INFORMATION:
This procedure must be carried out when a UPS with a generator (GE) is powered:
Turns on the GE, after it has started up and its output is stable in both frequency and voltage,
turn on the UPS.
After the UPS has turned on, connect the loads one at a time.
The power of the GE must be twice the power of the UPS.
Do not activate the ECO mode function if the GE output is not very stable.
6 Maintenance
Minimal maintenance is required for this series of UPSs. Battery batteries are hermetically sealed,
and only need to be charged properly in order to maintain the expected life. To charge the batteries,
simply connect the UPS to the network. The device will take care of protecting the batteries in case
of excessive charge, and in case of deep discharge.
6.1
Battery maintenance
1.
It is a good rule to perform a deep discharge and relative recharge, every three or four
months.
2.
If the batteries are placed in environments where high temperatures are present, the
discharge and recharge should be done every two months.
3.
On average, the expected life of sealed lead batteries varies from three to five years. During
periodic discharges / recharges, check the discharge / recharging times, should the batteries
shorten dramatically, they must be replaced as soon as possible by specialized personnel.
4.
It is advisable to replace all the batteries at once.
5.
ATTENTION: ALL MAINTENANCE ACTIVITIES MUST BE DONE BY SPECIALIZED
PERSONNEL AND FOLLOWING SAFETY REGULATIONS.
7 TROUBLESHOOTING
This chapter will describe the alarm codes that the user might encounter in the event of a UPS failure.
Read the manual carefully before performing any operations on the UPS.
ATTENTION: DANGEROUS VOLTAGES ARE PRESENT INSIDE THE APPARATUS.