7
Gask et around
outer edge
Insulated
deck
pan
Gask et around
duct
S/A
R/A
HVAC
unit
base
*Gask eting
outer flange
Flashing field
supplied
Roofing material
field supplied
Cant str ip
field supplied
*Provided with roofcurb
Roof
Duct wo rk
field supplied
Insulation (field
supplied)
Roofcurb*
Wood nailer*
Gask eting
inner flange*
Scre w
(NO TE A)
Roof Curb for Small Cabinet
Note A: When unit mounting scre
w is used
,
retainer
must also be used.
HVAC
unit
base
*Gask eting
outer flange
Flashing field
supplied
Roofing material
field supplied
Cant str ip
field supplied
*Provided with roofcurb
Roof
Duct wo rk
field supplied
Insulation (field
supplied)
Roofcurb*
Wood nailer*
Gask eting
inner flange*
Scre w
(NOTE A)
Roof Curb for
Large Cabinet
Note A: When unit mounting scre
w is used
,
retainer bra cket
must also be used.
A
B Typ.
Supply opening
(B x C)
Long
Support
D
44
5
/
16
"
Return opening
(B X C)
Insulated
deck pan
Short
Support
C Typ.
bracket
(1126 mm)
C00076
UNIT SIZE
CATALOG
NUMBER
A
IN. (MM)
B
IN. (MM)
C
IN. (MM)
D
IN. (MM)
607C024--030
CPRFCURB006A00
8 (203)
11 (279)
16--1/2 (419)
28--3/4 (730)
CPRFCURB007A00
14 (356)
11 (279)
16--1/2 (419)
28--3/4 (730)
607C036--060
CPRFCURB008A00
8 (203)
16--3/16 (411)
17--3/8 (441)
40--1/4 (1022)
CPRFCURB009A00
14 (356)
16--3/16 (411)
17--3/8 (441)
40--1/4 (1022)
NOTES:
1.
Roof curb must be set up for unit being installed.
2. Seal strip must be applied, as required, to unit being installed.
4. Dimension in ( ) are in millimeters.
5. Roof curb is made of 16---gauge steel.
6. Attach ductwork to curb (flanges of duct rest on curb).
7. Insulated panels: 1---in. (25 mm) thick fiberglass 1 lb. density.
8. When unit mounting screw is used (see Note A), a retainer bracket must
be used as well. This bracket must also be used when required by code for
hurricane or seismic conditions. This bracket is available through Micrometl.
Fig. 5 -- Roof Curb Dimensions
607C
Summary of Contents for 607C024
Page 4: ...4 A08084 Fig 2 607C024 030 Unit Dimensions 607C...
Page 5: ...5 A08085 Fig 3 607C036 060 Unit Dimensions 607C...
Page 12: ...12 A08024 Fig 12 Wiring Schematics 208 230 1 60 607C...
Page 13: ...13 A08025 Fig 13 Wiring Schematics 208 230 3 60 607C...
Page 14: ...14 A08026 Fig 14 Wiring Diagram 460 3 60 607C...