9
D. AS A BUILT-IN FIREPLACE
The figures describe this stoves installation vented into either
a special chase built outside an outer wall or a false inside wall.
This is especially suited for new construction or remodeling. The
equipment compartment (sides and rear of the stove in fireplace)
must be enclosed per the applicable electrical standards. This
can be accomplished by the use of this units panel kit. NOTE:
Floor protection for Built-in raised hearths requires a continuous
sheet beneath to prevent the possibility of embers falling through
to the combustible floor if cracks or separation should occur in
the finished surface. This fireplace insert must be installed with a
continuous chimney liner of 3” or 4” (77 mm or 102 mm) diameter
extending from the fireplace insert to the top of the chimney. The
chimney liner must conform to the Class 3 requirements of CAN/
ULC-S635, Standard for Lining Systems for Extending Masonry or
Factory-Built Chimneys and Vents, or CAN/ULC-S640, Standard for
Lining Systems for New Masonry Chimneys. The existing fireplace
damper may be removed or locked into the open position. The chase
dimensions shown are minimums and must be maintained.
IF THE FIREPLACE HAS BEEN MODIFIED TO ACCOMMODATE THE
FIREPLACE INSERT A METAL TAG SHALL BE ATTACHED TO THE
FIREPLACE.
DO NOT USE MAKESHIFT COMPROMISES DURING INSTALLATION.
E. INSTALLATION IN TO A FACTORY BUILT (METAL) FIREPLACE
When installing into a factory built fireplace, the firebox must
accept the insert without modification other than removing bolted
or screwed together pieces such as smoke shelf/deflectors, ash
lips, screen or door tracks and damper assemblies. These items
must be reinstalled to restore the fireplace to its original operating
condition if the insert is removed and not replaced. The removal of
any part must not alter the integrity of the listed fireplace in any way.
In zero-clearance fireplace installations, when the fireplace opening
is above the floor or raised hearth, the adjustable “Z-C Legs” can
be used to bridge the gap between the hearth and stove bottom.
The factory built fireplace must be listed per UL 127. Installation
must include a full height listed chimney liner meeting type HT
requirements (2100° F) per 1777 (U.S.). The liner must be securely
attached to the insert flue collar and the chimney top. The damper
area must be sealed to prevent room air passage to chimney cavity.
Alteration of the fireplace in any manner is not permitted except
with the following exceptions:
• External trim pieces, which do not affect the operation of the
fireplace, may be removed proving they can be stored on or
within, the fireplace for re-assembly if the insert is removed.
• The fireplace damper may be removed to install the chimney
liner.
Circulating air chambers, louvers or cooling air inlet or outlet
ports (i.e. in a steel fireplace liner or metal heat circulator) shall
not be blocked. Means must be provided for removal of the insert
to clean the chimney flue. A permanent metal warning label must
be attached to the back wall of the fireplace opening stating the
following:
• “This fireplace has been altered to accommodate a fireplace
insert and should be inspected by a qualified person prior to
re-use as a conventional fireplace.”
• This label is available upon request.
Final approval is contingent on the authority having jurisdiction.
22”
8”
MIN
MANTLE
FACADE
OPENING
24”
34”
34” MIN
17”
MIN
RAISED HEAR
TH
19
18
SEE “INSERT INSTALLATIONS” FOR
PANEL SURROUND INSTALLATION
6”
MIN.
6”
MIN.
3”
MIN.
3”
MIN.
CHASE CAP
MANTLE
OVER 6”
FACING
6”
MAX
15”
ATTACH THE PANEL SURROUND
TO THE FACE OF THE FIREPLACE
WITH ONE SCREW
12”
MIN.
22”
MIN.
6”
MIN.
8”
MIN.
FLOOR PROTECTOR MUST BE
CONTINUOUS WITH NO JOINTS
RAISED HEARTH MUST BE BUILT
OF 8” HOLLOW CONCRETE BLOCKS.
IF CHOOSING TO VENT HORIZONTALLY THROUGH THE WALL, WE RECOMMEND
TERMINATING VERTICALLY WITH AN ADDITIONAL RUN OF AT LEAST 5 FEET.
*
LISTED
CHIMNEY
CAP
*
LISTED
THIMBLE
6”
24”
MIN.
EQUIPMENT
COMPARTMENT
(OPTIONAL
VE
RTI
CAL INS
TALL
ATION)
L-VENT ONLY
SIDING
5/8” SHEETROCK
(ENTIRE FACADE)
A1/4” (OR SMALLER)
WIRE MESH SCREEN
MUST BE INSTALLED IN
THIS INSTALLATION TO
COVER THE EQUIPMENT
COMPARTMENT.
OUTSIDE AIR MAY
BE DRAWN FROM
A VENTILATED
CRAWL SPACE.
OUTSIDE
AIR
LISTED CHIMNEY CAP
STORM COLLAR
VERTICAL
CAP
STORM COLLAR
COVER PLATE
(NON-COMBUSTIBLE)
SEAL WITH SILICONE.
3 OR 4 INCH L-VENT
OR STAINLESS STEEL
FLEXIBLE OR SINGLE
WALL PIPE
THE SMOKE SHELF
MAY BE REMOVED
12”
THE DAMPER
MAY BE
REMOVED
INTERNAL
BAFFLES
MAY BE
REMOVED
NOTE:
THE LOG SHELF,
SCREEN, AND
DOORS (IF PRESENT)
MUST BE REMOVED
THE METAL SIDES, FRAME
MEMBERS, OR OTHER
STRUCTURAL COMPONENTS
OF THE FACTORY BUILT
FIREPLACE MAY NOT BE
REMOVED OR ALTERED
THE
MASONRY
LINING MAY
NOT BE
REMOVED
USE THE
ZERO-CLEARANCE
SKIRT TO SUPPORT
THE INSERT ON
RAISED FIREPLACES
TO PREVENT
FIREPLACE
ODORS
FROM
ENTERING
THE HOME,
PAINT THE
INTERIOR OF
THE
FIREPLACE
WITH LATEX
PAINT