7.2
Troubleshooting
Fault
Cause
Solution
The word "INPUT"
flashes on the display
Neutral and phase
reversed or Input voltage
out of range.
Connect the cables correctly.
Battery capacity
flashes.
Minimum battery voltage
or battery disconnection
Check the connections or battery status
Input voltage present,
but no output voltage
Open disconnector
Press the disconnector to reactivate it
Insufficient backup
time
Battery not fully charged
Connect the UPS to the mains for at least
8 hours.
UPS in overload
Check the loads and remove the least
significant ones.
Dated battery
Contact the Braga Moro service center
for battery replacement.
After pressing the ON
buttons the UPS does
not start.
The keys were not pressed
correctly
Press the ON buttons simultaneously
There is a problem with
the battery or there are too
many loads connected
Check the battery connection, if the
battery voltage is low, turn off the UPS
and remove loads and then start the UPS.
Fault in the UPS
Contact the Braga Moro service center.
The charger icon
flashes on the display
and the buzzer makes
a sound every second
The charger is not
working properly, or the
battery is dated
Contact the Braga Moro service center.