Illustration 2: Rear panel 

 

3.2

 

The principle of the product 

 

 

 

 

 

 

 

Illustration 3: Principle outline 

Summary of Contents for Aquarius Plus

Page 1: ...hts are reserved according to the law Reproducing or distributing this document to third parties without permission is prohibited BRAGA MORO SISTEMI DI ENERGIA S p A VIA LUDWIG VAN BEETHOVEN N 24 20092 CINISELLO BALSAMO MI Tel 39 02 51 67 22 01 Fax 39 02 51 67 22 13 mailto sales bragamoro com www bragamoro com USER MANULA AQUARIUS PLUS Da 1KVA a 3KVA Cosphi 0 9 ...

Page 2: ...g or distributing this document to third parties without permission is prohibited 1 DOCUMENT CHECK SECTION Drawing Written by Role Date Alessandri David Technical Staff 29 03 17 Control Control by Role Date Alessandri David Technical Staff 29 03 17 Approved Approved by Role Date Abbondio Adelio Technical Staff 29 03 17 Revision Rev Author Description Date B C D E F G H I L References Ref Author Ti...

Page 3: ...pletely It includes safety and operating installation instructions It will help your UPS get a longer service life This manual explains the principle of internal operation and the related protection functions This manual also contains information on the use of the equipment Please respect the instructions and all the warnings indicated in the manual or on the machine Do not use the machine before ...

Page 4: ... document to third parties without permission is prohibited General index 1 DOCUMENT CHECK SECTION 2 1 Preface 3 1 Description 5 2 Safety Instructions 7 3 Product presentation 8 4 Installation 11 5 Display operation and management 15 6 Maintenance 25 7 TROUBLESHOOTING 25 8 Reference standards 30 9 Electrical characteristics 30 10 Environmental conditions 31 11 Mechanical specifications Rack mounti...

Page 5: ... a sine wave with constant voltage and frequency low noise and without any type of interruption of energy supplied to the load All this guarantees the correct functioning of the equipment powered by our UPSs 5 The transfer time between the main source and the emergency source at the UPS exit is zero when the main power supply fails it is immediately replaced by the emergency power supply 6 With th...

Page 6: ...d by pressing two buttons on the control panel of the apparatus The content displayed on the interface is rich in measurements Alarms and statuses are easily controlled from the operator panel 14 It is possible to connect the UPS to a computer through an RS232 serial port A software must be installed on the PC that allows the intelligent management of most of the functionalities of the device 15 I...

Page 7: ...ds the nominal load 2 There are high capacity batteries in standard type UPSs Do not open the cover There is a danger of electric shock In case of maintenance or replacement of the internal battery please send it to the nearest UPS service center 3 A short circuit inside the UPS causes electric shock or possible fire Therefore do not place containers with liquid on top of the UPS so as not to caus...

Page 8: ...o the law Reproducing or distributing this document to third parties without permission is prohibited Dangerous Indicates the risk of serious injury or death or serious damage to the equipment Attention Indicates the risk of serious injury or damage to the equipment Warning Indicates risk of injury or equipment damage 3 Product presentation 3 1 Product appearance Illustration 1 front panel ...

Page 9: ...1 PUT9I1K5 DF19009A 05 04 19 9 di 32 PUT9I002 PUT9I003 MD03006C All rights are reserved according to the law Reproducing or distributing this document to third parties without permission is prohibited Illustration 2 Rear panel 3 2 The principle of the product Illustration 3 Principle outline ...

Page 10: ...inverter 4 DC AC inverter Converts the direct voltage DC to a stable alternating voltage AC output 5 Bypass When an overload or failure of the inverter occurs the UPS goes into bypass mode to supply loads 6 Charger the standard unit provides 1A while the long life charger provides 4A 7 Battery sealed lead acid batteries 8 Output Filter Completely filters the UPS output to provide clean energy for ...

Page 11: ...re flammable and corrosive gases and liquids The ambient temperature must be in a range between 0 C 40 C If the ambient temperature exceeds 40 C the nominal power decreases by 12 as the ambient temperature increases The maximum working temperature cannot be higher than 50 C The UPS must be placed in a sufficiently ventilated place 4 3 Mounting the brackets for the Tower mounted installation The pl...

Page 12: ...e Date Page Code PUT9I001 PUT9I1K5 DF19009A 05 04 19 12 di 32 PUT9I002 PUT9I003 MD03006C All rights are reserved according to the law Reproducing or distributing this document to third parties without permission is prohibited Illustration 6 mounting brackets for 2 3KVA ...

Page 13: ... parties without permission is prohibited 4 4 Mounting of rack mounting brackets The following illustrations show how to fix the brackets on the groups to perform a rack mount The screws SCREW A and B shown in illustration 9 are from M4 The fixing of the brackets must be carried out on both sides of the UPS Illustration 3 Fixing brackets for rack mounting Illustration 4 Fixing bracket Illustration...

Page 14: ... the precautions dictated by the safety rules at work in order to avoid accidents Pay attention to the battery polarity The red cable connects it with the positive of the battery and black cable connect it with the negative Please use insulated tools that comply with the occupational safety directives Do not place instruments or metal objects on the battery Note Before connecting the loads to the ...

Page 15: ...ing instructions contained in this without any special training 5 1 Button operation Buttons ON Press these two buttons for more than half a second to turn on the UPS Buttons OFF Press these two buttons for more than half a second to turn off the UPS TEST MUTE buttons Press the keys for more than 1 second in line mode or in economic mode the UPS will perform the auto test function Press the keys f...

Page 16: ...tting function 5 2 Function of the LED indicators Warning Red LED is on UPS is faulty For example overload beyond the allowed time inverter failure BUS failure high temperature etc Bypass Yellow LED on UPS is in alarm For example active bypass etc Battery Yellow LED on UPS is in alarm For example battery inverter power supply mode Inverter Green LED on UPS is normally powered from the mains or in ...

Page 17: ...phic section of battery capacity and load each box represents 20 of capacity As shown in the figure above the battery capacity is between 80 and 100 5 panels the load is between 40 and 60 3 panels When the UPS is overloaded the icon will flash when the battery capacity is too low or disconnected the icon will flash Fan Defines the fan status In case the fan is working properly the graph simulates ...

Page 18: ...e UPS will perform a self test The LEDs will turn on and off in a circular and orderly manner At the end of the initial test the device will be active and the Line Mode with the relative LED lit Starting the UPS in battery mode To start the UPS even in the absence of mains keep the ON key pressed for more than half a second When the time expires the inverter will start up The start up of the group...

Page 19: ...e pre test mode In case of pressure of the self test Mute for more than one second when the group is in Battery Mode the acoustic signal will be silenced 5 5 Parameter setting The UPS allows the modification of some parameters The changes can be implemented in any operating mode The application of the changes made to the group parameters will be checked by the software of the device before being s...

Page 20: ... to activate The activated functions have the word ON while the non active functions the word OFF To activate or deactivate the features press the button for two seconds After confirming the message ON or OFF will stop flashing To exit parameter modification keep the button pressed for at least two seconds 5 5 2 Bypass configuration Entering the parameter modification mode as described in the prev...

Page 21: ...button pressed for at least half a second The display will begin to flash To confirm the selection keep the key pressed for at least 2 seconds The word ON or OFF will stop flashing Pressing the button for another two seconds you return to the main menu 5 5 3 Output voltage setting optional NOTE Before changing the output voltage it is advisable to disconnect the load Entering the parameter modific...

Page 22: ...he selectable values are 208V 220V 230V and 240V to confirm the choice press the key for two seconds The numerical value of the voltage will stop flashing To return to the main menu press the key for two seconds 5 6 Display of the parameters To view the UPS parameters simply press the key or for half a second The parameters related to the input output battery and temperature will appear on the dis...

Page 23: ...ity 5 7 Run mode 5 7 1 Bypass mode The visual indications in Bypass mode are as follows The yellow LED on indicates that the UPS is in Bypass the sound signal emits a sound every two minutes even the red LED that signals an attention situation is on The display shows the measurements related to the load and the battery capacity Bypass mode is activated in the following conditions When the UPS is i...

Page 24: ...ignal every 4 seconds The Battery mode status remains until the input voltage is absent or out of limits 5 7 4 ECO mode The visual indications in ECO mode are as follows The green inverter LED and the yellow bypass LED are on The ECO mode status must first be activated secondly it remains until the input voltage remains in the ranges allowed by this mode If the input voltage exceeds the range allo...

Page 25: ...ries simply connect the UPS to the network The device will take care of protecting the batteries in case of excessive charge and in case of deep discharge 6 1 Battery maintenance 1 It is a good rule to perform a deep discharge and relative recharge every three or four months 2 If the batteries are placed in environments where high temperatures are present the discharge and recharge should be done ...

Page 26: ...s of the device it is necessary to know the following information 1 When the red LED on the front panel is lit there is a potential problem 2 If the acoustic signal is active a critical state is present 3 In the presence of one of the situations it is advisable to contact the Braga Moro customer service by sending an E mail to assistenza bragamoro com Specifying the following data Code and serial ...

Page 27: ...aw Reproducing or distributing this document to third parties without permission is prohibited 7 1 Alarm codes and related visual signals Appendix 1 Error codes Description Code Bus KO 00 19 Inverter KO 20 39 overtemperature 40 44 Short circuit 45 49 Overload 50 54 KO output relay 55 59 Input NTC KO 60 64 KO aux power supply 65 69 KO input fuses KO 70 74 Other 99 Appendices 2 Signalizing di state ...

Page 28: ...e limits Every second 4 Battery disconnection alarm Bypass mode Every 4 seconds Check if the battery switch is closed Inverter mode Every 4 seconds Check if the battery switch is closed Power on Six times Check if the battery switch is closed 5 Overload protection Overload warning in Line mode 2 per second Disconnect less important loads Protection for overload in Line mode Long sound Disconnect l...

Page 29: ...Press the disconnector to reactivate it Insufficient backup time Battery not fully charged Connect the UPS to the mains for at least 8 hours UPS in overload Check the loads and remove the least significant ones Dated battery Contact the Braga Moro service center for battery replacement After pressing the ON buttons the UPS does not start The keys were not pressed correctly Press the ON buttons sim...

Page 30: ...00W 1000VA 1800W 2000VA 2700W 3000VA Input Input type Single phase earth Voltage range 115 5VAC 295 5VAC Frequency range 45Hz 55Hz 50HZ 55Hz 65Hz 60HZ Power factor 0 98 ECO range Output voltage variation 20VAC Range Bypass 186VAC 252VAC Harmonic current 7 100 nonlinear load Output Output type Single phase earth Nominal voltages 208 220 230 240VAC Power factor 0 9 Voltage accuracy 2 Frequency Exit ...

Page 31: ... 72VDC 72VDC Battery number 2 4 6 Tipo batterie 12V 7AH airtight lead for standard UPS only Autonomy Full load 4 minutes For standard UPS only Charge current A 1 4 1 4 1 4 10 Environmental conditions Template 1KVA 3KVA Temperature 0 40 Humidity 0 95 without condensation Altitude 1500 m Storage temperature 25 55 11 Mechanical specifications Rack mounting 19 Model Dimension W D H mm Net Gross Weight...

Page 32: ...llowing smart cards can be installed in the UPS intelligent slot USB intelligent card SNMP card and relay card All these cards are hot plug and play USB intelligent card Useful to monitor the UPS and its parameters through the computer s USB port it is necessary to load the UPSILON2000 software on the PC to use this option WARNING If both the RS232 and the USB are installed on an UPS it is not pos...