4.5
UPS output input connection
the UPS to the mains and to the loads with the supplied power cable.
4.6
Connection to the high autonomy battery box
Attention:
Before installing the battery, make sure the UPS is turned off and its switch is open. Use all
the precautions dictated by the safety rules at work, in order to avoid accidents.
Pay attention to the battery polarity. The red cable connects it with the positive of the
battery "+" and black cable connect it with the negative "-".
Please use insulated tools that comply with the occupational safety directives. Do not place
instruments or metal objects on the battery.
Note:
Before connecting the loads to the UPS, open the relevant switches, then connect the cable
to power supply and finally turn on the loads one at a time.
To avoid damage, it is strictly forbidden to connect inductive loads such as motors,
fluorescent lamps and photocopiers to the UPS.
Connect the UPS to a device with overcurrent protection. The socket used must have a
ground connection.