1 Description
UPS (Uninterruptible Power Supply) is a device that allows continuity in the supply of loads in
alternating current, but also has protection and monitoring functions. The UPS plays a very
important role in the supply of computers and the computer network to which the computer is
possibly connected. The fields of application of UPS are numerous: communication, finance,
electricity, transport, national defense, universities, scientific research institutes and so on.
The Aquarius series from 1KVA to 3kVA, are products designed with the advanced ON-LINE UPS
technology, which provide the user with multiple functions and good performance.
1.1
Functions and features
1.
The latest generations of IGBTs have been used in our UPSs to provide reliability and high
performance. In general, the electronic components we have used are able to work normally for
more than 300,000 hours.
2.
Using digital technology associated with reliable algorithms, we have been able to create a
powerful and easy-to-use product.
3.
The self-test at the start-up of the apparatus, allows to find in advance, potential problems of the
UPS in order to be able to intervene and resolve the problem promptly.
4.
The on-line double conversion topology means that in the UPS output there is a sine wave with
constant voltage and frequency, low noise and without any type of interruption of energy supplied
to the load. All this guarantees the correct functioning of the equipment powered by our UPSs.
5.
The transfer time between the main source and the emergency source at the UPS exit is zero, when
the main power supply fails it is immediately replaced by the emergency power supply
6.
With the bypass function incorporated in the UPS, the energy is transferred to the loads without
any interruption. This feature is very useful when you need to perform maintenance on the UPS.
7.
Advanced voltage compensation technology leads to having the input voltage range from 115V to
295V, which reduces battery usage and improves the ability to adapt to changing network
conditions.
8.
The AC input frequency is 50Hz / 60Hz. When the output frequency is 50Hz, the AC input frequency
range is 45Hz-55Hz, when the output frequency is 60Hz, the AC input frequency range is 55Hz-
65Hz. The UPS has good compatibility with generators. It is suitable for different types of single-
phase generators.
9.
The advanced PFC (Power Factor Correction), a technology that leads to a power factor higher than
0.98 of the UPS, increasing its energy efficiency and removing harmonic distortion.
10.
The UPS starts up in battery mode, to be able to power the loads even in the absence of the mains.
When the battery voltage is low, the UPS protects itself and turns off automatically. When the main
power is restored, the UPS will detect its presence, checking that the voltage and frequency are in
the ranges. Once the input voltage is considered good, the UPS will automatically turn on to supply
loads; if the network is not considered good, the UPS will still start the charger to recharge the