 1 Factory shipped cooling heat pump heating speed NOT...

Page 20: ...ith a mild detergent and water solution Rinse coils with clear water using a garden hose Be careful not to splash water on motors insulation wiring or air filter s For best results spray condenser coi...

Page 21: ...ontrols and wiring replace all the panels Start the unit and observe at least one complete cooling cycle to ensure proper operation If discrepancies are observed in operating cycle or if a suspected m...

Page 22: ...amic suction or discharge valves and it is more tolerant of stresses caused by debris liquid slugging and flooded starts The compressor is equipped with an internal pressure relief port The pressure r...

Page 23: ...evice wired into control circuit low voltage It shuts off the compressor if abnormally low pressures are present in the refrigeration circuit NOTE Because these switches are attached to refrigeration...

Page 24: ...driers with rated working pressures less than 600 psig S Do not leave Puron suction line filter driers in line longer than 72 hours S Do not install a suction line filter drier in liquid line S POE o...

Page 25: ...Defective run start capacitor overload or start relay Determine cause and replace Defective thermostat Replace thermostat Faulty condenser fan motor or capacitor Replace Restriction in refrigerant sys...

Page 26: ...OLTAGE __________________________________ COMPRESSOR AMPS_________________________________ INDOOR EVAPORATOR FAN AMPS___________ TEMPERATURES OUTDOOR CONDENSER AIR TEMPERATURE ___________DB RETURN AIR...

Reviews: