background image

9

D.  AS A BUILT-IN FIREPLACE
The figures describe this stoves installation vented into either 

a special chase built outside an outer wall or a false inside wall. 

This is especially suited for new construction or remodeling. The 

equipment compartment (sides and rear of the stove in fireplace) 

must be enclosed per the applicable electrical standards. This 

can be accomplished by the use of this units panel kit. NOTE: 

Floor protection for Built-in raised hearths requires a continuous 

sheet beneath to prevent the possibility of embers falling through 

to the combustible floor if cracks or separation should occur in 

the finished surface. This fireplace insert must be installed with a 

continuous chimney liner of 3” or 4” (77 mm or 102 mm) diameter 

extending from the fireplace insert to the top of the chimney. The 

chimney liner must conform to the Class 3 requirements of CAN/

ULC-S635, Standard for Lining Systems for Extending Masonry or 

Factory-Built Chimneys and Vents, or CAN/ULC-S640, Standard for 

Lining Systems for New Masonry Chimneys. The existing fireplace 

damper may be removed or locked into the open position. The chase 

dimensions shown are minimums and must be maintained. 

IF THE FIREPLACE HAS BEEN MODIFIED TO ACCOMMODATE THE 

FIREPLACE INSERT A METAL TAG SHALL BE ATTACHED TO THE 

FIREPLACE.
DO NOT USE MAKESHIFT COMPROMISES DURING INSTALLATION.

E.  INSTALLATION IN TO A FACTORY BUILT (METAL) FIREPLACE
When installing into a factory built fireplace, the firebox must 

accept the insert without modification other than removing bolted 

or screwed together pieces such as smoke shelf/deflectors, ash 

lips, screen or door tracks and damper assemblies. These items 

must be reinstalled to restore the fireplace to its original operating 

condition if the insert is removed and not replaced. The removal of 

any part must not alter the integrity of the listed fireplace in any way. 

In zero-clearance fireplace installations, when the fireplace opening 

is above the floor or raised hearth, the adjustable “Z-C Legs” can 

be used to bridge the gap between the hearth and stove bottom. 

The factory built fireplace must be listed per UL 127. Installation 

must include a full height listed chimney liner meeting type HT 

requirements (2100° F) per 1777 (U.S.). The liner must be securely 

attached to the insert flue collar and the chimney top. The damper 

area must be sealed to prevent room air passage to chimney cavity. 

Alteration of the fireplace in any manner is not permitted except 

with the following exceptions:
•  External trim pieces, which do not affect the operation of the 

fireplace, may be removed proving they can be stored on or 

within, the fireplace for re-assembly if the insert is removed.

•  The fireplace damper may be removed to install the chimney 

liner.

Circulating air chambers, louvers or cooling air inlet or outlet 

ports (i.e. in a steel fireplace liner or metal heat circulator) shall 

not be blocked. Means must be provided for removal of the insert 

to clean the chimney flue. A permanent metal warning label must 

be attached to the back wall of the fireplace opening stating the 

following:
•  “This fireplace has been altered to accommodate a fireplace 

insert and should be inspected by a qualified person prior to 

re-use as a conventional fireplace.”

•  This label is available upon request.
Final approval is contingent on the authority having jurisdiction.

   22”

8”

MIN

MANTLE

FACADE

OPENING

24”

34”

34” MIN

17”

 MIN

RAISED HEAR

TH

19 

 18 

SEE  “INSERT INSTALLATIONS” FOR

PANEL SURROUND INSTALLATION

6”

MIN.

6”

MIN.

3”

MIN.

3”

MIN.

CHASE CAP

MANTLE

 OVER 6”  

FACING

6” 

MAX

15”

ATTACH THE PANEL SURROUND 

TO THE FACE OF THE FIREPLACE 

WITH ONE SCREW

12”

MIN.

22”

MIN.

6”

MIN.

8”

MIN.

FLOOR PROTECTOR MUST BE

CONTINUOUS WITH NO JOINTS

RAISED HEARTH MUST BE BUILT

OF 8” HOLLOW CONCRETE BLOCKS.

IF CHOOSING TO VENT HORIZONTALLY THROUGH THE WALL,  WE RECOMMEND

TERMINATING VERTICALLY WITH AN ADDITIONAL RUN OF AT LEAST 5 FEET.

*

LISTED 

CHIMNEY

CAP

*

LISTED 
THIMBLE

6”

24”

MIN.

EQUIPMENT

COMPARTMENT

(OPTIONAL

 VE

RTI

CAL INS

TALL

ATION)

L-VENT ONLY

SIDING

5/8” SHEETROCK

(ENTIRE FACADE)

A1/4” (OR SMALLER) 

WIRE MESH SCREEN 

MUST BE INSTALLED IN 

THIS INSTALLATION TO 

COVER THE EQUIPMENT 

COMPARTMENT.

OUTSIDE AIR MAY 

BE DRAWN FROM 

A VENTILATED 

CRAWL SPACE.

OUTSIDE 

AIR

LISTED CHIMNEY CAP

STORM COLLAR

VERTICAL 

CAP

STORM COLLAR

COVER PLATE

(NON-COMBUSTIBLE)

SEAL WITH SILICONE.

3 OR 4 INCH L-VENT

OR STAINLESS STEEL

FLEXIBLE OR SINGLE

WALL PIPE

THE SMOKE SHELF

MAY BE REMOVED

12”

THE DAMPER

MAY BE 

REMOVED

INTERNAL 

BAFFLES

MAY BE 

REMOVED

NOTE:

THE LOG SHELF, 

SCREEN, AND

DOORS (IF PRESENT)

MUST BE REMOVED 

THE METAL SIDES, FRAME 

MEMBERS, OR OTHER 

STRUCTURAL COMPONENTS 

OF THE FACTORY BUILT 

FIREPLACE MAY NOT BE 

REMOVED OR ALTERED

THE 

MASONRY 

LINING MAY 

NOT BE 

REMOVED

USE THE 

ZERO-CLEARANCE 

SKIRT TO SUPPORT 

THE  INSERT ON 

RAISED FIREPLACES

TO PREVENT 

FIREPLACE 

ODORS 

FROM 

ENTERING 

THE HOME, 

PAINT THE 

INTERIOR OF 

THE 

FIREPLACE 

WITH LATEX 

PAINT 

Summary of Contents for SP22

Page 1: ...all Installation and Operating Directions Never use makeshift compromises during the installation of this appliance Contact your local building or fire officials about restrictions and installation in...

Page 2: ...e National Electrical Code ANSI NFPA 70 The authority having jurisdiction such as municipal building department fire department fire prevention bureau etc should be consulted before installation to de...

Page 3: ...osote Never try to repair or replace any part of the stove unless instructions are given in this manual All other work should be done by a trained technician Do not throw this manual away This manual...

Page 4: ...229 mm sidewall 28 712 mm 6 153mm 2 51 mm 2 51 mm ALCOVE CLEARANCES 36 915 mm max 48 1220 mm min WITH HORIZONTAL EXHAUST 38 966 mm min Backwall With Vertical Exhaust Stove Door Face Must Be Equal To...

Page 5: ...to leak smoke into the room through appliance and chimney connector joints An uncontrollable burn or excessive temperature indicates excessive draft Take into account the chimney s location to ensure...

Page 6: ...from the exhaust outlet to the rear center of the stove OPTION Install PL Vent elbow in place of clean out tee Locate stove Drop plumb bob to center of tee outlet mark point on ceiling Install ceiling...

Page 7: ...the top plate from step 3 with non hardening mastic Slip the storm collar over the pipe and while holding the pipe at the proper elevation affix the collar with a mini mum of three 1 4 7 mm stainless...

Page 8: ...th non hardening mastic Failure to properly seal may result in smoke spillage 4 Slide vent pipe and intake pipe if used up through the blanking plate hole leaving enough to pull back down 5 Set the in...

Page 9: ...er area must be sealed to prevent room air passage to chimney cavity Alteration of the fireplace in any manner is not permitted except with the following exceptions External trim pieces which do not a...

Page 10: ...TALLATION This stove is provided with a 6 foot 1 8 m grounded electrical cord extending from the rear of the stove We recommend connecting to a good quality surge protector that is plugged into a stan...

Page 11: ...for which the stove has been approved and will void all warranties The design incorporates automatic feed of the pellet fuel into the fire at a carefully prescribed rate Any additional fuel introduced...

Page 12: ...NOT OVERFILL HOPPER A tool has been provided to help with the following functions a Stirring pellets in hopper unlike liquids in a tank pellets do not drain evenly into the auger Bridging across the o...

Page 13: ...ON COULD RESULT d Attempts to achieve heat output rates that exceed heater design specifications can result in permanent damage to the heater e WARNING DURING THE START UP CYCLE 1 DO NOT OPEN THE VIEW...

Page 14: ...l not work properly SMOKE AND CO MONITORS Burning wood naturally produces smoke and carbon monoxide CO emissions CO is a poisonous gas when exposed to elevated concentrations for extended periods of t...

Page 15: ...r ton of pellets burned to determine if cleaning is necessary c Inspection and Removal The chimney connector and chimney should be inspected annually or per ton to determine if a creosote or fly ash b...

Page 16: ...latched and the gasket is sealing good If the stove has just a small hole for the ashes to fall through under the burnpot make sure the slider plate is in place to seal off the firebox floor Vent pip...

Page 17: ...back in If the stove comes on and works you need to replace the POF thermodisc This is for testing only DO NOT LEAVE THE THERMODISC BYPASSED Your blowers will never shut off and if the fire went out t...

Page 18: ...t switch has tripped or is defective Wait for the stove to cool for about 30 45 minutes It should now function normally If not use the owner s manual to locate the high limit thermodisc To test if the...

Page 19: ...ight at each setting after the stove has completed the startup cycle Make sure the times match the auger timing chart If the auger motor runs constantly the board is bad Combustion blower is not spinn...

Page 20: ...ns of other types of fuel being used stop using them immediately Power surge or brown out situation A power surge spike or voltage drop could cause the high limit switch to trip Check to see if a surg...

Page 21: ...WHITE WHITE WHITE HIGH TEMP THERMODISC GROUND PURPLE BLACK WHITE ORANGE ORANGE BLUE PINK YELLOW RED GRAY GRAY WHITE WHITE COMBUSTION BLOWER CONVECTION BLOWER WHT GND BLK POWER OUTLET DETAIL LOOKING FR...

Page 22: ...isc Surf Mt Low Limit POF 1 15 80683 Thermodisc Surface Mount 300 1 16 27034 FS Side Sheet Right 1 17 80607 Ignitor Cartridge 1 18 40494 Transition Blower 1 19 80641 Blower Exhaust 1 20 88100 Gasket E...

Page 23: ...23 REPLACEMENT PARTS 1 16 17 20 21 23 24 41 40 39 28 29 27 26 25 19 18 2 3 32 31 30 33 34 35 36 37 38 7 5 6 4 22 12 10 11 9 8 13 14 15...

Page 24: ..._____________________ Engineer Name ________________________________ License No ____________________________________ Company _____________________________________ Telephone No _______________________...

Page 25: ...ro de pi ce____________________________________________________________ 2 La description de la pi ce_______________________________________________________ 3 Le num ro de mod le_______________________...

Page 26: ..._______________ Service de 07 Date _____________________ Nom de l ing nieur ____________________________ N de licence _________________________________ Compagnie ___________________________________ N...

Page 27: ...ow Limit Pof 1 15 80683 Thermodisc Surface Mount 300 1 16 27034 FS Side Sheet Right 1 17 80607 Cartouche Ignitor 1 18 40494 Transition souffleur 1 19 80641 Souffleur chappement 1 20 88100 Joint d tanc...

Page 28: ...25 PI CES DE RECHANGE 1 16 17 20 21 23 24 41 40 39 28 29 27 26 25 19 18 2 3 32 31 30 33 34 35 36 37 38 7 5 6 4 22 12 10 11 9 8 13 14 15...

Page 29: ...ANC BLANC HIGH TEMP THERMODISQUE GROUND PURPLE BLACK BLANC ORANGE ORANGE BLEU ROSE JAUNE RED GRAY GRAY BLANC BLANC VENTILATEUR DE COMBUSTION CONVECTION VENTILATEUR BLANC GND BLK DETAIL DE PUISSANCE DE...

Page 30: ...t le po le Surtension ou panne secteur localis e Une surtension des pics ou des creux de secteur peuvent faire d clencher l interrupteur sur limite haute V rifiez qu un parasurtenseur prot ge bien le...

Page 31: ...s quence de voyant d alimentation en carburant pour chaque r glage apr s que le po le ait termin sa s quence de d marrage Assurez fois que les dur es correspondent au tableau de s quences de la vis s...

Page 32: ...plaque d inspection d axe de vis sans fin dans la tr mie pour pouvoir la voir Levez doucement tout droit l axe de vis de fa on ce que son extr mit sorte de la douille du bas de tr mie Ensuite tez les...

Page 33: ...llumeur au d marrage Il doit y avoir l int gralit du courant Si la tension est inf rieure la valeur int grale v rifiez le c blage Si le c blage est contr l bon la carte est d fectueuse UNE ODEUR DE FU...

Page 34: ...pouvoir le lever hors du po le Une fois l axe sorti inspectez le pour chercher des filets d form s des barbures ou des soudures cass es Enlevez toute mati re trang re qui pourrait avoir caus le bloca...

Page 35: ...bien ferm e et que le joint est bien tanche Si le po le a juste un petit trou pour que les cendres tombent en travers sous le pot de combustion v rifiez que la plaque coulissante est en pace pour fer...

Page 36: ...la quantit de d p t de cr osote est inversement proportionnelle la temp rature du feu Ainsi des nettoyages hebdomadaires seront peut tre n cessaires en p riode de temps doux alors que des nettoyages m...

Page 37: ...nchez l alimentation lectrique avant d intervenir sur le po le Nettoyage Au fil du temps des cendres ou de la poussi re peuvent s accumuler sur les soufflantes de combustion et de convection P riodiqu...

Page 38: ...NON FIX S OU D PLA ABLES COMME MEUBLES TENTURES JOUETS ETC AU MOINS 90 cm L CART D UN PO LE ALLUM i Maintenez une bonne ventilation Il est important qu une quantit ad quate d oxyg ne soit fournie au f...

Page 39: ...va d pendre de l altitude et des conditions climatiques Observez le fonctionnement du po le et ajustez le registre si n cessaire AVERTISSEMENT DE FALSIFICATION Ce chauffage au bois a un taux de combus...

Page 40: ...rrez votre po le le ventilateur d air de la pi ce ne s active pas avant que l changeur thermique se soit r chauff Cela prend en g n ral 10 minutes partir du d marrage RED MARRAGE D UN PO LE CHAUD Si l...

Page 41: ...tion de br lage de ces mat riaux n interdit pas l utilisation d allume feu compos s de papier carton sciure de bois cire et substances similaires aux fins de d marrer le feu dans un chauffage au bois...

Page 42: ...branchement sur un parasurtenseur de qualit lui m me branch sur une prise secteur standard trois broches en 120 V 60 Hz Des variations de tension peuvent causer de s rieux probl mes de performance Le...

Page 43: ...ur la paroi arri re du foyer avec cet avis Ce foyer a t modifi pour recevoir un insert de foyer et doit tre inspect par une personne qualifi e avant de pouvoir tre r utilis comme foyer conventionnel U...

Page 44: ...DE CANAL SONT DES MINIMA QUI DOIVENT TRE RESPECT S NE PAS RECOURIR DES M THODES DE FORTUNE OU DES COMPROMIS LORS DE L INSTALLATION 6 po 6 po MAX 15 po 12 po 3 po PLAQUE SUP RIEURE SCELLER DESSUS DE C...

Page 45: ...le A MONTAGE DU JEU DE SOLINS Suivez les instructions fournie avec le jeu de solins r f rence B TUBE DE VENTILATION D PASSANT DU HAUT DE CHEMIN E 1 Vous aurez besoin d une longueur de tuyau gale la h...

Page 46: ...a chemin e existante jusqu sa terminaison C est la m thode pr f rer Respectez les consignes pour la longueur quivalente de ventilation E VERTICALEMENT DANS UN FOYER EN MA ONNERIE EXISTANT REMARQUE Sui...

Page 47: ...s cumuler plus de 10 pi 3 m de longueur quivalente Il est recommand que les tron ons verticaux fassent au moins 8 pi 243 cm Pour calculer l EVL utilisez les conversions suivantes Coude 90 ou T 5 pieds...

Page 48: ...maisons mobiles seulement un tuyau de 2 po 51 mm de diam tre int rieur peut tre utilis pour les 5 premiers pieds 1 5 m de la conduite d alimentation en air de combustion De 5 10 pieds 1 5 m 3 m utili...

Page 49: ...horizontal 38 po 966 mm min ARRI RE Avec sortie vertocale Poele porte visage doit tre gale ou d passera de visage d alc ve 8 1 4 po 210 mm sommet 3 po 77 mm 1 po 26 mm 9 po 229 mm flanc 8 1 4 po 210 m...

Page 50: ...ais de r parer ou de remplacer une quelconque partie du po le sauf si des instructions pour le faire sont donn es dans ce manuel Toutes les autres interventions doivent tre faites par un technicien ag...

Page 51: ...rvice municipal pour la construction les pompiers le bureau de pr vention des incendies etc doit tre consult e avant l installation afin de d terminer le besoin d obtention d une autorisation Cet appa...

Page 52: ...struire Veuillez lire enti rement ce manuel d installation et d utilisation AVANT de mettre en place et de faire fonctionner votre nouveau po le granul s de bois pour chauffage de pi ce Le fait de ne...

Reviews: